Page 121

E5CK

APPENDIX

SETTING LIST

Mode Protect Manual Level 0

Parameter Name Security [A/M] key protect

Default

0 to 6

None

1

None

OFF

-5.0 to 105.0

*1

%

0.0

Set point

Set point lower limit to Set point upper limit

EU

0

Run/Stop

Run/Stop

None

RUN

ON/OFF

OFF/AT-1/AT-2

None

OFF

Set point lower limit to Set point upper limit

EU

0

Multi-SP

Set point 1

Set point lower limit to Set point upper limit

EU

0

Multi-SP

During running

Alarm value 1

-1999 to 9999

EU

0

Alarm value 2

-1999 to 9999

EU

0

Alarm value 3

-1999 to 9999

EU

0

Proportional band

0.1 to 999.9

%FS

10.0

Integral time

0 to 3999 sec

233

Derivative time

0 to 3999 sec

40

Cooling coefficient

0.01 to 99.99

None

1.00

At heating and cooling control

Dead band

-19.99 to 99.99

%FS

0.00

At heating and cooling control

Manual reset value

0.0 to 100.0

%

50.0

Hysteresis (heat)

0.01 to 99.99

%FS

0.10

Hysteresis (cool)

0.01 to 99.99

%FS

0.10

Control period (heat)

1 to 99 sec

20

Control period (cool)

1 to 99 sec

20

RMT/LCL

None

LCL

SP ramp time unit

M(Minutes) / H(Hours)

None

M

SP ramp set value

0 to 9999

EU

0

LBA detection time

0 to 9999

Sec

0

MV at stop

-5.0 to 105.0

*1

%

0.0

MV at PV error

-5.0 to 105.0

*1

%

0.0

MV upper limit

MV lower limit + 0.1 to 105.0

*2

%

105.0

MV lower limit

-5.0 to MV upper limit -0.1

*3

%

-5.0

At heating and cooling control

At heating and cooling control

MV change rate limit

0.0 to 100.0

%/sec

0.0

Input digital filter

0 to 9999 sec

0

Alarm 1 hysteresis

0.01 to 99.99

%FS

0.02

Alarm 2 hysteresis

0.01 to 99.99

%FS

0.02

Alarm 3 hysteresis

0.01 to 99.99

%FS

0.02

Input shift upper limit

-199.9 to 999.9

°C/°F

0.0

Temperature input

Input shift lower limit

-199.9 to 999.9

°C/°F

0.0

Temperature input

*1 During heat and cooling control, the lower limit becomes -105.0%. *2 During heat and cooling control, the setting range becomes 0.0 to 105.0%. *3 During heat and cooling control, the setting range becomes -105.0 to 0.0%.

A--6

Remarks

Set point 0

Remote/Local

Level 2

Unit

Manual MV

AT Execute/Cancel

Level 1

Setting Range

Setting

Page 122

E5CK

SETTING LIST

Mode

Parameter Name Input type

Default

None

2

Remarks

Scaling lower limit +1 to 9999 *4

EU

-100

Analog input

Scaling lower limit

-1999 to SP setting upper limit -0.1 *4

EU

0

Analog input

Decimal point

0 to 3

None

0

Analog input

_C/_F selection

_C/_F

None

_C

Temperature input

Parameter initialize

Yes/No

None

NO

Control output 1 assignment

Heat/Cool/Alarm 1/Alarm 2/Alarm 3/LBA

None

HEAT

Control output 2 assignment

Heat/Cool/Alarm 1/Alarm 2/Alarm 3/LBA

None

AL-1

Auxiliary output 1 assignment

Alarm 1/Alarm 2/Alarm 3/LBA/ S.ERR/E333

None

AL-2

Alarm 1 type

1 to 11

None

2

Output assignment needed

Alarm 1 open in alarm

N-O/N-C

None

N-O

Output assignment needed

Alarm 2 type

1 to 11

None

2

Output assignment needed

Alarm 2 open in alarm

N-O/N-C

None

N-O

Output assignment needed

Alarm 3 type

1 to 11

None

2

Output assignment needed

Alarm 3 open in alarm

N-O/N-C

None

N-O

Output assignment needed

Direct/Reverse operation

OR-D/OR-R

None

OR-R

Set point upper limit

Set point lower limit +1 to scaling upper limit *2

None

1300 *4

Set point lower limit

Scaling lower limit to Set point upper limit -1 *2

None

-200 *4

PID / ON/OFF

None

PID

OFF/ON

None

OFF

ST stable range

0.1 to 999.9

°C/°F

15.0

α

0.00 to 1.00

None

0.65

AT calculated gain

PID/ON/OFF ST

0.1 to 10.0

None

1.0

Standby sequence reset setting method

0/1

None

0

Automatic return of display mode

0 to 99

Sec

0

AT hysteresis

0.1 to 9.9

%FS

0.2

LBA detection width

0.0 to 999.9

%FS

0.2

Multi-SP function

0/1

None

0

Event input assignment 1

STOP/MAN

None

STOP

Communication stop bit

1/2 bits

2

Communication data length

7/8 bits

7

None/Even/Odd

None

EVEN 9.6

Communication parity

Option

Unit

0 to 21

Scaling upper limit

Setup

Expansion

Setting Range

Communication baud rate

1.2/2.4/4.8/9.6/19.2 kbps

Communication unit No.

0 to 99

None

0

SP/SP-M/PV/O/C-O

None

SP

Transfer output upper limit

*5

*5

*5

Transfer output lower limit

*5

*5

*5

Transfer output type

Setting

ST=ON

*4 When temperature input is selected, the sensor range selected in the “input type” parameter (setup mode) corresponds to the scaling upper and lower limit value. *5 Set the transfer output type parameter according to the following table. Transfer Output Type SP

D D

Transfer Output Lower Limit to Transfer Output Upper Limit

:Set point

Set point lower limit to Set point upper limit

SP-M

:Set point during SP ramp

Set point lower limit to Set point upper limit

PV

:Process value

Scaling lower limit to scaling upper limit

O

:Manipulated variable (heat)

-5.0 to 105.0%

C-O

:Manipulated variable (cool)

0.0 to 105.0%

The output ranges of the SP setting, set point or process value when temperature input is selected are the ranges supported by the selected sensor. When the heating side manipulated variable or cooling side manipulated variable is selected, the transfer output lower limit in a heating and cooling control becomes “0.0”.

A--7

Page 123

E5CK

APPENDIX

PARAMETER OPERATIONS LIST • Switching to modes other than manual or protect mode is carried out by mode selection in the menu display. • The figure below shows all parameters in the order that they are displayed. Some parameters are not displayed depending on the protect mode setting and conditions of use.

Power ON A/M 1 second min.

1 second min.

Level 0 mode 1 second min.

1 second min.

1 second min.

1 second min.

1 second min.

1 second min.

Level 0

Manual mode A/M

Level 1 mode

1 second min.

Level 2 mode

A/M +

A/M

1 second min.

1 second min.

Setup mode

Protect mode

Expansion mode Option mode

A/M

+

1 second min.

Calibration mode

Parameters in a mode can be switched by the key. The parameter following the last parameter is the top parameter.

Level 1

Level 2

PV/SP

AT Execute/Cancel

Remote/Local

Set point during SP ramp

Set point 0

SP ramp time unit

MV monitor (heat)

Set point 1

SP ramp set value

MV monitor (cool)

Alarm value 1

LBA detection time

Run/Stop

Alarm value 2

MV at stop

Alarm value 3

MV at PV error

Proportional band

MV upper limit

Integral time

MV lower limit

Derivative time

MV change rate limit

Cooling coefficient

Input digital filter

Dead band

Alarm 1 hysteresis

Manual reset value

Alarm 2 hysteresis

Hysteresis (heat)

Alarm 3 hysteresis

Hysteresis (cool)

Input shift upper limit

Control period (heat)

Input shift lower limit

Manual mode Manual MV

Protect mode Security [A/M] key protect

Control period (cool)

A--8

+

Page 124

E5CK

PARAMETER OPERATIONS LIST

Expansion mode

Setup mode

Option mode

Input type

Set point upper limit

Multi-SP function

Scaling upper limit

Set point lower limit

Event input assignment 1

Scaling lower limit

PID / ON/OFF

Communication stop bit

Decimal point

ST

Communication data length

_C/_F selection

ST stable range

Communication parity

Parameter initialize

α

Communication baud rate

Control output 1 assignment

Communication unit No.

Alarm 1 type

AT calculated gain Standby sequence reset method Automatic return of display mode AT hysteresis

Alarm 1 open in alarm

LBA detection width

Control output 2 assignment Auxiliary output 1 assignment

Transfer output type Transfer output upper limit Transfer output lower limit

Alarm 2 type Alarm 2 open in alarm Alarm 3 type Alarm 3 open in alarm Direct/Reverse operation

Calibration mode

Thermocouple Thermocouple 1

Platinum resistance Current input thermometer

Thermocouple 2

Voltage input 0 to 5V 1 to 5V

0 to 10V

Transfer output Only when transfer output function is supported

Data save

Thermocouple 1 Thermocouple 2

: K1/J1/L1/E/N/W/PLII : K2/J2/L2/R/S/B/T/U

Platinum resistance thermometer

: JPt100/Pt100

A--9

Page 125

E5CK

APPENDIX

FUZZY SELF--TUNING Fuzzy self-tuning is a function that enables the E5CK to calculate the most suitable PID constants for the controlled object.

J Features • The E5CK determines by itself when to perform fuzzy self-tuning.

J Fuzzy Self--tuning Function The fuzzy self-tuning function has three modes. In SRT(step response tuning) mode, the PID constants are tuned using a step response method at the time the set point is changed. In DT(disturbance tuning) mode, the PID constants are amended so that the controlled temperature will be within the target range set in advance when there is external disturbance. In HT(hunting tuning) mode, when hunting occurs, the PID constants are amended to suppress the hunting. Note: Be sure to turn on the power supply to the load either before or simultaneously with the start of Temperature Controller operation. Dead time will be measured from the time the Temperature Controller starts operating. If a load such as a heater is turned on after the Temperature Controller is turned on, dead time longer than the actual value will be measured and inappropriate PID constants will be obtained. If an extremely large amount of dead time is measured, the control amount will be set to 0% for a short period of time before being returned to 100%, and the constants will then be returned. Retuning is performed only for large amounts of dead time, so be sure to follow the precaution given above when starting operation.

F Startup Conditions of SRT

SRT will start if the following conditions are satisfied simultaneously when the E5CK is turned on or the set point is changed. At the time the E5CK starts operation

At the time set point is changed

1) The set point at the time the E5CK starts operating is different from the set point used at the time SRT was last executed (see note). 2) The difference between the set point and the process value at the time the E5CK starts operating is larger than the present proportional band value (P) x 1.27+4 3) The process value at the time the E5CK starts operating is smaller than the set point in reverse operation and larger than the set point in normal operation.

1) The new set point is different from the set point used at the time SRT was executed last (see note). 2) The set point changing range is larger than the present proportional band value(P) x 1.27+4. 3) The process value is in stable condition before the set point is changed. 4) A larger set point value is set in reverse operation and a smaller set point is set in normal operation.

Note: The last SRT-executed set point is set to 0 before shipping and when changing from advanced PID control to advanced PID control with fuzzy self-tuning. A--10

Page 126

E5CK

FUZZY SELF--TUNING

F Imposition Completion Condition of Step Control Amount

In order to prevent overshooting, the step controlled amount must be imposed continuously only while the present deviation is the same as or greater than the value obtained from the proportional band (P) x 1.27. The step control will not be applied when the deviation becomes smaller than

F PID Constant Refreshing Conditions

If the step control amount is applied before the maximum temperature slope (R) is obtained, SRT will not renew any PID constant. If the proportional band obtained from the R and L values that were measured before the imposition had been completed is larger than the present proportional band, the PID constants will be renewed because the measured value is in the direction towards the suitable proportional band value, and the set point at that time will be the SRT-executed set point.

this value.

Temperature

Slope (R) Stable range P x 1.27

SP

Completion of SRT

Time

F Stable Temperature Status If the temperature is within the stable range for a certain time, it is deemed that the temperature is stable. This time is called stability judgement time. Like PID constants, stability judgement time is adjusted with fuzzy selftuning according to the characteristics of the object to be controlled. Fuzzy self-tuning will not be activated if the temperature is stable because the Temperature Controller deems that temperature control is smooth. Shorter than the stability judgement time

Stable range

Set point

Stable range (Set to 15.0_C before shipping) Stability judgement time Stable

Stable

A--11

Page 127

E5CK

APPENDIX

F Balanced Status If the process value is within the stable range for 60s when there is no output,it is deemed that the temperature is balanced.

F Startup Conditions of DT (1) DT will start if the temperature that has been stable varies due to external disturbance and the deflection of the temperature exceeds the stable range, and then the temperature becomes stable, provided that the number of maximum temperature values is less than four. (2) DT will start if the set point is changed under the condition that SRT does not start and the temperature becomes stable, provided that the number of maximum temperature values is less than four. If there are four or more maximum temperature values, HT will start. Extreme value 2

Set point change

Temperature SP

Extreme value 1

Time

F Startup Conditions of HT HT will be ON when there is hunting with four or more maximum temperature values(extreme values) while SRT is not being executed. Extreme value 2

Extreme value 4

Temperature SP

Extreme value 1

Extreme value 3

Time

Note: In specific applications where temperature varies periodically due to disturbance, internal parameters need to be adjusted.

A--12

Page 128

E5CK

MODEL LIST

MODEL LIST Description Base unit

Type Name

Specification

E5CK-AA1

Base unit (AC100--240V

E5CK-AA1-500

Base unit with terminal cover (AC100--240V

E5CK-AA1 AC/DC24V

Base unit (AC/DC24V

E5CK-AA1-500 AC/DC24V Base unit (AC/DC24V Output module

Option module

Terminal cover

) )

) ) with terminal cover

E53-R4R4

Relay/relay

E53-Q4R4

Pulse (NPN)/relay

E53-Q4HR4

Pulse (PNP)/relay

E53-C4R4

Linear (4 to 20mA)/relay

E53-C4DR4

Linear (0 to 20mA)/relay

E53-V44R4

Linear (0 to 10V)/relay

E53-Q4Q4

Pulse (NPN)/pulse (NPN)

E53-Q4HQ4H

Pulse (PNP)/pulse (PNP)

E53-CK01

RS-232C

E53-CK03

RS-485

E53-CKB

Event input : 1 point

E53-CKF

Transfer output (4 to 20mA)

E53-COV07

Terminal cover for E5CK

The output unit is required for E5CK-AA1 (including -500). For details on the output unit, see page 2-3. When adding on the option unit, also see the option unit list on page 2-3.

A--13

Page 129

E5CK

APPENDIX

X FORMAT

J Format

The E5CK controller supports communications in the X format which is used in other Omron controllers such as ES100, E5AJ/EJ and E5AX/EX. Commands are structured as follows and are paired with a response. 2B

F Command

F Response

@

2B

Unit No.

Header code

Data code

2B

2B

2B

Unit No.

@

2B

Header code

End code

2B Data

2B

FCS * 2B

Data

CR 2B

FCS *

CR

• “@” The start character. This character must be inserted before the leading byte. • Unit No. Specifies the “unit No.” of the E5CK. If there are two or more transmission destinations, specify the desired destination using “unit No.” • Header code/Data code Specifies the command type. For details on the command type, see page A-12. • Data Specifies the set value or setting content. The data length varies according to the command. • End code Sets the communication results. For details on the types and meanings of end codes, see 6.5 How to Read Communications Error Information (page 6-10). • FCS (Frame Check Sequence) Set the frame check results from the start character to the data section. For details on the frame check, see 6.6 Program Example (page 6-12). • “*” “CR (Carriage Return) code” Indicates the end (terminator) of the command or response block.

A--14

Page 130

E5CK

X FORMAT

J X FORMAT HEAD LIST Header Code

Data Code

Command Content

R/W

Data

Remarks Error response

IC

01

Undefined error

-

None

MB

01

Remote/Local

Write

4B

MA

01

RAM write mode

ME

01

Backup mode

Write

None

MW

01

RAM data batch save

01

Alarm value 1 read

02

Alarm value 2 read

03

Alarm value 3 read

RB

01

Proportional band read

Read

4B

RN

01

Integrated time read

RV

01

Derivative time read

RC

01

Cooling coefficient read

RD

01

Dead band read

Read

4B

01

Input shift upper limit read

02

Input shift lower limit read

Read

4B

RL

01

SP setting limit read

Read

8B

RO

01

Manipulated variable read

RS

01

Set point read

Read

4B

RX

01

Process value read

Read

8B

01

Alarm value 1 write

02

Alarm value 2 write

03

Alarm value 3 write

WB

01

Proportional band write

Write

4B

WN

01

Integrated time write

WV

01

Derivative time write

WC

01

Cooling coefficient write

WD

01

Dead band write

Write

4B

01

Input shift upper limit write

02

Input shift lower limit write

Write

4B

01

Set point write

R%

RI

W%

WI WS

During heating and cooling control

Upper-and lower-limit batch read with status

During heating and cooling control

A--15