Page 331
Section 8-2
Troubleshooting DRT1-AD04H Error
Probable cause
The AD converted data is 7FFF when the disconnection indicator is lit.
The Analog Input Terminal’s open-circuit detection function is activated when the input range is set to 1 to 5 V and the voltage drops below 0.8 V or the input range is set to 4 to 20 mA and the current drops below 3.2 mA. The converted data is set to FFFF when the open-circuit detection function is activated. The disconnection indicator will be lit at the same time. Check the Analog input’s cables for broken wires or incorrect wiring. When the input signal rises above 0.8 V or 3.2 mA, the converted data will automatically return to its normal range. The disconnection indicator will go out at the same time.
8-2-3
Temperature Input Terminal Troubleshooting Use the following table to troubleshoot problems in the Temperature Input Terminal.
Error Probable cause The temperature data is 7FFF when the dis- Check the temperature sensor cables for broken wires or incorrect wiring. connection indicator is lit. Check that input cables are wired properly. Check that the cold junction compensator is connected properly (applicable to the DRT1-TS04T only).
8-2-4
C200H I/O Link Unit Troubleshooting When an error occurs in the C200H I/O Link Unit and the error code is displayed by the 7-segment display, use the following table to troubleshoot the problem. If the error code is not shown on the 7-segment display, use the table under the heading Identifying Errors from Symptoms to troubleshoot the problem.
Identifying Errors from Seven-segment Display Display C0
C3
Probable cause
Possible remedy
Attempt was made to set the Link Area when the 1.Turn OFF bit 00 of the software switches. PLC is not in PROGRAM mode. 2.Switch the PLC’s operating mode to PROGRAM mode. 3.Turn ON bit 00 of the software switches again. Invalid setting values in Link Area. 1.Turn OFF bit 00 of the software switches. 2.Check the area settings, address settings, and size settings, and correct if necessary. 3.Turn ON bit 00 of the software switches again.
D9
Timeout error in communications with Master Unit. • The Master Unit is not operating. • The cables are not connected properly. • A source of noise is close to the Master Unit.
1.Check the status of the Master Unit. 2.Check that the DeviceNet communications cables are connected properly and that noise preventative measures have been taken. 3.If the error is not cleared after taking the above steps, restart the Unit.
E0
The Network’s communications power is not being supplied normally.
Check the Network’s power supply and wiring, and restart the Unit.
E4
The Unit’s Read/Write Area is set to default set- 1.Check that the area address settings for the SYSMAC tings with other Communications Units conBUS Masters, DeviceNet Masters, and DeviceNet nected. Slaves are not overlapping. 2.Set the Read/Write Area settings using bit 00 of the software switches. (If the settings are overlapping intentionally, the Unit will operate according to the Read/Write Area settings after setting this bit.) 3.Restart the Unit.
E6
The CPU Unit is mounted to a C200H or C200HS PLC.
316
Remount the CPU Unit to a C200HE, C200HG, or C200HX PLC, and restart the PLC.
Page 332
Section 8-2
Troubleshooting Display E8
Probable cause Internal non-volatile memory data error
Possible remedy 1.Set the Read/Write Area settings using bit 00 of the software switches. 2.Restart the Unit. 3.If the error is not cleared, replace the Unit.
F0
Duplicate node address error
F1
Bus Off error
Reset the node address to a number that is not used by another Unit, and restart the Unit. 1.Check that the DeviceNet communications cables are wired connected, and that noise preventative measures have been taken. 2.Restart the Unit.
Master Unit baud rate setting error
Make sure that the baud rate settings match and restart the Unit.
F3
Front/rear-panel DIP switch setting error • Pin 4 of front-panel DIP switch is ON. • Pins 1 and 2 of front-panel DIP switch are ON. • Pin 7 or 8 on rear-panel DIP switch is ON.
• Make sure pin 4 on the front panel, and pins 7 and 8 on the rear panel are turned OFF. • Turn ON or OFF pins 1 and 2 according to the correct baud rate setting.
F6
CPU Unit interface error from noise
Remove cause of noise and restart the Unit. If the error is not cleared, replace the C200H I/O Link Unit or the CPU Unit.
F9
Hardware error
1.Restart the Unit 2.If the error is not cleared, replace the Unit.
Identifying Errors from Symptoms Symptom The power is ON, but the Slave Unit’s indicators are all OFF.
Probable Cause CPU Unit error caused by noise interference.
Possible remedy Restart the Unit.
The Read/Write Area’s settings have been set, but data is not being refreshed according to the settings.
The settings have not been validated.
1.Turn ON bit 00 of the software switches. 2.Reset the Unit. Restart the PLC or turn ON and OFF the Unit’s Restart Bit. With C200HX/ HG/HE PLCs, these bits are in AR 01. With CS-series PLCs, these bits are in words A502 to A507. Check the area settings of other Communications Units, and correct settings so that data is not written to an area already being used by another Unit.
The Unit has not been reset.
After setting the areas and operating The area settings are overlapping with the Unit, the data in the output area fre- those of other Communications Units. quently appears as unexpected values. When reading the Slave’s DM Area from the Master, unstable values are returned and the data is unreadable.
Attempt was made to access of words from DM 4096 onwards in the C200HE-CPU11 CPU Unit.
Access the correct words only.
The Explicit Connection Established Flag is ON in the C200H I/O Link Unit’s status words, but Unit is not receiving an explicit message from the Master.
The Network cables are disconnected, or the Master Unit’s power supply is OFF. (OMRON Master Units do not have timeouts when explicit message communications are used, so the Explicit Connection Established Flag will not turn OFF even if communications are stopped).
Restart the Master Unit, or connect the cables correctly. (Timeouts cannot be set for OMRON Master Units using explicit message communications.)
317
Page 333
Section 8-3
Maintenance
8-2-5
RS-232C Unit Troubleshooting
Symptom Probable cause The RS-232C Unit’s ERR indicator is lit. The RS-232C Unit is damaged.
Possible remedy Replace the RS-232C Unit.
RS-232C port communications error (the Unit’s RD and SD indicators are not lit).
The wiring is incorrect, or the cables are not connected properly. The RS-232C port’s parameters do not match those of the RS-232C Unit.
Check the wiring with the RS-232C Unit and correct it if necessary. Reset the RS-232C port’s parameters to match the parameters of the RS232C Unit.
Parameter Error Flag (bit 01 or 09) in communications status word is ON.
The parameters are set incorrectly.
Parity Error Flag (bit 04 or 12) in communications status word is ON.
The parity setting does not match the setting in the RS-232C Unit.
Overrun Error Flag (bit 05 or 13) in communications status word is ON.
The baud rate does not match the setting in the RS-232C Unit.
Framing Error Flag (bit 06 or 14) in communications status word is ON.
The character block settings (data length, parity, and stop bits) do not match those in the RS-232C Unit.
Reset the parameters correctly using the PARAMETER SET command, then execute the RS-232C PORT RESET command or restart the RS-232C Unit. Reset the RS-232C port’s parity setting to match the parity of the RS-232C Unit. Reset the RS-232C port’s baud rate to match the baud rate of the RS-232C Unit. Reset the RS-232C port’s character block (data length, parity, and stop bits) to match the character block of the RS232C Unit.
Receive Buffer Error Flag (bit 07 or 15) The receive buffer has overflowed. in communications status word is ON.
8-3
The receive buffer for each of the RS232C Unit’s ports is 1,024 bytes. Increase the reading frequency so that the receive buffer does not overflow. If the receive buffer has overflown, execute the RS-232C PORT RESET command or restart the RS-232C Unit.
Maintenance This section describes the routine cleaning and inspection recommended as regular maintenance.
8-3-1
Cleaning Clean the DeviceNet Units regularly as described below in order to keep it in its optimal operating condition. • Wipe the Unit with a dry, soft cloth for regular cleaning. • When a spot cannot be removed with a dry cloth, dampen the cloth with a neutral cleanser, wring out the cloth, and wipe the Unit. • A smudge may remain on the Unit from gum, vinyl, or tape that was left on for a long time. Remove the smudge when cleaning. !Caution Never use volatile solvents such as paint thinner or benzene or chemical wipes. These substances could damage the surface of the Unit.
8-3-2
Inspection Be sure to inspect the system periodically to keep it in its optimal operating condition. In general, inspect the system once every 6 to 12 months, but inspect more frequently if the system is used with high temperature or humidity or under dirty/dusty conditions.
318
Page 334
Section 8-3
Maintenance Inspection Equipment
Prepare the following equipment before inspecting the system. Required Equipment Have a standard and phillips-head screwdriver, multimeter, alcohol, and a clean cloth. Equipment that May be Required Depending on the system conditions, a synchroscope, oscilloscope, thermometer, or hygrometer (to measure humidity) might be needed.
Inspection Procedure
Check the items in the following table and correct any items that are below standard. Item
Standard
Equipment Thermometer Hygrometer
Environmental conditions
Ambient and cabinet temperature Ambient and cabinet humidity
See below. See below.
Installation
Dust/dirt accumulation Are the Units installed securely?
None --No looseness ---
Are the communications connectors fully inserted?
No looseness ---
Are the external wiring screws No looseness --tight? Are the connecting cables undam- No damage --aged?
8-3-3
Replacing Nodes The DeviceNet Master Unit and Slave Units make up the network. The entire network is affected when a Unit is faulty, so a faulty Unit must be repaired or replaced quickly. We recommend having spare Units available to restore network operation as quickly as possible.
Precautions
Observe the following precautions when replacing a faulty Unit. • After replacement make sure that there are no errors with the new Unit. • When a Unit is being returned for repair, attach a sheet of paper detailing the problem and return the Unit to your OMRON dealer. • If there is a faulty contact, try wiping the contact with a clean, lint-free cloth dampened with alcohol.
Settings after Replacing Nodes
After replacing a Unit, set the new Unit’s switches to the same settings that were on the old Unit.
319
Page 335
Page 336
Appendix A Node Address Settings Table This appendix shows all of the node address settings for Slaves that have node addresses set in binary with pins 1 through 6 of the Slave’s DIP switch. There are some differences in the location and orientation of the DIP switches, but the node address is always set in binary. (0: OFF, 1: ON) DIP switch setting
Node address
DIP switch setting
Node address
Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 0 0 0 0 0 0 0
Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 0 0 0 0 0 1 32
1 0
0 1
0 0
0 0
0 0
0 0
1 2
1 0
0 1
0 0
0 0
0 0
1 1
33 34
1 0
1 0
0 1
0 0
0 0
0 0
3 4
1 0
1 0
0 1
0 0
0 0
1 1
35 36
1 0
0 1
1 1
0 0
0 0
0 0
5 6
1 0
0 1
1 1
0 0
0 0
1 1
37 38
1 0
1 0
1 0
0 1
0 0
0 0
7 8
1 0
1 0
1 0
0 1
0 0
1 1
39 40
1 0
0 1
0 0
1 1
0 0
0 0
9 10
1 0
0 1
0 0
1 1
0 0
1 1
41 42
1 0
1 0
0 1
1 1
0 0
0 0
11 12
1 0
1 0
0 1
1 1
0 0
1 1
43 44
1 0
0 1
1 1
1 1
0 0
0 0
13 14
1 0
0 1
1 1
1 1
0 0
1 1
45 46
1 0
1 0
1 0
1 0
0 1
0 0
15 16
1 0
1 0
1 0
1 0
0 1
1 1
47 48
1 0
0 1
0 0
0 0
1 1
0 0
17 18
1 0
0 1
0 0
0 0
1 1
1 1
49 50
1 0
1 0
0 1
0 0
1 1
0 0
19 20
1 0
1 0
0 1
0 0
1 1
1 1
51 52
1 0
0 1
1 1
0 0
1 1
0 0
21 22
1 0
0 1
1 1
0 0
1 1
1 1
53 54
1 0
1 0
1 0
0 1
1 1
0 0
23 24
1 0
1 0
1 0
0 1
1 1
1 1
55 56
1 0
0 1
0 0
1 1
1 1
0 0
25 26
1 0
0 1
0 0
1 1
1 1
1 1
57 58
1 0
1 0
0 1
1 1
1 1
0 0
27 28
1 0
1 0
0 1
1 1
1 1
1 1
59 60
1 0
0 1
1 1
1 1
1 1
0 0
29 30
1 0
0 1
1 1
1 1
1 1
1 1
61 62
1
1
1
1
1
0
31
1
1
1
1
1
1
63
321
Page 337
Page 338
Appendix B Using Another Company’s Master Unit This appendix explains how to operate an OMRON Slave when the Slave is connected to a Master manufactured by another company.
Use Poll Connection with Output Slaves If the Slave has outputs, do not communicate with the Master through a bit strobe connection. There are several DeviceNet I/O communications methods, including poll and bit strobe connections, but DeviceNet specifications allow the bit strobe connection with inputs only. OMRON Master Units conform to these specifications and communicate with Output Slaves through a poll connection, but some other company’s Masters allow bit strobe connections with Output Slaves. Before connecting an OMRON Slave to another company’s Master, verify the Master’s connection specifications.
About EDS Files When connecting an OMRON Slave to another company’s Master, it may be necessary to install the OMRON Slave’s EDS file in the other company’s configurator to set the Slave’s information in the Master. With some companies’ Masters, the Slaves can be connected without making settings. With some other companies’ configurators, installing the OMRON Slave’s EDS file in the configurator will allow you to make various parameter settings from the configurator. If you can’t obtain a copy of the EDS file or the other company’s configurator does not support EDS files, it will be necessary to directly input settings such as the connection type and data size.
Installing an EDS File EDS files are provided by the manufacturer for each Slave and contain settings such as the Slave’s ID and I/O data sizes. If the EDS file is installed in the configurator, the Slave’s settings can be changed and the I/O size will be input automatically when the Master’s scan list is created. EDS files for the Slaves described in this manual can be downloaded from the product catalog at the following website: http://www.odva.astem.or.jp Locate the EDS file for the desired Slave and install that EDS file in the configurator. Installation procedures vary; refer to the configurator’s manuals for details on the installation procedure.
Inputting Settings Directly If you can’t obtain a copy of the EDS file or the other company’s configurator does not support EDS files, it will be necessary to directly input settings such as the connection type and data size. (Always select the connection type that is supported by the Slave.) The following connection types are allowed in DeviceNet communications. Connection type poll bit strobe change of state (COS)
cyclic
Operation
Remarks
Data is exchanged in individual command/ --response transmissions from the Master to each Slave. The output data is transferred in commands and the input data is received in responses. The Master broadcasts a command and multiple The command is sent just once, so the cycle time Slaves return input data in their responses. is short, however this method supports a maximum of 8 bytes of input data from Slaves. Data is transmitted when the data has changed in Data is transmitted only when there has been a the Master or Slave. change. Devices that do not need to communicate will not communicate, so the network usage is more efficient. The Master and Slaves transmit input/output data --cyclically (at fixed intervals).
323
Page 339
Appendix B
Using Another Company’s Master Unit Table of Connection Type and Data Size Settings
The following table lists the I/O data sizes for each OMRON Slave as well as the supported connection types. (A “Yes” indicates that the connection is supported; a “No” indicates that it is not.) Slave group
Model
Yes
Connection type bit change cyclic strobe of state Yes No No
1
0
DRT1-ID08-1 DRT1-ID16
Yes Yes
Yes Yes
No No
No No
1 2
0 0
DRT1-ID16-1 DRT1-OD08
Yes Yes
Yes No
No No
No No
2 0
0 1
DRT1-OD08-1 DRT1-OD16
Yes Yes
No No
No No
No No
0 0
1 2
DRT1-OD16-1 DRT1-MD16
Yes Yes
No No
No No
No No
0 1
2 1
Transistor Remote I/O Terminals DRT1-ID16T with 3-tier I/O Terminal Blocks DRT1-ID16T-1
Yes Yes
Yes Yes
No No
No No
2 2
0 0
DRT1-ID16TA DRT1-ID16TA-1
Yes Yes
Yes Yes
No No
No No
2 2
0 0
DRT1-OD16T DRT1-OD16T-1
Yes Yes
No No
No No
No No
0 0
2 2
DRT1-OD16TA DRT1-OD16TA-1
Yes Yes
No No
No No
No No
0 0
2 2
DRT1-MD16T DRT1-MD16T-1
Yes Yes
No No
No No
No No
1 1
1 1
DRT1-MD16TA DRT1-MD16TA-1
Yes Yes
No No
No No
No No
1 1
1 1
Transistor Remote I/O Terminals DRT1-ID32ML with Connectors DRT1-ID32ML-1
Yes Yes
Yes Yes
No No
No No
4 4
0 0
DRT1-OD32ML DRT1-OD32ML-1
Yes Yes
No No
No No
No No
0 0
4 4
DRT1-MD32ML DRT1-MD32ML-1
Yes Yes
No No
No No
No No
2 2
2 2
DRT1-ID16X DRT1-ID16X-1
Yes Yes
Yes Yes
No No
No No
2 2
0 0
DRT1-OD16X DRT1-OD16X-1
Yes Yes
No No
No No
No No
0 0
2 2
Sensor Terminals
DRT1-HD16S DRT1-ND16S
Yes Yes
Yes No
No No
No No
2 1
0 1
Temperature Input Terminals
DRT1-TS04T DRT1-TS04P
Yes Yes
Yes Yes
No No
No No
8 8
0 0
Analog Input Terminals
DRT1-AD04 DRT1-AD04H
Yes Yes
Yes Yes
No No
No No
8 8
0 0
Analog Output Terminals CQM1 I/O Link Unit
DRT1-DA02 CQM1-DRT21
Yes Yes
No No
No No
No No
0 2
4 2 poll Transistor Remote I/O Terminals DRT1-ID08
Remote Adapters
324
Data sizes IN OUT
Page 340
Appendix B
Using Another Company’s Master Unit Slave group
Model poll
Environment-resistive Transistor Terminals
Connection type bit change strobe of state cyclic
Data sizes IN OUT
DRT1-ID08C DRT1-HD16C
Yes Yes
Yes Yes
No No
No No
1 2
0 0
DRT1-HD16C-1 DRT1-OD08C
Yes Yes
Yes No
No No
No No
2 0
0 1
DRT1-WD16C DRT1-WD16C-1
Yes Yes
No No
No No
No No
0 0
2 2
DRT1-MD16C DRT1-MD16C-1
Yes Yes
No No
No No
No No
1 1
1 1
DRT1-ID04CL DRT1-ID04CL-1
Yes Yes
Yes Yes
No No
No No
1 1
0 0
DRT1-ID08CL DRT1-ID08CL-1
Yes Yes
Yes Yes
No No
No No
1 1
0 0
DRT1-OD04CL DRT1-OD04CL-1
Yes Yes
No No
No No
No No
0 0
1 1
DRT1-OD08CL DRT1-OD08CL-1
Yes Yes
No No
No No
No No
0 0
1 1
B7AC Interface Unit C200H I/O Link Unit
DRT1-B7AC C200HW-DRT21
Yes Yes
Yes Yes (See note 1.)
No No
No No
4 0 to 64 (See note 2.)
0 0 to 64 (See note 2.)
RS-232C Unit
DRT1-232C2
Yes
Yes
No
No
2
0
Waterproof Terminals
Note 1. The bit strobe connection is supported only when the output size is set to 0 bytes and the input size is set to 8 bytes. 2. The data sizes can be changed. 3. The device profiles below contain more detailed DeviceNet specifications if more information needs to be registered in the scan list.
Device Profiles for Regular and Environment-resistive Slaves The following device profiles contains more detailed DeviceNet specifications for General-purpose and Environment-resistive Slaves if more information needs to be registered in the scan list.l General data
Compatible DeviceNet Specifications
Volume I - Release 1.3 Volume II - Release 1.3 (See note)
Header name Device protocol name
OMRON Corporation Slaves: Generic
Manufacturer catalog number Manufacturer revision
W347 1.0
Header ID = 47 Protocol number = 0
325