The text of a manual · part 13 of 14
E5CK Digital Controller User's Manual, pages 121 to 130
Pages 121 to 130 of 138
The original document is the PDF (1.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron E5CK
Page 121
E5CK
APPENDIX
SETTING LIST
Mode Protect Manual Level 0
Parameter Name Security [A/M] key protect
Default
0 to 6
None
1
None
OFF
-5.0 to 105.0
*1
%
0.0
Set point
Set point lower limit to Set point upper limit
EU
0
Run/Stop
Run/Stop
None
RUN
ON/OFF
OFF/AT-1/AT-2
None
OFF
Set point lower limit to Set point upper limit
EU
0
Multi-SP
Set point 1
Set point lower limit to Set point upper limit
EU
0
Multi-SP
During running
Alarm value 1
-1999 to 9999
EU
0
Alarm value 2
-1999 to 9999
EU
0
Alarm value 3
-1999 to 9999
EU
0
Proportional band
0.1 to 999.9
%FS
10.0
Integral time
0 to 3999 sec
233
Derivative time
0 to 3999 sec
40
Cooling coefficient
0.01 to 99.99
None
1.00
At heating and cooling control
Dead band
-19.99 to 99.99
%FS
0.00
At heating and cooling control
Manual reset value
0.0 to 100.0
%
50.0
Hysteresis (heat)
0.01 to 99.99
%FS
0.10
Hysteresis (cool)
0.01 to 99.99
%FS
0.10
Control period (heat)
1 to 99 sec
20
Control period (cool)
1 to 99 sec
20
RMT/LCL
None
LCL
SP ramp time unit
M(Minutes) / H(Hours)
None
M
SP ramp set value
0 to 9999
EU
0
LBA detection time
0 to 9999
Sec
0
MV at stop
-5.0 to 105.0
*1
%
0.0
MV at PV error
-5.0 to 105.0
*1
%
0.0
MV upper limit
MV lower limit + 0.1 to 105.0
*2
%
105.0
MV lower limit
-5.0 to MV upper limit -0.1
*3
%
-5.0
At heating and cooling control
At heating and cooling control
MV change rate limit
0.0 to 100.0
%/sec
0.0
Input digital filter
0 to 9999 sec
0
Alarm 1 hysteresis
0.01 to 99.99
%FS
0.02
Alarm 2 hysteresis
0.01 to 99.99
%FS
0.02
Alarm 3 hysteresis
0.01 to 99.99
%FS
0.02
Input shift upper limit
-199.9 to 999.9
°C/°F
0.0
Temperature input
Input shift lower limit
-199.9 to 999.9
°C/°F
0.0
Temperature input
*1 During heat and cooling control, the lower limit becomes -105.0%. *2 During heat and cooling control, the setting range becomes 0.0 to 105.0%. *3 During heat and cooling control, the setting range becomes -105.0 to 0.0%.
A--6
Remarks
Set point 0
Remote/Local
Level 2
Unit
Manual MV
AT Execute/Cancel
Level 1
Setting Range
Setting
Page 122
E5CK
SETTING LIST
Mode
Parameter Name Input type
Default
None
2
Remarks
Scaling lower limit +1 to 9999 *4
EU
-100
Analog input
Scaling lower limit
-1999 to SP setting upper limit -0.1 *4
EU
0
Analog input
Decimal point
0 to 3
None
0
Analog input
_C/_F selection
_C/_F
None
_C
Temperature input
Parameter initialize
Yes/No
None
NO
Control output 1 assignment
Heat/Cool/Alarm 1/Alarm 2/Alarm 3/LBA
None
HEAT
Control output 2 assignment
Heat/Cool/Alarm 1/Alarm 2/Alarm 3/LBA
None
AL-1
Auxiliary output 1 assignment
Alarm 1/Alarm 2/Alarm 3/LBA/ S.ERR/E333
None
AL-2
Alarm 1 type
1 to 11
None
2
Output assignment needed
Alarm 1 open in alarm
N-O/N-C
None
N-O
Output assignment needed
Alarm 2 type
1 to 11
None
2
Output assignment needed
Alarm 2 open in alarm
N-O/N-C
None
N-O
Output assignment needed
Alarm 3 type
1 to 11
None
2
Output assignment needed
Alarm 3 open in alarm
N-O/N-C
None
N-O
Output assignment needed
Direct/Reverse operation
OR-D/OR-R
None
OR-R
Set point upper limit
Set point lower limit +1 to scaling upper limit *2
None
1300 *4
Set point lower limit
Scaling lower limit to Set point upper limit -1 *2
None
-200 *4
PID / ON/OFF
None
PID
OFF/ON
None
OFF
ST stable range
0.1 to 999.9
°C/°F
15.0
α
0.00 to 1.00
None
0.65
AT calculated gain
PID/ON/OFF ST
0.1 to 10.0
None
1.0
Standby sequence reset setting method
0/1
None
0
Automatic return of display mode
0 to 99
Sec
0
AT hysteresis
0.1 to 9.9
%FS
0.2
LBA detection width
0.0 to 999.9
%FS
0.2
Multi-SP function
0/1
None
0
Event input assignment 1
STOP/MAN
None
STOP
Communication stop bit
1/2 bits
2
Communication data length
7/8 bits
7
None/Even/Odd
None
EVEN 9.6
Communication parity
Option
Unit
0 to 21
Scaling upper limit
Setup
Expansion
Setting Range
Communication baud rate
1.2/2.4/4.8/9.6/19.2 kbps
Communication unit No.
0 to 99
None
0
SP/SP-M/PV/O/C-O
None
SP
Transfer output upper limit
*5
*5
*5
Transfer output lower limit
*5
*5
*5
Transfer output type
Setting
ST=ON
*4 When temperature input is selected, the sensor range selected in the “input type” parameter (setup mode) corresponds to the scaling upper and lower limit value. *5 Set the transfer output type parameter according to the following table. Transfer Output Type SP
D D
Transfer Output Lower Limit to Transfer Output Upper Limit
:Set point
Set point lower limit to Set point upper limit
SP-M
:Set point during SP ramp
Set point lower limit to Set point upper limit
PV
:Process value
Scaling lower limit to scaling upper limit
O
:Manipulated variable (heat)
-5.0 to 105.0%
C-O
:Manipulated variable (cool)
0.0 to 105.0%
The output ranges of the SP setting, set point or process value when temperature input is selected are the ranges supported by the selected sensor. When the heating side manipulated variable or cooling side manipulated variable is selected, the transfer output lower limit in a heating and cooling control becomes “0.0”.
A--7
Page 123
E5CK
APPENDIX
PARAMETER OPERATIONS LIST • Switching to modes other than manual or protect mode is carried out by mode selection in the menu display. • The figure below shows all parameters in the order that they are displayed. Some parameters are not displayed depending on the protect mode setting and conditions of use.
Power ON A/M 1 second min.
1 second min.
Level 0 mode 1 second min.
1 second min.
1 second min.
1 second min.
1 second min.
1 second min.
Level 0
Manual mode A/M
Level 1 mode
1 second min.
Level 2 mode
A/M +
A/M
1 second min.
1 second min.
Setup mode
Protect mode
Expansion mode Option mode
A/M
+
1 second min.
Calibration mode
Parameters in a mode can be switched by the key. The parameter following the last parameter is the top parameter.
Level 1
Level 2
PV/SP
AT Execute/Cancel
Remote/Local
Set point during SP ramp
Set point 0
SP ramp time unit
MV monitor (heat)
Set point 1
SP ramp set value
MV monitor (cool)
Alarm value 1
LBA detection time
Run/Stop
Alarm value 2
MV at stop
Alarm value 3
MV at PV error
Proportional band
MV upper limit
Integral time
MV lower limit
Derivative time
MV change rate limit
Cooling coefficient
Input digital filter
Dead band
Alarm 1 hysteresis
Manual reset value
Alarm 2 hysteresis
Hysteresis (heat)
Alarm 3 hysteresis
Hysteresis (cool)
Input shift upper limit
Control period (heat)
Input shift lower limit
Manual mode Manual MV
Protect mode Security [A/M] key protect
Control period (cool)
A--8
+
Page 124
E5CK
PARAMETER OPERATIONS LIST
Expansion mode
Setup mode
Option mode
Input type
Set point upper limit
Multi-SP function
Scaling upper limit
Set point lower limit
Event input assignment 1
Scaling lower limit
PID / ON/OFF
Communication stop bit
Decimal point
ST
Communication data length
_C/_F selection
ST stable range
Communication parity
Parameter initialize
α
Communication baud rate
Control output 1 assignment
Communication unit No.
Alarm 1 type
AT calculated gain Standby sequence reset method Automatic return of display mode AT hysteresis
Alarm 1 open in alarm
LBA detection width
Control output 2 assignment Auxiliary output 1 assignment
Transfer output type Transfer output upper limit Transfer output lower limit
Alarm 2 type Alarm 2 open in alarm Alarm 3 type Alarm 3 open in alarm Direct/Reverse operation
Calibration mode
Thermocouple Thermocouple 1
Platinum resistance Current input thermometer
Thermocouple 2
Voltage input 0 to 5V 1 to 5V
0 to 10V
Transfer output Only when transfer output function is supported
Data save
Thermocouple 1 Thermocouple 2
: K1/J1/L1/E/N/W/PLII : K2/J2/L2/R/S/B/T/U
Platinum resistance thermometer
: JPt100/Pt100
A--9
Page 125
E5CK
APPENDIX
FUZZY SELF--TUNING Fuzzy self-tuning is a function that enables the E5CK to calculate the most suitable PID constants for the controlled object.
J Features • The E5CK determines by itself when to perform fuzzy self-tuning.
J Fuzzy Self--tuning Function The fuzzy self-tuning function has three modes. In SRT(step response tuning) mode, the PID constants are tuned using a step response method at the time the set point is changed. In DT(disturbance tuning) mode, the PID constants are amended so that the controlled temperature will be within the target range set in advance when there is external disturbance. In HT(hunting tuning) mode, when hunting occurs, the PID constants are amended to suppress the hunting. Note: Be sure to turn on the power supply to the load either before or simultaneously with the start of Temperature Controller operation. Dead time will be measured from the time the Temperature Controller starts operating. If a load such as a heater is turned on after the Temperature Controller is turned on, dead time longer than the actual value will be measured and inappropriate PID constants will be obtained. If an extremely large amount of dead time is measured, the control amount will be set to 0% for a short period of time before being returned to 100%, and the constants will then be returned. Retuning is performed only for large amounts of dead time, so be sure to follow the precaution given above when starting operation.
F Startup Conditions of SRT
SRT will start if the following conditions are satisfied simultaneously when the E5CK is turned on or the set point is changed. At the time the E5CK starts operation
At the time set point is changed
1) The set point at the time the E5CK starts operating is different from the set point used at the time SRT was last executed (see note). 2) The difference between the set point and the process value at the time the E5CK starts operating is larger than the present proportional band value (P) x 1.27+4 3) The process value at the time the E5CK starts operating is smaller than the set point in reverse operation and larger than the set point in normal operation.
1) The new set point is different from the set point used at the time SRT was executed last (see note). 2) The set point changing range is larger than the present proportional band value(P) x 1.27+4. 3) The process value is in stable condition before the set point is changed. 4) A larger set point value is set in reverse operation and a smaller set point is set in normal operation.
Note: The last SRT-executed set point is set to 0 before shipping and when changing from advanced PID control to advanced PID control with fuzzy self-tuning. A--10
Page 126
E5CK
FUZZY SELF--TUNING
F Imposition Completion Condition of Step Control Amount
In order to prevent overshooting, the step controlled amount must be imposed continuously only while the present deviation is the same as or greater than the value obtained from the proportional band (P) x 1.27. The step control will not be applied when the deviation becomes smaller than
F PID Constant Refreshing Conditions
If the step control amount is applied before the maximum temperature slope (R) is obtained, SRT will not renew any PID constant. If the proportional band obtained from the R and L values that were measured before the imposition had been completed is larger than the present proportional band, the PID constants will be renewed because the measured value is in the direction towards the suitable proportional band value, and the set point at that time will be the SRT-executed set point.
this value.
Temperature
Slope (R) Stable range P x 1.27
SP
Completion of SRT
Time
F Stable Temperature Status If the temperature is within the stable range for a certain time, it is deemed that the temperature is stable. This time is called stability judgement time. Like PID constants, stability judgement time is adjusted with fuzzy selftuning according to the characteristics of the object to be controlled. Fuzzy self-tuning will not be activated if the temperature is stable because the Temperature Controller deems that temperature control is smooth. Shorter than the stability judgement time
Stable range
Set point
Stable range (Set to 15.0_C before shipping) Stability judgement time Stable
Stable
A--11
Page 127
E5CK
APPENDIX
F Balanced Status If the process value is within the stable range for 60s when there is no output,it is deemed that the temperature is balanced.
F Startup Conditions of DT (1) DT will start if the temperature that has been stable varies due to external disturbance and the deflection of the temperature exceeds the stable range, and then the temperature becomes stable, provided that the number of maximum temperature values is less than four. (2) DT will start if the set point is changed under the condition that SRT does not start and the temperature becomes stable, provided that the number of maximum temperature values is less than four. If there are four or more maximum temperature values, HT will start. Extreme value 2
Set point change
Temperature SP
Extreme value 1
Time
F Startup Conditions of HT HT will be ON when there is hunting with four or more maximum temperature values(extreme values) while SRT is not being executed. Extreme value 2
Extreme value 4
Temperature SP
Extreme value 1
Extreme value 3
Time
Note: In specific applications where temperature varies periodically due to disturbance, internal parameters need to be adjusted.
A--12
Page 128
E5CK
MODEL LIST
MODEL LIST Description Base unit
Type Name
Specification
E5CK-AA1
Base unit (AC100--240V
E5CK-AA1-500
Base unit with terminal cover (AC100--240V
E5CK-AA1 AC/DC24V
Base unit (AC/DC24V
E5CK-AA1-500 AC/DC24V Base unit (AC/DC24V Output module
Option module
Terminal cover
) )
) ) with terminal cover
E53-R4R4
Relay/relay
E53-Q4R4
Pulse (NPN)/relay
E53-Q4HR4
Pulse (PNP)/relay
E53-C4R4
Linear (4 to 20mA)/relay
E53-C4DR4
Linear (0 to 20mA)/relay
E53-V44R4
Linear (0 to 10V)/relay
E53-Q4Q4
Pulse (NPN)/pulse (NPN)
E53-Q4HQ4H
Pulse (PNP)/pulse (PNP)
E53-CK01
RS-232C
E53-CK03
RS-485
E53-CKB
Event input : 1 point
E53-CKF
Transfer output (4 to 20mA)
E53-COV07
Terminal cover for E5CK
The output unit is required for E5CK-AA1 (including -500). For details on the output unit, see page 2-3. When adding on the option unit, also see the option unit list on page 2-3.
A--13
Page 129
E5CK
APPENDIX
X FORMAT
J Format
The E5CK controller supports communications in the X format which is used in other Omron controllers such as ES100, E5AJ/EJ and E5AX/EX. Commands are structured as follows and are paired with a response. 2B
F Command
F Response
@
2B
Unit No.
Header code
Data code
2B
2B
2B
Unit No.
@
2B
Header code
End code
2B Data
2B
FCS * 2B
Data
CR 2B
FCS *
CR
• “@” The start character. This character must be inserted before the leading byte. • Unit No. Specifies the “unit No.” of the E5CK. If there are two or more transmission destinations, specify the desired destination using “unit No.” • Header code/Data code Specifies the command type. For details on the command type, see page A-12. • Data Specifies the set value or setting content. The data length varies according to the command. • End code Sets the communication results. For details on the types and meanings of end codes, see 6.5 How to Read Communications Error Information (page 6-10). • FCS (Frame Check Sequence) Set the frame check results from the start character to the data section. For details on the frame check, see 6.6 Program Example (page 6-12). • “*” “CR (Carriage Return) code” Indicates the end (terminator) of the command or response block.
A--14
Page 130
E5CK
X FORMAT
J X FORMAT HEAD LIST Header Code
Data Code
Command Content
R/W
Data
Remarks Error response
IC
01
Undefined error
-
None
MB
01
Remote/Local
Write
4B
MA
01
RAM write mode
ME
01
Backup mode
Write
None
MW
01
RAM data batch save
01
Alarm value 1 read
02
Alarm value 2 read
03
Alarm value 3 read
RB
01
Proportional band read
Read
4B
RN
01
Integrated time read
RV
01
Derivative time read
RC
01
Cooling coefficient read
RD
01
Dead band read
Read
4B
01
Input shift upper limit read
02
Input shift lower limit read
Read
4B
RL
01
SP setting limit read
Read
8B
RO
01
Manipulated variable read
RS
01
Set point read
Read
4B
RX
01
Process value read
Read
8B
01
Alarm value 1 write
02
Alarm value 2 write
03
Alarm value 3 write
WB
01
Proportional band write
Write
4B
WN
01
Integrated time write
WV
01
Derivative time write
WC
01
Cooling coefficient write
WD
01
Dead band write
Write
4B
01
Input shift upper limit write
02
Input shift lower limit write
Write
4B
01
Set point write
R%
RI
W%
WI WS
During heating and cooling control
Upper-and lower-limit batch read with status
During heating and cooling control
A--15