Page 361
Appendix C
Connectable Devices and Device Current Consumptions
Special I/O Slave Units Model
Specifications
Manufacturer
C200HW-DRT21
I/O Link Unit for C200HE, C200HG, C200HX PLCs (User-set allocations possible) 512 inputs max, 512 outputs max. Read/Write Area can be user-set using explicit DeviceNet messages
OMRON
DRT1-232C2
RS-232C Unit with 2 RS-232C ports 16 inputs (communications status) RS-232C ports’ parameters can be set, and data can be transmitted to and from external devices using explicit DeviceNet messages
OMRON
Communications Cables Model
Specifications
DCA2-5C10 DCA1-5C10
Thick cable: 5 wires, 100 m Thin cable: 5 wires, 100 m
OMRON OMRON
DVN18-10G DVN18-30G
Thick cable: 5 wires, 10 m Thick cable: 5 wires, 30 m
Nihon Wire & Cable Nihon Wire & Cable
DVN18-50G DVN18-100G
Thick cable: 5 wires, 50 m Thick cable: 5 wires, 100 m
Nihon Wire & Cable Nihon Wire & Cable
DVN18-300G DVN18-500G
Thick cable: 5 wires, 300 m Thick cable: 5 wires, 500 m
Nihon Wire & Cable Nihon Wire & Cable
DVN24-10G DVN24-30G
Thin cable: 5 wires, 10 m Thin cable: 5 wires, 30 m
Nihon Wire & Cable Nihon Wire & Cable
DVN24-50G DVN24-100G
Thin cable: 5 wires, 50 m Thin cable: 5 wires, 100 m
Nihon Wire & Cable Nihon Wire & Cable
DVN24-300G DVN24-500G
Thin cable: 5 wires, 300 m Thin cable: 5 wires, 500 m
Nihon Wire & Cable Nihon Wire & Cable
1485C-P1-A50 1485C-P1-C150
Thick cable: 5 wires, 50 m Thin cable: 5 wires, 150 m
Allen-Bradley Allen-Bradley
DCA1-5CN@W1
Cable with round shielded connectors on both ends (one socket and one plug)
OMRON
DCA1-5CN@F1
Cable with round shielded connector (female socket) on one end Cable with round shielded connector (male plug) on one end
OMRON
DCA1-5CN@H1
Manufacturer
OMRON
Note 1. The cables made by Nihon Wire & Cable Company Ltd. are sold through the OMRON 24 Service Co., Ltd. The product specifications are identical to the OMRON cable specifications. 2. The cables made by Allen-Bradley are stiffer than the cables made by OMRON and Nihon Wire & Cable Company Ltd., so do not bend the Allen-Bradley cables as much as the others
346
Page 362
Appendix C
Connectable Devices and Device Current Consumptions
Connectors Model
Specifications
Manufacturer
MSTB2.5/5-ST-5.08AU
For node connection Phoenix Contact Without connector set screws GmbH & Co. (Included with the DRT1-@D08(-1), DRT1@D16(-1), DRT1-@D16X(-1), DRT1-@D16S(1), DRT1-AD04(H), DRT1-DA02, and DRT1TS04@)
XW4B-05C1-H1-D
For T-branch Tap and node connection With connector set screws (Included with the DRT1-@D16T(-1), DRT1-@D32ML(-1), CVM1-DRM21-V1, C200HW-DRM21-V1, CQM1-DRT21, and DCN1) For node connection (Multi-drop wiring) Without connector set screws
OMRON
For node connection (Multi-drop wiring) With connector set screws
OMRON
XW4B-05C4-T-D XW4B-05C4-TF-D
OMRON
Crimp Terminals for Communications Cables Remarks
Manufacturer
TC series: TME TC-0.5 (for thin cable) TME TC-2-11 (power supply wire for thick cable) TME TC-1.25-11 (communications wire for thick cable)
Model NH-32
Crimper
For single wire insertion
Nichifu Co., Ltd. (See note.)
AI series: AI-0.5-8WH-B (product number 3201369) AI series: AI-TWIN2×0.5-8WH (product number 3200933)
ZA3
For single wire insertion
Phoenix Contact GmbH & Co.
UD6 (product number For two-wire 1204436) insertion (Multi-drop use)
Note The solderless (crimp) terminals made by Nichifu Co., Ltd. are sold through the OMRON 24 Service Co., Ltd. Contact the Nichifu Co., Ltd. directly for details on their products.
Specialty Screwdrivers for Connectors Model XW4Z-00C SZF-1
Specifications
Manufacturer
Special screwdriver for DeviceNet connectors Special screwdriver for DeviceNet connectors
OMRON OMRON Tsufo Service
Model DRS1-T
Specifications Terminal-block Terminating Resistor, 121 Ω
Manufacturer OMRON
DRS2-1 DRS2-2
Shielded Terminating Resistor (male plug) Shielded Terminating Resistor (female socket)
Terminating Resistors
Note Also can be used as Terminating Resistor with T-branch Tap.
347
Page 363
Connectable Devices and Device Current Consumptions
Appendix C
T-branch Taps Model
Specifications
Manufacturer
DCN1-1C
3 connectors provided (When used on trunk line, 1 drop line can be connected.) Terminating Resistor can be connected.
OMRON
DCN1-3C
5 connectors provided (When used on trunk line, 3 drop lines can be connected.) Terminating Resistor can be connected.
OMRON
T-branch Connector Model DCN2-1
Specifications Shielded T-branch Connector (1 branch)
Manufacturer OMRON
Power Supply Sharing Taps Model 1485T-P2T5-T5
Specifications Manufacturer Required when connecting more than one power Allen-Bradley supply. Countercurrent flow prevention, ground terminal provided
DCN1-1P
One-branch tap for power supply. Use this tap when connecting a communications power supply. Two connectors and two fuses are standard.
OMRON
Note The Power Supply Sharing Taps are sold through the OMRON 24 Service Co., Ltd.
Connectors for I/O Cable Connections to Sensor Terminals Model XS8A-0441
Specifications Connector marking: XS8-1 Applicable cable wire size: 0.3 to 0.5 mm2
Manufacturer OMRON
XS8A-0442
Connector marking: XS8-2 Applicable cable wire size: 0.14 to 0.2 mm2
OMRON
Connectors for Environment-resistive Slaves DRT1-@D@@C (-1): I/O Connectors Model XS2G-D4@@ XS2H-D421-@@@ XS2W-D42@-@@@
348
Description Connector male plug assembly (Crimp-connect or soldered) Cable with connector on one end (Male plug on one end, cable wires on one end) Cable with connectors at both ends (Male plug on one end, female socket on one end)
Manufacturer OMRON
Page 364
Appendix C
Connectable Devices and Device Current Consumptions DRT1-@D@@C (-1): External Power Supply Connectors Model
Description
XS2C-D4@@
Female connector socket assembly (Crimp-connect or soldered)
XS2F-D42@-@80-A
Cable with connector on one end (Female socket on one end, cable wires on one end)
Manufacturer OMRON
DRT1-@D@@CL (-1): I/O Connectors Model XS2G-D4@@ XS2H-D421-@@@-@
Description Connector male plug assembly (Crimp-connect or soldered) Cable with connector on one end (Male plug on one end, cable wires on one end)
Manufacturer OMRON
XS2W-D42@-@@@-@ Cable with connectors at both ends (Male plug on one end, female socket on one end)
DRT1-@D@@CL (-1): External Power Supply Connectors Model
Description
Manufacturer
XS2C-D4@@
Female connector socket assembly OMRON (Crimp-connect or soldered) XS2F-D42@-@80-@ Cable with connector on one end (Female socket on one end, cable wires on one end) XS2W-D42@-@@@-@ Cable with connectors at both ends (Male plug on one end, female socket on one end)
DRT1-B7AC: I/O Connectors Model XS2G-D4@@
Description Connector male plug assembly (Crimp-connect or soldered)
Manufacturer OMRON
XS2H-D42@-@@@-@ Cable with connector on one end (Male plug on one end, cable wires on one end) XS2W-D42@-@@@-@ Cable with connectors at both ends (Male plug on one end, female socket on one end)
DRT1-B7AC: External Power Supply Connectors Model XS2C-D4@@
Description Manufacturer Female connector socket assembly OMRON (Crimp-connect or soldered) XS2F-D42@-@@@-@ Cable with connector on one end (Female socket on one end, cable wires on one end) XS2W-D42@-@@@-@ Cable with connectors at both ends (Male plug on one end, female socket on one end)
T-joint Model XS2R-D427-5
Description Shielded T-joint (Use to branch a cable for an Environment-resistive Terminal’s internal power supply.)
Manufacturer OMRON
Y-joint Plug/Socket Model XS2R-D426-@11F
With cable
XS2R-D426-1
Without cable
Description Manufacturer Use for Environment-resistive Ter- OMRON minals with 16 inputs or 16 outputs. (Branches a single connector’s signals to two connectors.)
349
Page 365
Appendix C
Connectable Devices and Device Current Consumptions
Connector Covers for Environment-resistive Slaves Model
Description
XS2Z-12 XS2Z-15
Manufacturer
Waterproof Cover (meets 1P67 standards) Dust Cover
OMRON
RS-232C Connectors for the RS-232C Unit Name
Model
Description
Manufacturer
Plug Hood
XM2D-0901 (or equivalent) XM2S-0913 (or equivalent)
9-pin, female 9-pin, SAE screws
OMRON
Recommended cable
UL2464 AWG28×5P IFS-RVV-SB AWG28×5P IFVV-SB
UL listed
Fujikura
UL2464-SB 5P×AWG28 CO-MA-VV-SB 5P×AWG28
UL listed Not UL listed
Not UL listed Hitachi
Bracket for Remote I/O Terminal with Connector Model SRT2-ATT02
Description Mounting bracket B
Manufacturer OMRON
MIL Cables for Remote I/O Terminal with Connector Cables with Connectors on Both Ends (40-pin on One End, Two 20-pins on One End) Model
Compatible Slaves
G79-I50-25-D1 (50 cm) G79-I75-50-D1 (75 cm)
DRT1-ID32ML DRT1-OD32ML-1
G7TC-ID16, G7TC-IA16 G7TC-OC16-4, M7F
Compatible Terminals
G79-I50-25-D2 (50 cm) G79-I75-50-D2 (75 cm)
DRT1-ID32ML-1
G70A-ZIM16-5
G79-O50-25-D1 (50 cm) G79-O75-50-D1 (75 cm)
DRT1-OD32ML
G7TC-OC08/OC16, G70D-SOC16/VSOC16, G70A-ZOC16-3
DRT1-OD32ML-1
G70A-ZOC16-4, G70D-SOC16-1
G79-M50-25-D1 (50 cm) G79-M75-50-D1 (75 cm)
DRT1-MD32ML
Inputs: G7TC-ID16/IA16 Outputs: G7TC-OC08/ OC16, G7OD-SOC16/VSOC16, G70A-ZOC16-3
G79-M50-25-D2 (50 cm) G79-M75-50-D2 (75 cm)
DRT1-MD32ML-1
Inputs: G70A-ZIM16-5 Outputs: G70A-ZOC16-4, G70D-SOC16-1
Manufacturer OMRON
Cables with Connector on One End (40-pin on One End, WIres on One End) Model Description G79-A200C-D1 (2 m) Loose wire gauge: 28 AWG G79-A500C-D1 (5 m) (Wires are just cut.) G79-Y100C-D1 (1 m) Fork terminals are attached to all of the loose wires. G79-Y200C-D1 (2 m) Fork terminal model number: 161071-M2 G79-Y500C-D1 (5 m)
350
Manufacturer OMRON
Page 366
Appendix C
Connectable Devices and Device Current Consumptions Flat Cable Crimp Connector Model XG4M-4030-T
Description For cable with 28 AWG wires
Manufacturer OMRON
Loose WIre Crimp Connectors Name
Model
Description
Manufacturer
Socket
XG5M-4032-N XG5M-4035-N
For cable with 24 AWG wires For cable with 28 to 26 AWG wires
Partial Cover Hood Cover
XG5S-2001 XG5S-2002
Two are required for each connector Cannot be used together with DeviceNet Connectors for multi-drop wiring.
OMRON
Current Consumption Summary Model
Internal current consumption
Communications current consumption
DRT1-ID08 DRT1-ID08-1
50 mA max. 50 mA max.
30 mA max. 30 mA max.
DRT1-ID16 DRT1-ID16-1
50 mA max. 50 mA max.
30 mA max. 30 mA max.
DRT1-OD08 DRT1-OD08-1
50 mA max. 50 mA max.
30 mA max. 30 mA max.
DRT1-OD16 DRT1-OD16-1
50 mA max. 50 mA max.
30 mA max. 30 mA max.
DRT1-MD16 DRT1-ID16T
50 mA max. 90 mA max.
25 mA max. 30 mA max.
DRT1-ID16T-1 DRT1-ID16TA
90 mA max. (See note.)
30 mA max. 50 mA max.
DRT1-ID16TA-1 DRT1-OD16T
(See note.) 90 mA max.
50 mA max. 30 mA max.
DRT1-OD16T-1 DRT1-OD16TA
90 mA max. (See note.)
30 mA max. 50 mA max.
DRT1-OD16TA-1 DRT1-MD16T
(See note.) 90 mA max.
50 mA max. 30 mA max.
DRT1-MD16T-1 DRT1-MD16TA
90 mA max. (See note.)
30 mA max. 50 mA max.
DRT1-MD16TA-1 DRT1-ID32ML
(See note.) (See note.)
50 mA max. 50 mA max.
DRT1-ID32ML-1 DRT1-OD32ML
(See note.) (See note.)
50 mA max. 90 mA max.
DRT1-OD32ML-1 DRT1-MD32ML
(See note.) (See note.)
90 mA max. 70 mA max.
DRT1-MD32ML-1 DRT1-ID16X
(See note.) 70 mA max.
70 mA max. 30 mA max.
DRT1-ID16X-1 DRT1-OD16X
70 mA max. 70 mA max.
30 mA max. 30 mA max.
DRT1-OD16X-1 DRT1-HD16S
70 mA max. 60 mA max.
30 mA max. 40 mA max.
DRT1-ND16S DRT1-AD04
60 mA max. 80 mA max.
40 mA max. 30 mA max.
351
Page 367
Appendix C
Connectable Devices and Device Current Consumptions Model
Internal current consumption
DRT1-AD04H
130 mA max.
Communications current consumption 30 mA max.
DRT1-DA02 DRT1-TS04T
140 mA max. 130 mA max.
30 mA max. 30 mA max.
DRT1-TS04P CQM1-DRT21
130 mA max. 80 mA max. (at 5 V DC, supplied from the PLC’s Power Supply Unit)
30 mA max. 40 mA max.
CPM1A-DRT21
50 mA max. (at 5 V DC, supplied from the PLC’s CPU Unit.)
30 mA max.
Note The internal power supply and communications power supply are shared.
Environment-resistive Slaves Model
Internal current consumption
Communications current consumption
DRT1-ID04CL DRT1-ID04CL-1
(See note.) (See note.)
25 mA max. 25 mA max.
DRT1-ID08CL DRT1-ID08CL-1
(See note.) (See note.)
30 mA max. 30 mA max.
DRT1-ID08C DRT1-HD16C
50 mA max. 50 mA max.
30 mA max. 30 mA max.
DRT1-HD16C-1 DRT1-OD04CL
50 mA max. (See note.)
30 mA max. 35 mA max.
DRT1-OD04CL-1 DRT1-OD08CL
(See note.) (See note.)
35 mA max. 40 mA max.
DRT1-OD08CL-1 DRT1-OD08C
(See note.) 50 mA max.
40 mA max. 30 mA max.
DRT1-WD16C DRT1-WD16C-1
60 mA max. 60 mA max.
30 mA max. 30 mA max.
DRT1-MD16C DRT1-MD16C-1
50 mA max. 50 mA max.
30 mA max. 50 mA max.
DRT1-B7AC
500 mA max.
70 mA max.
Note The internal power supply and communications power supply are shared.
Special-purpose Slaves Model
352
Internal current consumption
Communications current consumption
C200HW-DRT21
250 mA max. (Supplied from the Backplane)
45 mA max.
DRT1-232C2
100 mA max.
50 mA max.
Page 368
Appendix D Precautions when Connecting Two-wire DC Sensors When using a two-wire sensor with a 12-V DC or 24-V DC input device, check that the following conditions have been met. Failure to meet these conditions may result in operating errors.
Relation between Slave with Transistor Inputs and Sensor Residual Voltage VON ≤ VCC – VR VCC:
I/O power supply voltage (The allowable power supply range is 20.4 to 26.4 V, and thus 20.4 V will be used to allow for the worst possible conditions.)
VON:
ON voltage for a Slave with Transistor Inputs
VR:
Sensor’s output residual voltage
ON Current for Slave with Transistor Inputs and Sensor Control Output (Load Current) IOUT (min) ≤ ION ≤ IOUT (max.) IOUT: Sensor control output (load current) ION:
Slave ON current ION = (VCC – VR – VF)/RIN VF: RIN:
Internal residual voltage of Slave Input impedance of Slave
When ION is smaller than IOUT (min), connect a bleeder resistor R. The bleeder resistor constant can be calculated as follows: R ≤ (VCC – VR)/(IOUT (min.) – ION) Power W ≥ (VCC – VR)2/R × 4 [allowable margin] 2-wire sensor
VR
R
RIN
Slave with Transistor Input
VCC
Relation between OFF Current of Slave with Transistor Inputs and Sensor Leakage Current IOFF ≥ Ileak IOFF: OFF current of Slave Ileak: Leakage current of Slave Connect a breeder resistor if Ileak is greater than IOFF. Use the following equation to calculate the breeder resistance constant. R ≤ (IOFF x RIN + VF)/(Ileak – VOFF) Power W ≥ (VCC – VR)2/R × 4 [allowable margin]
353
Page 369
Page 370
Glossary Busoff
A Busoff error occurs when there is an unacceptably high error rate on the communications bus. This error is detected when the internal error counter exceeds a specified value. (The error counter is cleared whenever the Master Unit is started or reset.)
CAN
Controller Area Network. A communications protocol for a LAN developed for mounting in automobiles. The DeviceNet uses CAN technology.
configurator
A device used to make system settings, read IDs, read/write parameters, read the network configuration, etc. OMRON provides a DeviceNet Configurator for OMRON Master Units.
consumed connection size
The size in bytes of the data received through a connection.
ODVA
Open DeviceNet Vendor Association. A non-profit vendor association responsible for spreading DeviceNet.
produced connection size
The size in bytes of the data sent through a connection.
connection
A logical communications channel created to communicate between two nodes. Connections are established and maintained between masters and slaves.
device profile
A description of the structure and behavior of a device giving the minimum data configurations and operations that the device must support. Device profiles enable common device models, and are also called device models. Device profiles are being studied for sensors, valves, displays, encoders, and other devices.
master
A node that controls the collection and distribution of data. With the DeviceNet, the predefined master/slave connection set defines the functions provided by all masters.
slave
A node that provides data in response to requests from masters. With the DeviceNet, the predefined master/slave connection set defines the functions provided by all slaves.
355