The text of a manual · part 36 of 39
C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual: W347-E1-06.pdf, pages 351 to 360
Pages 351 to 360 of 381, from C200HW-DRT21, CQM1-DRT21, DRT1 Series DeviceNet Slaves Operation Manual
The original document is the PDF (7.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron DRT1-ID16
Page 351
Appendix B
Using Another Company’s Master Unit Item Object instance 2
Section Instance type
Polled I/O
1
Production trigger Transport type
Cyclic Server
-----
Transport class
2
---
Item Object instance 2
ID content Attribute
Max. number of instances
1 State
Get (read) Yes
Set (write) No
---
2 Instance type 3 Transport class trigger
Yes Yes
No No
0100 (hexadecimal) 82 (hexadecimal)
4 Produced connection ID 5 Consumed connection ID
Yes Yes
No No
-----
6 Initial comm. characteristics 7 Produced connection size
Yes Yes
No No
01 (hexadecimal) See note.
8 Consumed connection size 9 Expected packet rate
Yes Yes
No Yes
See note. ---
12 Watchdog time-out action 13 Produced connection path length
Yes Yes
No No
0000 (hexadecimal) 0000 (hexadecimal)
14 Produced connection path 15 Consumed connection path length
Yes Yes
No No
No 0000 (hexadecimal)
16 Consumed connection path 17 Production inhibit time
Yes Yes
No No
No 0000 (hexadecimal)
Item Object instance 2
Information
DeviceNet service Service
Value
Parameter option
05Reset 0EGet_Attribute_Single
No No
10Set_Attribute_Single
No
Note The number of bytes in the specified Read Area (Input Area) and Write Area (Output Area) is as follows: Produced connection size: Read Area bytes (default: 0200 (hexadecimal)) Consumed connection size: Write Area bytes (default: 0200 (hexadecimal)) Item Object instance 3
336
Section
Information
Max. number of instances
Instance type Production trigger
Bit strobed I/O Cyclic
1 ---
Transport type Transport class
Server 2
-----
Page 352
Appendix B
Using Another Company’s Master Unit Item Object instance 3
ID content Attribute
1 State
Get (read) Yes
Set (write) No
---
2 Instance type 3 Transport class trigger
Yes Yes
No No
0100 (hexadecimal) 82 (hexadecimal)
4 Produced connection ID 5 Consumed connection ID
Yes Yes
No No
-----
6 Initial comm. characteristics 7 Produced connection size
Yes Yes
No No
01 (hexadecimal) See note.
8 Consumed connection size 9 Expected packet rate
Yes Yes
No Yes
0800 (hexadecimal) ---
12 Watchdog time-out action 13 Produced connection path length
Yes Yes
No No
0000 (hexadecimal) 0000 (hexadecimal)
14 Produced connection path 15 Consumed connection path length
Yes Yes
No No
No 0000 (hexadecimal)
16 Consumed connection path 17 Production inhibit time
Yes Yes
No No
No 0000 (hexadecimal)
Item Object instance 3
DeviceNet service Service
Value
Parameter option
05
Reset
No
0E
Get_Attribute_Single
No
10
Set_Attribute_Single
No
Note The number of bytes in the specified Read Area (Input Area) is as follows: Produced connection size: Read Area bytes (default: 0200 (hexadecimal))
PLC Object (0x2F) Object class
Attribute
Not supported
Service
Not supported
Item Object instance 1 (CIO Area 1: IR 000 to IR 235) See note.
Service
Object instance 2 (CIO Area 2: IR 300 to IR 511) See note.
Service
Object instance 3 (DM Area: DM 0 to DM 6143) See note.
Service
Object instance 4 (LR Area: LR 00 to LR 63) See note.
Service
Object instance 5 (HR Area: HR 00 to HR 99) See note.
Service
DeviceNet service 1C Block String Read
Parameter option Logical Area Address Length
1D Block String N Read 1E Block String Write
Logical Area Address Length Logical Area Address
1F Block String N Write 1C Block String Read
Logical Area Address Logical Area Address Length
1D Block String N Read 1E Block String Write
Logical Area Address Length Logical Area Address
1F Block String N Write 1C Block String Read
Logical Area Address Logical Area Address Length
1D Block String N Read 1E Block String Write
Logical Area Address Length Logical Area Address
1F Block String N Write 1C Block String Read
Logical Area Address Logical Area Address Length
1D Block String N Read 1E Block String Write
Logical Area Address Length Logical Area Address
1F Block String N Write 1C Block String Read
Logical Area Address Logical Area Address Length
1D Block String N Read 1E Block String Write
Logical Area Address Length Logical Area Address
1F Block String N Write
Logical Area Address
337
Page 353
Appendix B
Using Another Company’s Master Unit Item Object instance 6 (AR Area: AR 00 to AR 27) See note.
Service
Object instance 7 (TIM/CNT Area: TIM/CNT 000 to TIM/CNT 511) See note.
Service
Object instance 8 Service (EM Area: Depends on the model) See note.
DeviceNet service 1C Block String Read
Parameter option Logical Area Address Length
1D Block String N Read 1E Block String Write
Logical Area Address Length Logical Area Address
1F Block String N Write 1C Block String Read
Logical Area Address Logical Area Address Length
1D Block String N Read 1E Block String Write
Logical Area Address Length Logical Area Address
1F Block String N Write 1C Block String Read
Logical Area Address Logical Area Address Length
1D Block String N Read 1E Block String Write
Logical Area Address Length Logical Area Address
1F Block String N Write
Logical Area Address
Note The data areas shown in the table are for C200HX/HG/HE (-ZE) PLCs. Refer to the following table for the equivalent data areas in CS1H/G PLCs. C200HX/HG/HE (-ZE) CIO Area 1 (IR 000 to IR 235)
CS1H/G CIO Area 1 (CIO 000 to CIO 235)
CIO Area 2 (IR 300 to IR 511) DM Area (DM 0000 to DM 6143)
CIO Area 2 (CIO 300 to CIO 511) Data Memory Area (D0000 to D6143)
LR Area (LR 00 to LR 63) HR Area (HR 00 to HR 99)
No equivalent Holding Area (H000 to H099)
AR Area (AR 00 to AR 27) TC Area (TC 00 to TC 511)
Holding Area (H100 to H127) (H101 is not allowed.) Timer PV Area (T000 to T511)
EM Area (Depends on the model being used.)
E Area (Depends on the model being used.)
Refresh Object (0x92) Object class
Attribute Service Item
Object instance 1 (current value)
ID and contents Attribute
Item Object instance 1 (current value)
338
64: Output refresh bytes 65: Output refresh area type
Get (read) Yes Yes
Set (write) No No
-----
Yes
No
---
67: Input refresh bytes 68: Input refresh area type
Yes Yes
No No
-----
69: Input refresh address
Yes
No
--Parameter option
0EGet_Attribute_Single 01Set_Attribute_Single ID content
Attribute
Value
66: Output refresh address
DeviceNet service Service
Item Object instance 2 (set value)
Not supported Not supported
No No
64: Output refresh bytes
Get (read) Yes
Set (write) Yes
Value ---
65: Output refresh area type 66: Output refresh address
Yes Yes
Yes Yes
-----
67: Input refresh bytes 68: Input refresh area type
Yes Yes
Yes Yes
-----
69: Input refresh address
Yes
Yes
---
Page 354
Appendix B
Using Another Company’s Master Unit Item Object instance 2 (set value)
DeviceNet service Service
Parameter option
0E Get_Attribute_Single
No
10 Set_Attribute_Single
No
01 Get_Attribute_All
No
02 Set_Attribute_All
No
Note The refresh areas are divided as follows: C200HX/HG/HE (-ZE)
CS1H/G
CIO Area 1 (IR 000 to IR 235) CIO Area 2 (IR 300 to IR 511)
CIO Area 1 (CIO 000 to CIO 235) CIO Area 2 (CIO 300 to CIO 511)
DM Area (DM 0000 to DM 6143) LR Area (LR 00 to LR 63)
Data Memory Area (D0000 to D6143) No equivalent
HR Area (HR 00 to HR 99) AR Area (AR 00 to AR 27)
Holding Area (H000 to H099) Holding Area (H100 to H127) (H101 is not allowed.)
TC Area (TC 00 to TC 511) Timer PV Area (T000 to T511) EM or E Area (Only valid with PLC’s equipped with Extended Data Memory. Bank 0 only.)
Note Device Profile for the RS-232C Unit General data
Compatible DeviceNet Specifications
Volume I - Release 2.0 Volume II - Release 2.0
Header name Device type name
OMRON Corporation Slaves: Generic W347
Manufacturer catalog number Manufacturer revision Physical conform- Network current consumption ance data Connector type
Communications data
Header ID = 47 Device type number = 0
1.0 24 V DC at 50 mA max.
Physical insulation
Open plug Yes
Supported indicators MAC ID setting
Module, Network DIP switch
Default MAC ID Baud rate setting
0 DIP switch
Supported baud rates Predefined Master/Slave connection set
125 kbps, 250 kbps, and 500 kbps Group 2 only server
Dynamic connection support (UCMM) Explicit message fragmentation support
Yes Yes
Object Mounting Identity Object (0x01) Object class
Attribute
Not supported
Service
Not supported
339
Page 355
Appendix B
Using Another Company’s Master Unit Item Object instance Attribute
ID content 1 Vendor
Get (read) Set (write) Yes No 47
2 Product type 3 Product code
Yes Yes
No No
0 308
4 Revision 5 Status (bits supported)
Yes Yes
No No
1.4 ---
6 Serial number 7 Product name
Yes Yes
No No
Unique for each Unit DRT1-232C
8 State
No
No
---
Item Object instance
DeviceNet service Service
05Reset 0EGet_Attribute_Single
Value
Parameter option No No
Message Router Object (0x02) Object class
Attribute Service
Not supported Not supported
Object instance
Attribute Service
Not supported Not supported
Header specification addition
No
DeviceNet Object (0x03) Item Object class Object class
ID content
Set (write) No
Value
1 Revision
Service
Not supported ID content
Get (read)
Set (write)
Attribute
1 MAC ID 2 Baud rate
Yes Yes
No No
-----
3 BOI 4 Bus Off counter
Yes Yes
No No
00 (hexadecimal) ---
5 Allocation information 6 MAC ID switch changed
Yes No
No No
-----
7 Baud rate switch changed 8 MAC ID switch value
No No
No No
-----
9 Baud rate switch value
No
No
---
Item Object instance
Get (read) Yes
Attribute
Item Object instance Service
02 (hexadecimal)
DeviceNet service 0EGet_Attribute_Single
No
4BAllocate_Master/Slave_Connection_Set 4CRelease_Master/Slave_Connection_Set
No No
Value
Parameter option
Assembly Object (0x04) Object class
Attribute
Not supported
Service
Not supported
Item Object instance Attribute Item Object instance
340
ID content 3 Data
Get (read) Set (write) Yes No ---
DeviceNet service Service
0EGet_Attribute_Single 10Set_Attribute_Single
Value
Parameter option No No
Page 356
Appendix B
Using Another Company’s Master Unit Connection Object (0x05) Object class
Attribute Service
Not supported Not supported
Max. number of active connections
1
Item
Section
Object instance 1
Max. number of instances
Instance type Production trigger
Explicit Message Cyclic
1 ---
Transport type Transport class
Server 3
-----
Item Object instance 1
Information
ID content Attribute
1 State
Get (read) Yes
Set (write) No
---
2 Instance type 3 Transport class trigger
Yes Yes
No No
0000 (hexadecimal) 83 (hexadecimal)
4 Produced connection ID 5 Consumed connection ID
Yes Yes
No No
-----
6 Initial comm. characteristics 7 Produced connection size
Yes Yes
No No
21 (hexadecimal) FFFF (hexadecimal)
8 Consumed connection size 9 Expected packet rate
Yes Yes
No Yes
FFFF (hexadecimal) ---
12 Watchdog time-out action 13 Produced connection path length
Yes Yes
Yes No
01 (hexadecimal) 00 (hexadecimal)
14 Produced connection path 15 Consumed connection path length
Yes Yes
No No
--00 (hexadecimal)
16 Consumed connection path 17 Production inhibit time
Yes Yes
No No
--00 (hexadecimal)
Item
DeviceNet service 0EGet_Attribute_Single 10Set_Attribute_Single
Value
Parameter option
Object instance 1
Service
No No
Item Object instance 2
Section Instance type
Polled I/O
1
Production trigger Transport type
Cyclic Server
-----
Transport class
2
---
Information
Max. number of instances
341
Page 357
Appendix B
Using Another Company’s Master Unit Item Object instance 2
ID content Attribute
1 State
Get (read) Yes
Set (write) No
---
2 Instance type 3 Transport class trigger
Yes Yes
No No
01 (hexadecimal) 82 (hexadecimal)
4 Produced connection ID 5 Consumed connection ID
Yes Yes
No No
-----
6 Initial comm. characteristics 7 Produced connection size
Yes Yes
No No
01 (hexadecimal) 0200 (hexadecimal)
8 Consumed connection size 9 Expected packet rate
Yes Yes
No Yes
0000 (hexadecimal) ---
12 Watchdog time-out action 13 Produced connection path length
Yes Yes
No No
00 (hexadecimal) 02 (hexadecimal)
14 Produced connection path 15 Consumed connection path length
Yes Yes
No No
--00 (hexadecimal)
16 Consumed connection path 17 Production inhibit time
Yes Yes
No No
--00 (hexadecimal)
Item Object instance 2
DeviceNet service Service
Item
Item Object instance 3
342
No No Information
Max. number of instances
Instance type Production trigger
Bit strobed I/O Cyclic
1 ---
Transport type Transport class
Server 2
-----
Item Object instance 3
Parameter option
0EGet_Attribute_Single 10Set_Attribute_Single Section
Object instance 3
ID content Attribute
Service
Value
Set (write)
Get (read)
Value
1 State 2 Instance type
Yes Yes
No No
--01 (hexadecimal)
3 Transport class trigger 4 Produced connection ID
Yes Yes
No No
82 (hexadecimal) ---
5 Consumed connection ID 6 Initial comm. characteristics
Yes Yes
No No
--02 (hexadecimal)
7 Produced connection size 8 Consumed connection size
Yes Yes
No No
0200 (hexadecimal) 0800 (hexadecimal)
9 Expected packet rate 12 Watchdog time-out action
Yes Yes
Yes No
--00 (hexadecimal)
13 Produced connection path length 14 Produced connection path
Yes Yes
No No
06 (hexadecimal) 20_04_24_01_30_03
15 Consumed connection path length 16 Consumed connection path
Yes Yes
No No
00 (hexadecimal) ---
17 Production inhibit time
Yes
No
00 (hexadecimal)
DeviceNet service 0EGet_Attribute_Single
No
Parameter option
10Set_Attribute_Single
No
Page 358
Appendix C Connectable Devices and Device Current Consumptions Slave Units Basic I/O Slave Units Model DRT1-ID08
Specifications Remote I/O Terminal 8 Transistor inputs (NPN)
Manufacturer OMRON
DRT1-ID08-1
Remote I/O Terminal 8 Transistor inputs (PNP)
OMRON
DRT1-ID16
Remote I/O Terminal 16 Transistor inputs (NPN)
OMRON
DRT1-ID16-1
Remote I/O Terminal 16 Transistor inputs (PNP)
OMRON
DRT1-OD08
Remote I/O Terminal 8 Transistor outputs (NPN) Remote I/O Terminal 8 Transistor outputs (PNP) Remote I/O Terminal 16 Transistor outputs (NPN) Remote I/O Terminal 16 Transistor outputs (PNP)
OMRON
DRT1-OD08-1 DRT1-OD16 DRT1-OD16-1
OMRON OMRON OMRON
DRT1-MD16
Remote I/O Terminal OMRON 8 Transistor inputs, 8 transistor outputs (NPN)
DRT1-ID16T
Remote I/O Terminal 16 Transistor inputs (NPN) (3-tier I/O Terminal Block)
OMRON
DRT1-ID16T-1
Remote I/O Terminal 16 Transistor inputs (PNP) (3-tier I/O Terminal Block) Remote I/O Terminal 16 Transistor outputs (NPN) (3-tier I/O Terminal Block) Remote I/O Terminal 16 Transistor outputs (PNP) (3-tier I/O Terminal Block) Remote I/O Terminal 8 Transistor inputs, 8 transistor outputs (NPN) (3-tier I/O Terminal Block)
OMRON
DRT1-OD16T
DRT1-OD16T-1
DRT1-MD16T
OMRON
OMRON
OMRON
DRT1-MD16T-1
Remote I/O Terminal OMRON 8 Transistor inputs, 8 transistor outputs (PNP) (3-tier I/O Terminal Block)
DRT1-ID16TA
Remote I/O Terminal OMRON 16 Transistor inputs (NPN) (3-tier I/O Terminal Block, internal power supply not required) Remote I/O Terminal OMRON 16 Transistor inputs (PNP) (3-tier I/O Terminal Block, internal power supply not required)
DRT1-ID16TA-1
343
Page 359
Connectable Devices and Device Current Consumptions Model DRT1-OD16TA
Specifications Manufacturer Remote I/O Terminal OMRON 16 Transistor outputs (NPN) (3-tier I/O Terminal Block, internal power supply not required)
DRT1-OD16TA-1
Remote I/O Terminal OMRON 16 Transistor outputs (PNP) (3-tier I/O Terminal Block, internal power supply not required) Remote I/O Terminal OMRON 8 Transistor inputs, 8 transistor outputs (NPN) (3-tier I/O Terminal Block, internal power supply not required)
DRT1-MD16TA
DRT1-MD16TA-1
DRT1-ID32ML
Remote I/O Terminal OMRON 8 Transistor inputs, 8 transistor outputs (PNP) (3-tier I/O Terminal Block, internal power supply not required) Remote I/O Terminal OMRON 32 Transistor inputs (NPN) with Connectors
DRT1-ID32ML-1
Remote I/O Terminal 32 Transistor inputs (PNP) with Connectors
OMRON
DRT1-OD32ML
Remote I/O Terminal 32 Transistor outputs (NPN) with Connectors
OMRON
DRT1-OD32ML-1
Remote I/O Terminal 32 Transistor outputs (PNP) with Connectors Remote I/O Terminal 16 Transistor inputs, 16 transistor outputs (NPN) with Connectors
OMRON
DRT1-MD32ML-1
Remote I/O Terminal 16 Transistor inputs, 16 transistor outputs (PNP) with Connectors
OMRON
DRT1-ID16X
Remote Adapter 16 Transistor inputs (NPN)
OMRON
DRT1-ID16X-1
Remote Adapter 16 Transistor inputs (PNP)
OMRON
DRT1-OD16X
Remote Adapter 16 Transistor outputs (NPN) Remote Adapter 16 Transistor outputs (PNP) Sensor Terminal 8 sensor inputs (NPN) 2 inputs per sensor Sensor Terminal 8 sensor inputs (NPN) 1 input and 1 output per sensor
OMRON
DRT1-AD04
Analog Input Terminal 4 analog inputs (using 4 words) or 2 analog inputs (using 2 words) (Switchable)
OMRON
DRT1-AD04H
Analog Input Terminal 4 analog inputs (using 4 words)
OMRON
DRT1-DA02
Analog Output Terminal 2 analog outputs (using 2 words) Temperature Input Terminal Thermocouple thermometer input 4 temperature data inputs (using 4 words)
OMRON
DRT1-MD32ML
DRT1-OD16X-1 DRT1-HD16S
DRT1-ND16S
DRT1-TS04T
344
Appendix C
OMRON
OMRON OMRON
OMRON
OMRON
Page 360
Appendix C
Connectable Devices and Device Current Consumptions Model DRT1-TS04P
CQM1-DRT21
Specifications Temperature Input Terminal Temperature-resistance thermometer input 4 temperature data inputs (using 4 words) I/O Link Unit suitable for CQM1-series PLC. 16 inputs and 16 outputs
Manufacturer OMRON
OMRON
Environment-resistive Slaves Model
Specifications
DRT1-ID08C
Environment-resistive Terminal 8 Transistor inputs (NPN) Conforms to IEC IP66
OMRON
DRT1-HD16C
Environment-resistive Terminal 16 Transistor inputs (NPN) Conforms to IEC IP66
OMRON
DRT1-HD16C-1
Environment-resistive Terminal 16 Transistor inputs (PNP) Conforms to IEC IP66 Environment-resistive Terminal 8 Transistor outputs (NPN) Conforms to IEC IP66 Environment-resistive Terminal 16 Transistor outputs (NPN) Conforms to IEC IP66 Environment-resistive Terminal 16 Transistor outputs (PNP) Conforms to IEC IP66
OMRON
DRT1-OD08C
DRT1-WD16C
DRT1-WD16C-1
Manufacturer
OMRON
OMRON
OMRON
DRT1-MD16C
Environment-resistive Terminal OMRON 8 Transistor inputs, 8 transistor outputs (NPN) Conforms to IEC IP66
DRT1-MD16C-1
Environment-resistive Terminal OMRON 8 Transistor inputs, 8 transistor outputs (NPN) Conforms to IEC IP66 Waterproof Terminal OMRON 4 Transistor inputs (NPN) Conforms to IEC IP67 Waterproof Terminal OMRON 4 Transistor inputs (PNP) Conforms to IEC IP67 Waterproof Terminal OMRON 8 Transistor inputs (NPN) Conforms to IEC IP67
DRT1-ID04CL
DRT1-ID04CL-1
DRT1-ID08CL
DRT1-ID08CL-1
Waterproof Terminal 8 Transistor inputs (PNP) Conforms to IEC IP67
OMRON
DRT1-OD04CL
Waterproof Terminal 4 Transistor outputs (NPN) Conforms to IEC IP67
OMRON
DRT1-OD04CL-1
Waterproof Terminal 4 Transistor outputs (PNP) Conforms to IEC IP67 Waterproof Terminal 8 Transistor outputs (NPN) Conforms to IEC IP67 Waterproof Terminal 8 Transistor outputs (PNP) Conforms to IEC IP67 B7AC Interface Unit
OMRON
DRT1-OD08CL
DRT1-OD08CL-1
DRT1-B7AC
OMRON
OMRON
OMRON
345