Page 361

Appendix C

Connectable Devices and Device Current Consumptions

Special I/O Slave Units Model

Specifications

Manufacturer

C200HW-DRT21

I/O Link Unit for C200HE, C200HG, C200HX PLCs (User-set allocations possible) 512 inputs max, 512 outputs max. Read/Write Area can be user-set using explicit DeviceNet messages

OMRON

DRT1-232C2

RS-232C Unit with 2 RS-232C ports 16 inputs (communications status) RS-232C ports’ parameters can be set, and data can be transmitted to and from external devices using explicit DeviceNet messages

OMRON

Communications Cables Model

Specifications

DCA2-5C10 DCA1-5C10

Thick cable: 5 wires, 100 m Thin cable: 5 wires, 100 m

OMRON OMRON

DVN18-10G DVN18-30G

Thick cable: 5 wires, 10 m Thick cable: 5 wires, 30 m

Nihon Wire & Cable Nihon Wire & Cable

DVN18-50G DVN18-100G

Thick cable: 5 wires, 50 m Thick cable: 5 wires, 100 m

Nihon Wire & Cable Nihon Wire & Cable

DVN18-300G DVN18-500G

Thick cable: 5 wires, 300 m Thick cable: 5 wires, 500 m

Nihon Wire & Cable Nihon Wire & Cable

DVN24-10G DVN24-30G

Thin cable: 5 wires, 10 m Thin cable: 5 wires, 30 m

Nihon Wire & Cable Nihon Wire & Cable

DVN24-50G DVN24-100G

Thin cable: 5 wires, 50 m Thin cable: 5 wires, 100 m

Nihon Wire & Cable Nihon Wire & Cable

DVN24-300G DVN24-500G

Thin cable: 5 wires, 300 m Thin cable: 5 wires, 500 m

Nihon Wire & Cable Nihon Wire & Cable

1485C-P1-A50 1485C-P1-C150

Thick cable: 5 wires, 50 m Thin cable: 5 wires, 150 m

Allen-Bradley Allen-Bradley

DCA1-5CN@W1

Cable with round shielded connectors on both ends (one socket and one plug)

OMRON

DCA1-5CN@F1

Cable with round shielded connector (female socket) on one end Cable with round shielded connector (male plug) on one end

OMRON

DCA1-5CN@H1

Manufacturer

OMRON

Note 1. The cables made by Nihon Wire & Cable Company Ltd. are sold through the OMRON 24 Service Co., Ltd. The product specifications are identical to the OMRON cable specifications. 2. The cables made by Allen-Bradley are stiffer than the cables made by OMRON and Nihon Wire & Cable Company Ltd., so do not bend the Allen-Bradley cables as much as the others

346

Page 362

Appendix C

Connectable Devices and Device Current Consumptions

Connectors Model

Specifications

Manufacturer

MSTB2.5/5-ST-5.08AU

For node connection Phoenix Contact Without connector set screws GmbH & Co. (Included with the DRT1-@D08(-1), DRT1@D16(-1), DRT1-@D16X(-1), DRT1-@D16S(1), DRT1-AD04(H), DRT1-DA02, and DRT1TS04@)

XW4B-05C1-H1-D

For T-branch Tap and node connection With connector set screws (Included with the DRT1-@D16T(-1), DRT1-@D32ML(-1), CVM1-DRM21-V1, C200HW-DRM21-V1, CQM1-DRT21, and DCN1) For node connection (Multi-drop wiring) Without connector set screws

OMRON

For node connection (Multi-drop wiring) With connector set screws

OMRON

XW4B-05C4-T-D XW4B-05C4-TF-D

OMRON

Crimp Terminals for Communications Cables Remarks

Manufacturer

TC series: TME TC-0.5 (for thin cable) TME TC-2-11 (power supply wire for thick cable) TME TC-1.25-11 (communications wire for thick cable)

Model NH-32

Crimper

For single wire insertion

Nichifu Co., Ltd. (See note.)

AI series: AI-0.5-8WH-B (product number 3201369) AI series: AI-TWIN2×0.5-8WH (product number 3200933)

ZA3

For single wire insertion

Phoenix Contact GmbH & Co.

UD6 (product number For two-wire 1204436) insertion (Multi-drop use)

Note The solderless (crimp) terminals made by Nichifu Co., Ltd. are sold through the OMRON 24 Service Co., Ltd. Contact the Nichifu Co., Ltd. directly for details on their products.

Specialty Screwdrivers for Connectors Model XW4Z-00C SZF-1

Specifications

Manufacturer

Special screwdriver for DeviceNet connectors Special screwdriver for DeviceNet connectors

OMRON OMRON Tsufo Service

Model DRS1-T

Specifications Terminal-block Terminating Resistor, 121 Ω

Manufacturer OMRON

DRS2-1 DRS2-2

Shielded Terminating Resistor (male plug) Shielded Terminating Resistor (female socket)

Terminating Resistors

Note Also can be used as Terminating Resistor with T-branch Tap.

347

Page 363

Connectable Devices and Device Current Consumptions

Appendix C

T-branch Taps Model

Specifications

Manufacturer

DCN1-1C

3 connectors provided (When used on trunk line, 1 drop line can be connected.) Terminating Resistor can be connected.

OMRON

DCN1-3C

5 connectors provided (When used on trunk line, 3 drop lines can be connected.) Terminating Resistor can be connected.

OMRON

T-branch Connector Model DCN2-1

Specifications Shielded T-branch Connector (1 branch)

Manufacturer OMRON

Power Supply Sharing Taps Model 1485T-P2T5-T5

Specifications Manufacturer Required when connecting more than one power Allen-Bradley supply. Countercurrent flow prevention, ground terminal provided

DCN1-1P

One-branch tap for power supply. Use this tap when connecting a communications power supply. Two connectors and two fuses are standard.

OMRON

Note The Power Supply Sharing Taps are sold through the OMRON 24 Service Co., Ltd.

Connectors for I/O Cable Connections to Sensor Terminals Model XS8A-0441

Specifications Connector marking: XS8-1 Applicable cable wire size: 0.3 to 0.5 mm2

Manufacturer OMRON

XS8A-0442

Connector marking: XS8-2 Applicable cable wire size: 0.14 to 0.2 mm2

OMRON

Connectors for Environment-resistive Slaves DRT1-@D@@C (-1): I/O Connectors Model XS2G-D4@@ XS2H-D421-@@@ XS2W-D42@-@@@

348

Description Connector male plug assembly (Crimp-connect or soldered) Cable with connector on one end (Male plug on one end, cable wires on one end) Cable with connectors at both ends (Male plug on one end, female socket on one end)

Manufacturer OMRON

Page 364

Appendix C

Connectable Devices and Device Current Consumptions DRT1-@D@@C (-1): External Power Supply Connectors Model

Description

XS2C-D4@@

Female connector socket assembly (Crimp-connect or soldered)

XS2F-D42@-@80-A

Cable with connector on one end (Female socket on one end, cable wires on one end)

Manufacturer OMRON

DRT1-@D@@CL (-1): I/O Connectors Model XS2G-D4@@ XS2H-D421-@@@-@

Description Connector male plug assembly (Crimp-connect or soldered) Cable with connector on one end (Male plug on one end, cable wires on one end)

Manufacturer OMRON

XS2W-D42@-@@@-@ Cable with connectors at both ends (Male plug on one end, female socket on one end)

DRT1-@D@@CL (-1): External Power Supply Connectors Model

Description

Manufacturer

XS2C-D4@@

Female connector socket assembly OMRON (Crimp-connect or soldered) XS2F-D42@-@80-@ Cable with connector on one end (Female socket on one end, cable wires on one end) XS2W-D42@-@@@-@ Cable with connectors at both ends (Male plug on one end, female socket on one end)

DRT1-B7AC: I/O Connectors Model XS2G-D4@@

Description Connector male plug assembly (Crimp-connect or soldered)

Manufacturer OMRON

XS2H-D42@-@@@-@ Cable with connector on one end (Male plug on one end, cable wires on one end) XS2W-D42@-@@@-@ Cable with connectors at both ends (Male plug on one end, female socket on one end)

DRT1-B7AC: External Power Supply Connectors Model XS2C-D4@@

Description Manufacturer Female connector socket assembly OMRON (Crimp-connect or soldered) XS2F-D42@-@@@-@ Cable with connector on one end (Female socket on one end, cable wires on one end) XS2W-D42@-@@@-@ Cable with connectors at both ends (Male plug on one end, female socket on one end)

T-joint Model XS2R-D427-5

Description Shielded T-joint (Use to branch a cable for an Environment-resistive Terminal’s internal power supply.)

Manufacturer OMRON

Y-joint Plug/Socket Model XS2R-D426-@11F

With cable

XS2R-D426-1

Without cable

Description Manufacturer Use for Environment-resistive Ter- OMRON minals with 16 inputs or 16 outputs. (Branches a single connector’s signals to two connectors.)

349

Page 365

Appendix C

Connectable Devices and Device Current Consumptions

Connector Covers for Environment-resistive Slaves Model

Description

XS2Z-12 XS2Z-15

Manufacturer

Waterproof Cover (meets 1P67 standards) Dust Cover

OMRON

RS-232C Connectors for the RS-232C Unit Name

Model

Description

Manufacturer

Plug Hood

XM2D-0901 (or equivalent) XM2S-0913 (or equivalent)

9-pin, female 9-pin, SAE screws

OMRON

Recommended cable

UL2464 AWG28×5P IFS-RVV-SB AWG28×5P IFVV-SB

UL listed

Fujikura

UL2464-SB 5P×AWG28 CO-MA-VV-SB 5P×AWG28

UL listed Not UL listed

Not UL listed Hitachi

Bracket for Remote I/O Terminal with Connector Model SRT2-ATT02

Description Mounting bracket B

Manufacturer OMRON

MIL Cables for Remote I/O Terminal with Connector Cables with Connectors on Both Ends (40-pin on One End, Two 20-pins on One End) Model

Compatible Slaves

G79-I50-25-D1 (50 cm) G79-I75-50-D1 (75 cm)

DRT1-ID32ML DRT1-OD32ML-1

G7TC-ID16, G7TC-IA16 G7TC-OC16-4, M7F

Compatible Terminals

G79-I50-25-D2 (50 cm) G79-I75-50-D2 (75 cm)

DRT1-ID32ML-1

G70A-ZIM16-5

G79-O50-25-D1 (50 cm) G79-O75-50-D1 (75 cm)

DRT1-OD32ML

G7TC-OC08/OC16, G70D-SOC16/VSOC16, G70A-ZOC16-3

DRT1-OD32ML-1

G70A-ZOC16-4, G70D-SOC16-1

G79-M50-25-D1 (50 cm) G79-M75-50-D1 (75 cm)

DRT1-MD32ML

Inputs: G7TC-ID16/IA16 Outputs: G7TC-OC08/ OC16, G7OD-SOC16/VSOC16, G70A-ZOC16-3

G79-M50-25-D2 (50 cm) G79-M75-50-D2 (75 cm)

DRT1-MD32ML-1

Inputs: G70A-ZIM16-5 Outputs: G70A-ZOC16-4, G70D-SOC16-1

Manufacturer OMRON

Cables with Connector on One End (40-pin on One End, WIres on One End) Model Description G79-A200C-D1 (2 m) Loose wire gauge: 28 AWG G79-A500C-D1 (5 m) (Wires are just cut.) G79-Y100C-D1 (1 m) Fork terminals are attached to all of the loose wires. G79-Y200C-D1 (2 m) Fork terminal model number: 161071-M2 G79-Y500C-D1 (5 m)

350

Manufacturer OMRON

Page 366

Appendix C

Connectable Devices and Device Current Consumptions Flat Cable Crimp Connector Model XG4M-4030-T

Description For cable with 28 AWG wires

Manufacturer OMRON

Loose WIre Crimp Connectors Name

Model

Description

Manufacturer

Socket

XG5M-4032-N XG5M-4035-N

For cable with 24 AWG wires For cable with 28 to 26 AWG wires

Partial Cover Hood Cover

XG5S-2001 XG5S-2002

Two are required for each connector Cannot be used together with DeviceNet Connectors for multi-drop wiring.

OMRON

Current Consumption Summary Model

Internal current consumption

Communications current consumption

DRT1-ID08 DRT1-ID08-1

50 mA max. 50 mA max.

30 mA max. 30 mA max.

DRT1-ID16 DRT1-ID16-1

50 mA max. 50 mA max.

30 mA max. 30 mA max.

DRT1-OD08 DRT1-OD08-1

50 mA max. 50 mA max.

30 mA max. 30 mA max.

DRT1-OD16 DRT1-OD16-1

50 mA max. 50 mA max.

30 mA max. 30 mA max.

DRT1-MD16 DRT1-ID16T

50 mA max. 90 mA max.

25 mA max. 30 mA max.

DRT1-ID16T-1 DRT1-ID16TA

90 mA max. (See note.)

30 mA max. 50 mA max.

DRT1-ID16TA-1 DRT1-OD16T

(See note.) 90 mA max.

50 mA max. 30 mA max.

DRT1-OD16T-1 DRT1-OD16TA

90 mA max. (See note.)

30 mA max. 50 mA max.

DRT1-OD16TA-1 DRT1-MD16T

(See note.) 90 mA max.

50 mA max. 30 mA max.

DRT1-MD16T-1 DRT1-MD16TA

90 mA max. (See note.)

30 mA max. 50 mA max.

DRT1-MD16TA-1 DRT1-ID32ML

(See note.) (See note.)

50 mA max. 50 mA max.

DRT1-ID32ML-1 DRT1-OD32ML

(See note.) (See note.)

50 mA max. 90 mA max.

DRT1-OD32ML-1 DRT1-MD32ML

(See note.) (See note.)

90 mA max. 70 mA max.

DRT1-MD32ML-1 DRT1-ID16X

(See note.) 70 mA max.

70 mA max. 30 mA max.

DRT1-ID16X-1 DRT1-OD16X

70 mA max. 70 mA max.

30 mA max. 30 mA max.

DRT1-OD16X-1 DRT1-HD16S

70 mA max. 60 mA max.

30 mA max. 40 mA max.

DRT1-ND16S DRT1-AD04

60 mA max. 80 mA max.

40 mA max. 30 mA max.

351

Page 367

Appendix C

Connectable Devices and Device Current Consumptions Model

Internal current consumption

DRT1-AD04H

130 mA max.

Communications current consumption 30 mA max.

DRT1-DA02 DRT1-TS04T

140 mA max. 130 mA max.

30 mA max. 30 mA max.

DRT1-TS04P CQM1-DRT21

130 mA max. 80 mA max. (at 5 V DC, supplied from the PLC’s Power Supply Unit)

30 mA max. 40 mA max.

CPM1A-DRT21

50 mA max. (at 5 V DC, supplied from the PLC’s CPU Unit.)

30 mA max.

Note The internal power supply and communications power supply are shared.

Environment-resistive Slaves Model

Internal current consumption

Communications current consumption

DRT1-ID04CL DRT1-ID04CL-1

(See note.) (See note.)

25 mA max. 25 mA max.

DRT1-ID08CL DRT1-ID08CL-1

(See note.) (See note.)

30 mA max. 30 mA max.

DRT1-ID08C DRT1-HD16C

50 mA max. 50 mA max.

30 mA max. 30 mA max.

DRT1-HD16C-1 DRT1-OD04CL

50 mA max. (See note.)

30 mA max. 35 mA max.

DRT1-OD04CL-1 DRT1-OD08CL

(See note.) (See note.)

35 mA max. 40 mA max.

DRT1-OD08CL-1 DRT1-OD08C

(See note.) 50 mA max.

40 mA max. 30 mA max.

DRT1-WD16C DRT1-WD16C-1

60 mA max. 60 mA max.

30 mA max. 30 mA max.

DRT1-MD16C DRT1-MD16C-1

50 mA max. 50 mA max.

30 mA max. 50 mA max.

DRT1-B7AC

500 mA max.

70 mA max.

Note The internal power supply and communications power supply are shared.

Special-purpose Slaves Model

352

Internal current consumption

Communications current consumption

C200HW-DRT21

250 mA max. (Supplied from the Backplane)

45 mA max.

DRT1-232C2

100 mA max.

50 mA max.

Page 368

Appendix D Precautions when Connecting Two-wire DC Sensors When using a two-wire sensor with a 12-V DC or 24-V DC input device, check that the following conditions have been met. Failure to meet these conditions may result in operating errors.

Relation between Slave with Transistor Inputs and Sensor Residual Voltage VON ≤ VCC – VR VCC:

I/O power supply voltage (The allowable power supply range is 20.4 to 26.4 V, and thus 20.4 V will be used to allow for the worst possible conditions.)

VON:

ON voltage for a Slave with Transistor Inputs

VR:

Sensor’s output residual voltage

ON Current for Slave with Transistor Inputs and Sensor Control Output (Load Current) IOUT (min) ≤ ION ≤ IOUT (max.) IOUT: Sensor control output (load current) ION:

Slave ON current ION = (VCC – VR – VF)/RIN VF: RIN:

Internal residual voltage of Slave Input impedance of Slave

When ION is smaller than IOUT (min), connect a bleeder resistor R. The bleeder resistor constant can be calculated as follows: R ≤ (VCC – VR)/(IOUT (min.) – ION) Power W ≥ (VCC – VR)2/R × 4 [allowable margin] 2-wire sensor

VR

R

RIN

Slave with Transistor Input

VCC

Relation between OFF Current of Slave with Transistor Inputs and Sensor Leakage Current IOFF ≥ Ileak IOFF: OFF current of Slave Ileak: Leakage current of Slave Connect a breeder resistor if Ileak is greater than IOFF. Use the following equation to calculate the breeder resistance constant. R ≤ (IOFF x RIN + VF)/(Ileak – VOFF) Power W ≥ (VCC – VR)2/R × 4 [allowable margin]

353

Page 369

This page is a scan with no text; see it in the PDF.

Page 370

Glossary Busoff

A Busoff error occurs when there is an unacceptably high error rate on the communications bus. This error is detected when the internal error counter exceeds a specified value. (The error counter is cleared whenever the Master Unit is started or reset.)

CAN

Controller Area Network. A communications protocol for a LAN developed for mounting in automobiles. The DeviceNet uses CAN technology.

configurator

A device used to make system settings, read IDs, read/write parameters, read the network configuration, etc. OMRON provides a DeviceNet Configurator for OMRON Master Units.

consumed connection size

The size in bytes of the data received through a connection.

ODVA

Open DeviceNet Vendor Association. A non-profit vendor association responsible for spreading DeviceNet.

produced connection size

The size in bytes of the data sent through a connection.

connection

A logical communications channel created to communicate between two nodes. Connections are established and maintained between masters and slaves.

device profile

A description of the structure and behavior of a device giving the minimum data configurations and operations that the device must support. Device profiles enable common device models, and are also called device models. Device profiles are being studied for sensors, valves, displays, encoders, and other devices.

master

A node that controls the collection and distribution of data. With the DeviceNet, the predefined master/slave connection set defines the functions provided by all masters.

slave

A node that provides data in response to requests from masters. With the DeviceNet, the predefined master/slave connection set defines the functions provided by all slaves.

355