Page 1 of E5CK Digital Controller User's Manual

Manual · Omron

E5CK Digital Controller User's Manual

Manual138 pagesPDF 1.7 MB

User's manual for the Omron E5CK compact digital controller: setup, wiring, operation, parameters, communications and troubleshooting.

Download the PDF1.7 MB

Covers · 1 model

The models it covers

Summary

What is in it

Omron user's manual for the E5CK compact, high-function digital controller. It introduces the front panel, inputs and outputs, then covers installation, wiring and switch settings, basic operation with a control example, applied operation (control method, option functions, loop break alarm, calibration), a full parameter reference by mode, the communications function with commands and a program example, and troubleshooting. Appendices give specifications, a setting list, fuzzy self-tuning and a model list.

Its parts

  1. Introduction
  2. Preparations
  3. Basic Operation
  4. Applied Operation
  5. Parameters
  6. Using the Communications Function
  7. Troubleshooting

From the manual

Key facts from this manual

Each line names its page in the PDF.

Omron user's manual H078-E1-03D for the E5CK compact digital controller. It covers setting up output and option units, panel mounting and wiring, parameters and menus, the communications function, and troubleshooting with the error display. Appendices give specifications and a model list.

Read for this summary: pages 1 to 3, 5 to 7, 11 to 12, 20 to 25, 111 to 115, 117 to 119 and 128 of 138.

Device
Compact digital controller with multiple temperature and analog inputs, output assignment, two setpoints and loop break alarm p. 2
Power
AC100-240V type: 100 to 240 VAC, 50/60 Hz, 15 VA; AC/DC24V type: 24 VAC/DC, 6 VA, 3.5 W; terminals 4 and 5 p. 23
Inputs
One at a time: thermocouple K, J, T, E, L, U, N, R, S, B, W, PLII; RTD JPt100, Pt100; current 4 to 20 mA, 0 to 20 mA; or voltage input p. 11
Auxiliary output
SPST-NO, 1A at 250 VAC (resistive load), terminals 2 and 3 p. 25, 117
Control method
Advanced PID or ON/OFF control p. 117
Output units
E53-R4R4 relay/relay, E53-Q4R4 pulse (NPN)/relay, E53-Q4HR4 pulse (PNP)/relay, E53-C4R4 4 to 20 mA/relay, E53-C4DR4 0 to 20 mA/relay, E53-V44R4 0 to 10 V/relay, E53-Q4Q4 NPN/NPN, E53-Q4HQ4H PNP/PNP p. 128
Output ratings
Relay SPST, 250 VAC, 3A resistive; voltage NPN or PNP, 12 VDC, 20 mA with short-circuit protection; linear 0 to 10 VDC, 4 to 20 mA or 0 to 20 mA p. 119
Option units
E53-CK01 RS-232C, E53-CK03 RS-485, E53-CKB event input (1 point), E53-CKF transfer output (4 to 20 mA) p. 128
Communications
RS-232C or RS-485; half-duplex; 1.2/2.4/4.8/9.6/19.2 kbps p. 119
Base units
E5CK-AA1 and E5CK-AA1-500 (with terminal cover E53-COV07), each in AC100-240V and AC/DC24V versions; an output unit is required p. 128
Error displays
Input error, memory error, A/D converter error, calibration data error; display range over is shown but is not an error p. 112, 113
Sampling period
Temperature input 250 ms, analog input 100 ms p. 118
Ambient conditions
-10°C to 55°C operating, -25°C to 65°C storage, no icing; 35% to 85% RH p. 117
Panel cutout
45 +0.6/0 mm; panel thickness 1 to 5 mm p. 21

What this manual walks you through

  • Assigning output functions to the outputs p. 12
  • Installing output and option units p. 20
  • Mounting the controller in a panel with its adapter p. 21, 22
  • Wiring power, input, outputs and option units p. 23, 24, 25
  • Setting the input type jumper p. 24
  • Initial checks when trouble occurs p. 111
  • Reading error displays and fixing their causes p. 112, 113
  • Using error output and the loop break alarm p. 114
  • Checking why auto-tuning or self-tuning will not run p. 115

Good to know

  • The output functions do not operate for five seconds after power-on. p. 12
  • At power-on the supply must reach its prescribed voltage within two seconds. p. 5
  • Tighten terminal screws to no more than 0.78 N·m (8 kgf·cm). p. 23
  • If a memory or A/D converter error stays after turning the power off and on, the controller must be repaired. p. 112
  • The non-volatile memory allows 100000 write operations at most; parameter changes count as writes. p. 118

Questions this manual answers

What do I do when the E5CK shows an input error?

Check the input wiring for disconnections and shorts, and check the input type setting and the input type jumper connector. p. 112

Is there a 24 V version of the E5CK?

Yes. The model list includes the E5CK-AA1 and E5CK-AA1-500 in an AC/DC24V version, rated 6 VA, 3.5 W. p. 23, 128

Why don't the E5CK outputs turn on right after power-up?

The output functions do not operate for five seconds after the E5CK is turned on. p. 12

Which functions can be assigned to the E5CK auxiliary output?

Only alarms 1 to 3, LBA, and errors 1 and 2. Control outputs 1 and 2 take heat, cool, alarms 1 to 3 and LBA. p. 12

What does the E5CK loop break alarm detect?

Heater burnout, output errors such as a welded contact or damaged transistors, and sensor errors such as constant input values. p. 114

The whole text · 14 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 5041-50
  6. Pages 51 to 6051-60
  7. Pages 61 to 7061-70
  8. Pages 71 to 8071-80
  9. Pages 81 to 9081-90
  10. Pages 91 to 10091-100
  11. Pages 101 to 110101-110
  12. Pages 111 to 120111-120
  13. Pages 121 to 130121-130
  14. Pages 131 to 138131-138

The file

Revision and size

RevisionCat. No. H078-E1-03D
PublisherOMRON
Pages138
PDF1.7 MB
TextText from the PDF itself.

The first pages · 3 of 138

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 138
Page 2
Page 2of 138
Page 3
Page 3of 138