CHAPTER 6 USING THE COMMUNICATIONS FUNCTION

6.4 Commands and Responses This section describes commands and response in detail. The conventions used in this section and data restrictions are as follows: • Data is expressed in 1-byte units and in ASCII code. • When the read or write data is a numerical value, the data to be set must conform to the following conditions: (1) The decimal point “.” is not indicated in fractions. (2) The leftmost bit of minus numerical data must be expressed as follows: [example] 10.0=[0100], -150.0=[A500], -15=[F015]

J Reading/writing parameters F Reading parameters Command

Response

@

@

F Writing parameters Command

Response

@

@

2B

2B

Unit No.

Parameter No.

1

4B

2B

2B

FCS X

X

X

X

* CR X: Any value acceptable

2B

2B

2B

4B

2B

Unit No.

Parameter No.

End code

Read data

FCS

1

*

2B

2B

4B

2B

Unit No.

Parameter No.

Write data

FCS

2

CR

2B

*

CR

2B

2B

2B

4B

2B

Unit No.

Parameter No.

End code

Write data

FCS

2

2B

2B

*

CR

Reading or writing of the parameters of a specified controller is executed. • Writing is possible only during remote operation. • Reading is impossible during executing auto-tuning. • The followings are set aside as special commands. For details, see page 6-9. “run/stop”, “remote/local”, “AT execute/cancel” • For details on parameters in each setting level, see the tables on pages 6-7 and 6-8.

Writing the Set Value

6--6

With X format “MA” and “ME” commands (see page A--- 12), you can select non-volatile RAM or RAM as the memory for the set value. The limit for the number of times that non-volatile RAM can be written to is 100,000 times. When the number of times that the set point is written exceeds this limit, set RAM write mode as the memory.

Page 102

E5CK

6.4 Commands and Responses

Parameter No.

Parameter

Data Setting and Monitor Range

00

PV monitor

*1

86

SP monitor during SP ramp

*1

04

MV monitor (heat)

*1

--5.0 to 105.0

42

MV monitor (cool)

*1

0.0 to 105.0

01

Set point

02

Alarm value 1

--1999 to 9999

03

Alarm value 2

--1999 to 9999

41

Alarm value 3

--1999 to 9999

19

Proportional band

0.1 to 999.9

20

Integral time

0 to 3999

21

Derivative time

0 to 3999

22

Cooling coefficient

0.01 to 99.99

09

Dead band

--19.99 to 99.99

23

Manual reset value

0.0 to 100.0

06

Hysteresis (heat)

0.01 to 99.99

43

Hysteresis (cool)

0.01 to 99.99

07

Control period (heat)

1 to 99

08

Control period (cool)

1 to 99

44

SP ramp time unit

0: Minutes, 1: Hours

45

SP ramp set value

0 to 9999

46

LBA detection time

Mode

Scaling lower limit -10% to scaling upper *2 limit +10% Set point lower limit to set point upper limit *3

Level 0

Set point lower limit to set point upper limit

Level 1

0 to 9999

47

MV at stop

--5.0 to 105.0

48

MV at PV error

--5.0 to 105.0

50

MV upper limit

MV lower limit +0.1 to 105.0

49

MV lower limit

--5.0 to MV upper limit --0.1

51

MV change rate limit

56

Input digital filter

0 to 9999

25

Alarm 1 hysteresis

0.01 to 99.99

26

Alarm 2 hysteresis

0.01 to 99.99

52

Alarm 3 hysteresis

0.01 to 99.99

53

Input shift upper limit

--199.9 to 999.9

54

Input shift lower limit

--199.9 to 999.9

0.0 to 100.0

*4 *4

*5

Level 2

*1 Possible only during reading *2 During temperature input, the range becomes the range of use of the selected sensor. *3 During heating and cooling control, the range becomes 0.0 to 105.0. *4 During heating and cooling control, the range becomes -105.0 to 105.0. *5 During heating and cooling control, the range becomes -105.0 to MV upper limit -0.1.

About invalid parameters

Currently, if a command is used for invalid parameters (parameters that do not satisfy the conditions of use in Chapter 5), the “undefined” error (end code: IC) is output.

6--7

Page 103

E5CK

CHAPTER 6 USING THE COMMUNICATIONS FUNCTION

Parameter No.

Parameter

Data Setting Range 0 to 21

Mode *1

57

Input type

59

Scaling upper limit

Scaling lower limit +1 to 9999

58

Scaling lower limit

--1999 to scaling upper limit --1

60

Decimal point

0 to 3

30

_C/_F selection

0 : _C, 1 : _F

61

Control output 1 assignment

0 to 4, 6

*2

62

Control output 2 assignment

0 to 4, 6

*2

63

Auxiliary output 1 assignment

2 to 4, 6 to 8

*3

65

Alarm 1 type

1 to 11

*4

66

Alarm 1 open in alarm

67

Alarm 2 type

68

Alarm 2 open in alarm

69

Alarm 3 type

70

Alarm 3 open in alarm

0: closed in alarm, 1: open in alarm

71

Direct/Reverse operation

0: Reverse operation, 1: Direct operation

28

Set point upper limit

*5

Set point lower limit +1 to scaling upper limit

27

Set point lower limit

*5

Scaling lower limit to Set point upper limit --1

72

PID / ON/OFF

73

ST

34

ST stable range width

0.1 to 999.9

35

α

0.00 to 1.00

85

AT calculated gain

0.1 to 10.0

37

Standby sequence reset method

0, 1

36

Automatic return of display mode

0 to 99

93

AT hysteresis

0.1 to 9.9

55

LBA detection width

0.0 to 999.9

Setup

0: closed in alarm, 1: open in alarm 1 to 11

*4

0: closed in alarm, 1: open in alarm 1 to 11

*4

0: Advanced PID, 1: ON/OFF 0 : OFF, 1 : ON

Expansion *6

*1 See page 5-22. *2 0: Control output (heat), 1: Control output (cool), 2: Alarm 1, 3: Alarm 2, 4: Alarm 3, 6: LBA. *3 2: Alarm 1, 3: Alarm 2, 4: Alarm 3, 6: LBA, 7: Error 1, 8: Error 2 *4 See page 5-25. *5 During temperature input, the range becomes the range of use of the selected sensor. *6 See page 5-30.

Reading the status

6--8

To read the E5CK controller status, use the X format “RX” command. For details, see the Appendix: X Format Head List (page A-13).

Page 104

E5CK

6.4 Commands and Responses

J Issuing special commands Command

Response

@

@

2B

2B

4B

2B

Unit No.

Command code

Instruction code

FCS

3

2B

*

CR

2B

2B

2B

4B

2B

Unit No.

Command code

End code

Instruction code

FCS

3

2B

*

CR

The following functions are issued as special commands. • Run/Stop Runs or stops programs. This command cannot be issued in setting level 1. Run/Stop can be switched up to 100,000 times. • Remote/Local Selects remote operation or local operation. • AT Execute/Cancel Executes or cancels auto-tuning. This command cannot be issued in setting level 1. • Move to setting level 1 Issue this command when writing parameters in setup and expansion modes. • Software reset A response is not returned to this command. Also, communications with the E5CK cannot be carried out for five seconds after reset. The following table shows the special commands that are available on the E5CK controller. Command No. 00 02

About Setting Levels

Command Run/Stop Remote/Local

07

AT Execute/Cancel

09 11

Move to setting level 1 Software reset

Instruction Code 0000: Run, 0001: Stop 0000: Remote, 0001: Local 0000: Cancel, 0001: 40%AT execution, 0002: 100% AT execution 0000 0000

To return to setting level 0 from setting level 1, issue the “software reset” command. If the parameter write command is issued for the setup and expansion modes in setting level 0, an error occurs, and the end code (0D = Command cannot be executed) is returned.

6--9

Page 105

E5CK

CHAPTER 6 USING THE COMMUNICATIONS FUNCTION

6.5 How to Read Communications Error Information The result of communications on the E5CK can be checked by the end code in the response frame. Use this end code to remedy errors that may occur.

J End code

Communications are normal when the end code in the response is “00”. If the end code is not “00”, this indicates that an error other that is not an undefined error has occurred. The end code format is as follows and does not contain a data area. 2B @

1B

Unit No.

2B

2B

2B

Command code

End code

FCS

2B

*

CR

Command type

End code

0D

Code name

F Description

F Action End code

10

Command cannot be executed

• Writing was carried out during local operation. • Writing was carried out during executing auto-tuning. • An attempt was made to execute 40%AT during heating and cooling control. • An attempt was made to switch run/stop in setting level 1. • An attempt was made to execute AT in setting level 1. • Issue the parameter read or write commands in conditions other than above.

Code name

Parity error

F Description

Parity check error was detected in the received data.

F Action

Check the communications condition. If the communications condition of the host computer and E5CK controller match, then a probable cause is a problem in the communications circuit of one or both of the host computer and E5CK controller.

End code

11

Code name

Framing error

F Description

Stop bit cannot be detected.

F Action

Check the communications condition. If the communications condition of the host computer and E5CK controller match, then a probable cause is a problem in the communications circuit of one or both of the host computer and E5CK controller.

About the unit No.

6--10

Responses are not returned unless the target unit for communications and the unit No. in the command match.

Page 106

E5CK

6.5 How to Read Communications Error Information

End code

12

Code name

Overrun error

F Description

The receive buffer overflowed.

F Action

Check the communications condition. If the communications condition of the host computer and E5CK controller match, then a probable cause is a problem in the communications circuit of one or both of the host computer and E5CK controller.

End code

13

Code name

FCS error

F Description

The FCS (Frame Check Sequence) do not match.

F Action

Check the FCS program.

End code

14

Code name

Format error

F Description

The received command length does not match the length defined in the frame format.

F Action

Check the communications condition. If the communications condition of the host computer and E5CK controller match, then a probable cause is a problem in the communications circuit of one or both of the host computer and E5CK controller.

End code

15

Code name

Setting range error

F Description

Numerical values or code values in the data are not within the setting range.

F Action

Check the parameter and read or write data of special commands.

J Undefined error 2B @

F Description

Unit No.

2B

2B

2B FCS

I

C

*

CR

• An undefined header code has been received. • A currently invalid parameter (e.g. the scaling command during temperature input) has been received.

F Action

• Check the parameter No.

6--11

Page 107

E5CK

CHAPTER 6 USING THE COMMUNICATIONS FUNCTION

6.6 Program Example

J How to use programs The program described below is for obtaining corresponding response frame data when some of the command frame data is input. The input format is as follows. The FCS and terminator are automatically generated, and need not be input. 2B @

1B

Unit No.

2B

4B

2B

Command code

Data

FCS

2B

*

CR

Command type Input data

Automatically generated

The output format is as follows. The content of the response frame is displayed as it is. 2B @

1B

Unit No.

2B Command code

2B End code

4B

2B

Data

FCS

2B

*

CR

Command type

F Procedure (1) Read the program. (2) Enter “RUN”. (3) When “send data:” is displayed, enter the command data (from @ to the command string). (4) The content of the response frame is displayed following “receive data:”.

F Conditions when running a program • Set the communications condition as follows: Baud rate Bit length Parity Stop bit

: : : :

9600 bps 7 bits Even 2

• Make sure that the communications cable is properly connected.

6--12

Page 108

E5CK

6.6 Program Example

J Program list (language: IBM PC COMPATIBLE MACHINE)

1000 ’ 1010 ’ PROGRAM : E5CK Communication Program 1020 ’ For IBM PC COMPATIBLE MACHINE 1030 ’ VERSION : 1.00 1040 ’ Copyright (C) 1995 OMRON Corporation All Rights Reserved. 1050 ’ 1060 ’ RS-232C SPEED: 9600BPS, PARITY: EVEN, DATA: 7, STOP: 2 1070 OPEN ”COM: 9600, E, 7, 2, CD0, CS0, DS0, RB256, RS ”FOR RANDAM AS #1 LEN=256 1080 REPEAT 1090 ’ Make Command 1100 PRINT ”send data : ” ; 1110 INPUT SEND$ 1120 ’ FCS calculation 1130 FCS=0 1140 FOR IFCS=1 TO LEN (SEND$) 1150 FCS=FCS XOR ASC (MID$ (SEND$, IFCS, 1)) 1160 NEXT 1170 FCS$=RIGHT$ (”0”+HEX$ (FCS), 2) 1180 ’ Send data to communication port 1190 PRINT #1, SEND$+FCS$+”*” 1200 ’ Receive data from communication port 1210 RECCNT=0: TMP$=”” 1220 DRECLOOP: 1230 IF LOC (1) <> 0 THEN DREC1 1240 RECCNT=RECCNT+1 1250 IF RECCNT=5000 THEN *DRECERR ELSE DRECLOOP 1260 ‘DREC1 1270 TMP$=TMP$+INPUT$ (LOC (1), #1) 1280 IF RIGHT$ (TMP&, 1)=CHR$ (13) THEN DRECEND ELSE RECCNT=0: GOTO DRECLOOP 1290 DRECERR: 1300 TMP$=”No response !!” 1310 DRECEND: 1320 RECV$=TMP$ 1330 PRINT ”response: ”; RECV$ 1340 ’ Repeat to make Command 1350 GOTO REPEAT 1360 ’ END 1370 CLOSE #1 1380 END

6--13

Page 109

E5CK

CHAPTER 6 USING THE COMMUNICATIONS FUNCTION

J Examples of use F Set the unit No. to “00” • In the following examples, data is shown in individual blocks to make the examples easier to understand. However, when actually creating programs, do not leave spaces between frame items. Also, response are displayed without spaces between frame items.

F Set the set point to “300.0” • Input data @ 00 2 01 3000 300.0 Set point Write parameter

• Response @ 00 2 01 00 3000 (FCS) * Normal end

F Start running • Input data @ 00 3 00 0000 Run Run/Stop Special command

• Response @ 00 3 00 00 0000 (FCS) * Normal end

F Monitor process value • Input data @ 00 1 00 0000 Dummy data Monitor process value Read parameter

• Response @ 00 1 00 00 2000 (FCS) * Process value = 2000 Normal end

6--14

Page 110

CHAPTER 7 TROUBLESHOOTING

7

CHAPTER 7 TROUBLESHOOTING This chapter describes how to find out and remedy the cause if the E5CK does not function properly.

7.1 Initial Checks . . . . . . . . . . . . . . . . . . . . . . . . . .

7---2

7.2 How to Use the Error Display . . . . . . . . . . .

7---3

7.3 How to Use Error Output . . . . . . . . . . . . . . .

7---5

7.4 Checking Operation Restrictions . . . . . . . .

7---6

7--1