Page 111

E5CK

CHAPTER 7 TROUBLESHOOTING

7.1 Initial Checks If trouble occurs, first of all check the following. (1) Power supply Make sure that the power supply is ON. Also, make sure that the power supply is within the rated voltage range. (2) Input type jumper connectors Make sure that the jumper connectors are at their correct positions. The following table shows the operations when the jumper connector positions do not match the “input type” parameter settings. Jumper Connector TC S PT

Parameter Current (0 to 20mA)

Operation Fixed at scaling lower limit value

Current (4 to 20mA) Voltage (0 to 10V, 0 to 5V)

Fixed at scaling lower limit value

Voltage (1 to 5V)

I

Temperature input Voltage (0 to 10V, 0 to 5V)

Fixed at scaling lower limit value

Voltage (1 to 5V)

V

Temperature input Current (0 to 20mA)

Fixed at scaling lower limit value

Current (4 to 20mA)

(3) Wiring Make sure that all cables are properly connected. (4) Communications condition When communicating using the RS-232C or RS-485 communications interfaces, make sure that the baud rate and other communications condition settings on the host computer and E5CK controller are matching, and are within the permissible ranges. If there appears to be nothing wrong after checking the E5CK controller, and the same phenomenon continues, check the controller in more detail, for example, on the error display.

7--2

Page 112

E5CK

7.2 How to Use the Error Display

7.2 How to Use the Error Display When an error has occurred, the No.1 display alternately indicates error codes together with the current display item. This section describes how to check error codes on the display, and the actions you must be taken to remedy the problem.

Input error F Meaning

Input is in error.

F Action

Check the wiring of inputs, disconnections, and shorts, and check the input type and the input type jumper connector.

F Operation at error

For control output functions, output the manipulated variable matched to the setting of the “MV at PV error” parameter (level 2 mode). Alarm output functions are activated when the upper limit is exceeded.

Memory error F Meaning

Internal memory operation is in error

F Action

First, turn the power OFF then back ON again. If the display remains the same, the E5CK controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise.

F Operation at error

Control output functions turn OFF (2mA max. at 4 to 20mA output, and output equivalent to 0% in case of other outputs). Alarm output functions turn OFF.

A/D converter error F Meaning

Internal circuits are in error.

F Action

First, turn the power OFF then back ON again. If the display remains the same, the E5CK controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise.

F Operation at error

Control output functions turn OFF (2mA max. at 4 to 20mA output, and output equivalent to 0% in case of other outputs). Alarm output functions turn OFF. 7--3

Page 113

E5CK

CHAPTER 7 TROUBLESHOOTING

Calibration data error This error is output only during temperature input, and is displayed for two seconds when the power is turned ON.

F Meaning

Calibration data is in error.

F Action

Must repair.

F Operation at error

Both control output functions and alarm output functions operate. However, note that readout accuracy is not assured.

Display range over F Meaning

Though not an error, this is displayed when the process value exceeds the display range when the control range (setting range ±10%) is larger than the display range (---1999 to 9999). • When less than “-1999”

F Operation

7--4

[

]

• When greater than “9999” [

]

Control continues, allowing normal operation.

Page 114

E5CK

7.3 How to Use Error Output

7.3 How to Use Error Output The E5CK controller allows you to assign error output to terminals as outputs. For details on output assignments, see 3.3 Setting Output Specifications (page 3-5).

F LBA

• LBA (Loop Break Alarm) can be used as a means for detecting loop breaks when the control loop is not functioning normally. For details, see page 4-9. • LBA allows you to detect the following errors: (1) Heater burnout (2) Output error (contact weld, damaged transistors, etc.) (3) Sensor error (constant input values, etc.) • If you use the LBA function, set the loop break detection time matched to the control characteristics in the “LBA detection time” parameter (level 2 mode).

F Input errors

• If you assign error 1 as the output, an error can be output when input is in error. When this error occurs, remedy by following the description for “Input error” (page 7-3).

F A/D converter error

• If you assign error 2 as the output, an error can be output when the A/D converter is in error. When this error occurs, remedy by following the description for “A/D converter error” (page 7-3).

7--5

Page 115

E5CK

CHAPTER 7 TROUBLESHOOTING

7.4 Checking Operation Restrictions With the E5CK controller, auto-tuning or self-tuning sometimes do not operate depending on the way functions are combined. The table below summarizes the main operating restrictions. If the E5CK controller is not operating properly, first check whether operating conditions violate the restrictions in this table. Restriction

Inoperable or Invalid Functions ST Execution

AT Execution

Limiter Function

Other

At analog input

¢

At heating and cooling control

¢

40%AT

At ON/OFF control

¢

¢

Manipulated variable MV change rate

ST = ON

--

¢

Manipulated variable MV change rate

SP ramp function

At AT execution

--

--

MV change rate

Parameter setting

At stop

¢

¢

Manipulated variable MV change rate

Items marked by a “x” indicates combinations of conditions not acceptable during ST or AT execution. Items marked by “ ---” are impossible combinations.

7--6

Page 116

APPENDIX

APPENDIX

SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . A---2 CONTROL BLOCK DIAGRAM . . . . . . . . . . . . . . A---5 SETTING LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . A---6 PARAMETER OPERATIONS LIST . . . . . . . . . . A---8 FUZZY SELF-TUNING . . . . . . . . . . . . . . . . . . . . . A---10 MODEL LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A---13 X FORMAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A---14 ASCII CODE LIST . . . . . . . . . . . . . . . . . . . . . . . . . . A---17

A--1

Page 117

E5CK

APPENDIX

SPECIFICATIONS J Ratings AC100--240V type

AC/DC24V type

Supply Voltage

AC100--240V ~, 50/60 Hz

AC/DC24

Power Consumption

15VA

6VA, 3.5W

Operating Voltage Range

85% to 110% of rated supply voltage

Input

Thermocouple : K, J, T, E, L, U, N, R, S, B, W, PLII Platinum resistance thermometer : JPt100, Pt100 Current input : 4 to 20mA, 0 to 20mA Voltage input : 1 to 5V, 0 to 5V, 1 to 10V

Input Impedance

Voltage input : 1 MΩ min. Current input : 150 Ω

Control Output

According to output unit (see “Output Unit Ratings and Characteristics”)

Auxiliary Output

SPST-NO, 1A at 250 VAC (resistive load)

Control Method

Advanced PID or ON/OFF control

Setting Method

Digital setting using front panel keys

Indication Method

7-segment digital display and LEDs

Other Functions

According to option unit (see “Option Unit Ratings and Characteristics”)

Ambient Temperature

Operating : -10°C to 55°C (with no icing)/3-year warranty period: -10°C to 50°C Storage : -25°C to 65°C (with no icing)

Ambient Humidity

35% to 85% RH

, 50/60Hz

*1, *2

*1 Thermocouple W is W/Re5-26 (tungsten rhenium 5, tungsten rhenium 26). *2 The following table shows the setting ranges and indication ranges for each of the inputs. Input

Indication Range

--199.9 to 650.0(_C)

/--199.9 to 999.9(_F)

--199.9 to 735.0(_C)

/--199.9 to 999.9(_F)

Pt100

--199.9 to 650.0(_C)

/--199.9 to 999.9(_F)

--199.9 to 735.0(_C)

/--199.9 to 999.9(_F)

K1

--200 to 1300(_C)

/--300 to 2300(_F)

--350 to 1450(_C)

/--560 to 2560(_F)

K2

0.0 to 500.0(_C)

/0.0 to 900.0(_F)

--50.0 to 550.0(_C)

/--90.0 to 990.0(_F) /--260 to 1660(_F)

J1

--100 to 850(_C)

/--100 to 1500(_F)

--195 to 945(_C)

J2

0.0 to 400.0(_C)

/0.0 to 750.0(_F)

--40.0 to 440.0(_C)

/--75.0 to 825.0(_F)

T

--199.9 to 400.0(_C)

/--199.9 to 700.0(_F)

--199.9 to 460.0(_C)

/--199.9 to 790.0(_F)

E

0 to 600(_C)

/0 to 1100(_F)

--60 to 660(_C)

/--110 to 1210(_F)

L1

--100 to 850(_C)

/--100 to 1500(_F)

--195 to 945(_C)

/--260 to 1660(_F)

L2

0.0 to 400.0(_C)

/0.0 to 750.0(_F)

--40.0 to 440.0(_C)

/--75.0 to 825.0(_F)

U

--199.9 to 400.0(_C)

/--199.9 to 700.0(_F)

--199.9 to 460.0(_C)

/--199.9 to 790.0(_F)

N

--200 to 1300(_C)

/--300 to 2300(_F)

--350 to 1450(_C)

/--560 to 2560(_F)

R

0 to 1700(_C)

/0 to 3000(_F)

--170 to 1870(_C)

/--300 to 3300(_F)

S

0 to 1700(_C)

/0 to 3000(_F)

--170 to 1870(_C)

/--300 to 3300(_F)

B

100 to 1800(_C)

/300 to 3200(_F)

--70 to 1970(_C)

/10 to 3490(_F)

W

0 to 2300(_C)

/0 to 4100(_F)

--230 to 2530(_C)

/--410 to 4510(_F)

PLII

0 to 1300(_C)

/0 to 2300(_F)

--130 to 1430(_C)

/--230 to 2530(_F)

4 to 20mA 0 to 20mA 1 to 5V 0 to 5V 0 to 10V

A--2

Setting Range

JPt100

One of following ranges depending on results of scaling --1999 to 9999 --199.9 to 999.9 --19.99 to 99.99 --1.999 to 9.999

-10 to 110% of setting range. Note, however that max. value is -1999 to 9999

Page 118

E5CK

SPECIFICATIONS

J Characteristics Thermocouple: (±0.3% of indication value or ± 1°C, whichever greater) ± 1 digit max. (*1) Indication Accuracy

Platinum resistance thermometer: (±0.2% of indication value or ± 0.8°C whichever greater)± 1 digit max. Analog input: ±0.2%± 1 digit max.

Temperature variation influence (*2)

Voltage variation influence (*2)

Platinum resistance thermometer: (±1% of PV or ± 2°C, whichever greater) ±1 digit max. Thermocouple (R, S, B, W): (±1% of PV or ± 10°C, whichever greater) ±1 digit max. Other thermocouples (K1, K2, J1, J2, E, N, T, L1, L2, U, PLII): (±1% of PV or ± 4°C, whichever greater) ±1 digit max. Analog input (current, voltage, or remote SP input): ±1%FS±1 digit max.

Hysteresis

0.01 to 99.99%FS (in units of 0.01%FS)

Proportional Band (P)

0.1 to 999.9% FS (in units of 0.1%FS)

Integral (reset) Time (I)

0 to 3999 s (in units of 1 second)

Derivative (rate) Time (D)

0 to 3999 s (in units of 1 second)

Control Period

1 to 99 s (in units of 1 second)

Manual Reset Value

0.0 to 100.0% (in units of 0.1%)

Alarm Setting Range

-1999 to 9999 or -199.9 to 999.9 (decimal point position dependent on input type)

Sampling Period

Temperature input: 250 ms, Analog input: 100 ms

Insulation Resistance

20 MΩ min. (at 500 VDC)

Dielectric Strength

2000 VAC, 50/60Hz for 1 min (between terminals of different polarities)

Vibration Resistance

Malfunction

10 to 55 Hz, 10 m/s2 (1G) for 10 min each in X, Y, and Z directions

Destruction

10 to 55 Hz, 20 m/s2 (2G) for 2hrs each in X, Y, and Z directions

Shock Resistance

Malfunction

200 m/s2 min. (20G), 3 times each in 6 directions (100 m/s2 (10G) applied to the relay)

Destruction

300 m/s2 min. (30G), 3 times each in 6 directions

Weight

Approx. 170 g, adapter: approx. 10 g

Enclosure Ratings

Front panel: NEMA4 for indoor use (equivalent to IP66) Rear case: IEC standard IP20 Terminals: IEC standard IP00

Memory Protection

Non-volatile memory (Write operation : 100000 max.) (*3)

*1The indication accuracy of the K1, T, and N thermocouples at a temperature of -100°C or less is ±2°C ±1 digit maximum. The indication accuracy of the U, L1 and L2 thermocouples at any temperature is ±2°C ±1 digit maximum. The indication accuracy of the B thermocouple at a temperature of 400°C or less is unrestricted. The indication accuracy of the R and S thermocouples at a temperature of 200°C or less is ±3°C ±1 digit maximum. The indication accuracy of the W thermocouple is ±1 digit max. of whichever is the greater of ±0.3% or ±3°C of the indicated value. The indication accuracy of the PLII thermocouple is ±1 digit max. of whichever is the greater of ±0.3% or ±2°C of the indicated value. *2 Ambient temperature: ---10°C to 23°C to 55°C Voltage range: ---15 to +10% of rated voltage *3 Write operations: Parameter changes, remote/local selection, etc.

A--3

Page 119

E5CK

APPENDIX

J Output Unit Ratings and Characteristics SPST, 250 VAC, 3A (resistive load) Relay output

Mechanical life expectancy: 10,000,000 operations min Electrical life expectancy: 100,000 operations min

Voltage Output (NPN)

NPN, 12 VDC, 20 mA (with short-circuit protection)

Voltage Output (PNP)

PNP, 12 VDC, 20 mA (with short-circuit protection)

Linear Voltage Output

0 to 10 VDC, Permissible load impedance: 1 kΩ min., Resolution: Approx. 2600

Linear Current Output

4 to 20 mA, Permissible load impedance: 500 Ω max., Resolution: Approx. 2600 0 to 20 mA, Permissible load impedance: 500 Ω max., Resolution: Approx. 2600

J Option Unit Ratings and Characteristics Event inputs

Communications

Transfer output

A--4

Contact input

ON: 1 kΩ max., OFF: 100 kΩ min.

No-contact input

ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max.

Interface

:RS-232C or RS-485

Transmission method

:Half-duplex

Synchronization method

:Start-stop synchronization (asynchronous method)

Baud rate

:1.2/2.4/4.8/9.6/19.2 kbps

4 to 20 mA, Permissible load impedance: 500 Ω max. Resolution: Approx. 2600

Page 120

E5CK

CONTROL BLOCK DIAGRAM

CONTROL BLOCK DIAGRAM

Temperature input

Analog input

Digital filter

Digital filter

Input shift

Scaling

Set point limiter

Set point

Input type

SP ramp

ON/OFF control

Process/function Control Data

Process value

Control method

Heating and Cooling control

Control mode

Control mode

PID control MV change rate limiter

ON/OFF control 3-position control

Heating Cooling side side

PID control

MV change rate limiter MV limiter

MV limiter

Dead band

Error

MV at PV error

Error

Stop

MV at stop

Stop

Manual

Manual MV

Manual

Manipulated variable at heating side

Manipulated variable at cooling side

A--5