E5CK Digital Controller User's Manual
Manual138 pagesPDF 1.7 MB
User's manual for the Omron E5CK compact digital controller: setup, wiring, operation, parameters, communications and troubleshooting.
Covers · 1 model
The models it covers
Summary
What is in it
Omron user's manual for the E5CK compact, high-function digital controller. It introduces the front panel, inputs and outputs, then covers installation, wiring and switch settings, basic operation with a control example, applied operation (control method, option functions, loop break alarm, calibration), a full parameter reference by mode, the communications function with commands and a program example, and troubleshooting. Appendices give specifications, a setting list, fuzzy self-tuning and a model list.
Its parts
- Introduction
- Preparations
- Basic Operation
- Applied Operation
- Parameters
- Using the Communications Function
- Troubleshooting
From the manual
Key facts from this manual
Each line names its page in the PDF.
Omron user's manual H078-E1-03D for the E5CK compact digital controller. It covers setting up output and option units, panel mounting and wiring, parameters and menus, the communications function, and troubleshooting with the error display. Appendices give specifications and a model list.
- Device
- Compact digital controller with multiple temperature and analog inputs, output assignment, two setpoints and loop break alarm p. 2
- Power
- AC100-240V type: 100 to 240 VAC, 50/60 Hz, 15 VA; AC/DC24V type: 24 VAC/DC, 6 VA, 3.5 W; terminals 4 and 5 p. 23
- Inputs
- One at a time: thermocouple K, J, T, E, L, U, N, R, S, B, W, PLII; RTD JPt100, Pt100; current 4 to 20 mA, 0 to 20 mA; or voltage input p. 11
- Auxiliary output
- SPST-NO, 1A at 250 VAC (resistive load), terminals 2 and 3 p. 25, 117
- Control method
- Advanced PID or ON/OFF control p. 117
- Output units
- E53-R4R4 relay/relay, E53-Q4R4 pulse (NPN)/relay, E53-Q4HR4 pulse (PNP)/relay, E53-C4R4 4 to 20 mA/relay, E53-C4DR4 0 to 20 mA/relay, E53-V44R4 0 to 10 V/relay, E53-Q4Q4 NPN/NPN, E53-Q4HQ4H PNP/PNP p. 128
- Output ratings
- Relay SPST, 250 VAC, 3A resistive; voltage NPN or PNP, 12 VDC, 20 mA with short-circuit protection; linear 0 to 10 VDC, 4 to 20 mA or 0 to 20 mA p. 119
- Option units
- E53-CK01 RS-232C, E53-CK03 RS-485, E53-CKB event input (1 point), E53-CKF transfer output (4 to 20 mA) p. 128
- Communications
- RS-232C or RS-485; half-duplex; 1.2/2.4/4.8/9.6/19.2 kbps p. 119
- Base units
- E5CK-AA1 and E5CK-AA1-500 (with terminal cover E53-COV07), each in AC100-240V and AC/DC24V versions; an output unit is required p. 128
- Error displays
- Input error, memory error, A/D converter error, calibration data error; display range over is shown but is not an error p. 112, 113
- Sampling period
- Temperature input 250 ms, analog input 100 ms p. 118
- Ambient conditions
- -10°C to 55°C operating, -25°C to 65°C storage, no icing; 35% to 85% RH p. 117
- Panel cutout
- 45 +0.6/0 mm; panel thickness 1 to 5 mm p. 21
What this manual walks you through
- Assigning output functions to the outputs p. 12
- Installing output and option units p. 20
- Mounting the controller in a panel with its adapter p. 21, 22
- Wiring power, input, outputs and option units p. 23, 24, 25
- Setting the input type jumper p. 24
- Initial checks when trouble occurs p. 111
- Reading error displays and fixing their causes p. 112, 113
- Using error output and the loop break alarm p. 114
- Checking why auto-tuning or self-tuning will not run p. 115
Good to know
- The output functions do not operate for five seconds after power-on. p. 12
- At power-on the supply must reach its prescribed voltage within two seconds. p. 5
- Tighten terminal screws to no more than 0.78 N·m (8 kgf·cm). p. 23
- If a memory or A/D converter error stays after turning the power off and on, the controller must be repaired. p. 112
- The non-volatile memory allows 100000 write operations at most; parameter changes count as writes. p. 118
Questions this manual answers
What do I do when the E5CK shows an input error?
Check the input wiring for disconnections and shorts, and check the input type setting and the input type jumper connector. p. 112
Is there a 24 V version of the E5CK?
Yes. The model list includes the E5CK-AA1 and E5CK-AA1-500 in an AC/DC24V version, rated 6 VA, 3.5 W. p. 23, 128
Why don't the E5CK outputs turn on right after power-up?
The output functions do not operate for five seconds after the E5CK is turned on. p. 12
Which functions can be assigned to the E5CK auxiliary output?
Only alarms 1 to 3, LBA, and errors 1 and 2. Control outputs 1 and 2 take heat, cool, alarms 1 to 3 and LBA. p. 12
What does the E5CK loop break alarm detect?
Heater burnout, output errors such as a welded contact or damaged transistors, and sensor errors such as constant input values. p. 114