Page 41
E5CK
CHAPTER 4 APPLIED OPERATION
4.1 Selecting the Control Method When selecting the control method, set the parameters according to the following table. (Parameters are factory-set to heating control.) Parameter
Control output 1 assignment
Control output 2 assignment
Direct/Reverse operations
Heating control (Standard)
Control output (heat)
--
Reverse operation
Cooling control (Standard)
Control output (heat)
--
Direct operation
Heating and cooling control
Control output (heat)
Control output (cool)
Reverse operation
Control Method
For details on how to assign outputs, see 3.3 Setting Output Specifications (page 3---5).
J Heating and cooling control
• When heating and cooling control is selected, the “deadband” and “cooling coefficient” parameters can be used.
F Dead band
The dead band is set with the set point as its center. The dead band width is the set value of the “dead band” parameter (level 1 mode). Setting a positive value produces a dead band, while setting a negative value produces an overlap band. Dead band: dead band width = positive
Output
Cooling side
Heating side 0
PV Set point
F Cooling coefficient
F Manipulated variable at stop
Switching with Manual operation
4--2
Overlap band: dead band width = negative
Output
Cooling side
Heating side 0
PV Set point
If the heating and cooling characteristics of the control target greatly differ, preventing satisfactory control characteristics from being obtained by the same PID parameters, adjust the proportional band (P at cooling side) using the cooling coefficient to balance control between the heating and cooling sides. In heating and cooling control, P at the heating or cooling side is calculated by the following formula: Heating side P = P; Cooling side P = cooling coefficient ¢ P • In heating and cooling control, the manipulated variable output that is output when controller operation is stopped is dependent on the set value of the “MV at stop” parameter (level 2 mode) in the same way as for standard control. • However, note that in heating and cooling control, the manipulated variable at the cooling side is treated as a negative value for the sake of convenience. When the manipulated variable at STOP is a negative value, the manipulated variable is output to only the cooling side, and when a positive value, the manipulated variable is output to only the heating side. The factory setting is “0”. If the controller is operated using the factory setting, the manipulated variable is not output to both the heating and cooling sides. When the overlap band is set, the bumpless function that operates when switching between manual and automatic operation may not work.
Page 42
E5CK
4.1 Selecting the Control Method
J ON/OFF control
F Hysteresis
• Switching between advanced PID control and ON/OFF control is carried out by the “PID / ON/OFF” parameter (expansion mode). When this ], advanced PID control is selected, and when parameter is set to [ set to [ ], ON/OFF control is selected. Default is [ ]. • In ON/OFF control, hysteresis is provided in the program when switching between ON and OFF to stabilize operation. The hysteresis width provided during ON/OFF control is simply referred to as “hysteresis.” Control output (heat) and control output (cool) functions are set in the “hysteresis (heat)” and “hysterisis (cool)” parameters, respectively. • In standard control (heating or cooling control), hysteresis can be set only for the heating side. Hysteresis (heat) ON
PV
OFF Set point
• In heating and cooling control, a dead band can be set. So, 3-position control is made possible. Dead band Hysteresis (cool)
Hysteresis (heat) ON Heating side
Cooling side PV
OFF Set point
Parameters
Symbol
Parameter Name: Mode
Description
Control output 1 assignment
For specifying control method : Setup
Control output 2 assignment
: Setup
Direct/Reverse operation
: Setup
For specifying control method
Dead band
: Level 1
Heating and cooling control
Cooling coefficient
: Level 1
Heating and cooling control
MV at stop
: Level 2
Manipulated variable when control operation is stopped
Hysteresis (heat)
: Level 1
ON/OFF control
Hysteresis (cool)
: Level 1
ON/OFF control
PID / ON/OFF
: Expansion
ON/OFF control
For specifying control method
4--3
Page 43
E5CK
CHAPTER 4 APPLIED OPERATION
4.2 Operating Condition Restrictions J Manipulated variable restrictions F MV limiter
The upper-and lower-limit values of the manipulated variable can be restricted by the MV limiter, and the change rate of the manipulated variable can be restricted by the MV change rate limiter. The upper-and lower-limit values of the manipulated variable are set in the “MV upper limit” and “MV lower limit” parameters (level 2 mode). When the manipulated variable calculated by the E5CK is outside of the range of the MV limiter, actual outputs are dependent on the set value of these parameters. Output (%) 100
MV upper limit value
MV lower limit value
0
PV
In heating and cooling control, the manipulated variable at the cooling side is treated as a negative value for the sake of convenience. The upper limit is set for the heating side (positive value), and the lower limit is set for the cooling side (negative value) as shown in the following figure. Output (%) 100
MV lower limit value MV upper limit value Heating side
Cooling side Set point
F MV change rate limiter
PV 100
The “MV change rate limit” parameter (level 2 mode) sets the maximum permissible change width per second of the manipulated variable. If a change in the manipulated variable exceeds this parameter setting, the value calculated by the E5CK is reached while changing the value by the per-second value set in this parameter. Output (%) 100 MV change rate limit value 1 second
0
Time Switching point
4--4
Page 44
E5CK
4.2 Operating Condition Restrictions
F Limiter operation conditions
The limiters are invalid or cannot be set when any of the following conditions occurs: • During ON/OFF control • During ST execution • During AT execution (only by MV change rate limiter) • During manual operation • When operation is stopped • When an error has occurred.
J Set point limiter
The setting range of the set point is limited by the set point limiter. The upper-and lower-limit values of this set point limiter are set in the “Set point upper limit” and “Set point lower limit” parameters (expansion mode), respectively. However, note that when the set point limiter is reset, the set point is forcibly changed to the upper-or lower-limit value of the set point limiter if the set point is out of the limiter range. Also, when the input type, temperature unit and scaling (sensor) range are changed, set point limiter is forcibly reset to the scaling (sensor) range. Scaling (sensor) range Set point limiter Setting range
Changed to upper limit value
SP Changed to the new upper limit value
Input type changed Set point Upper-and lower-limit values of the limiter Scaling (sensor) upper-and lower-limit values
J SP ramp
A ○
B × SP
C
B ○
With the SP ramp function, the controller operates according to the value (set point during SP ramp) limited by a change rate, instead of the changed set point when set point is changed. The interval in which the set point during SP ramp is limited is referred to as the “SP ramp”. SP Set point
SP ramp
SP ramp set value
SP ramp time unit Time Switching point
4--5
Page 45
E5CK
CHAPTER 4 APPLIED OPERATION
The change rate during the SP ramp is specified by the “SP ramp set value” and “SP ramp time unit” parameters. At the “SP ramp set value” default “0”, the SP ramp function is disabled. The set point changing in SP ramp can be monitored in the “Set point during SP ramp” parameter (level 0 mode).
F Operation at start
The limiters are invalid or cannot be set when any of the following conditions occurs: If the SP ramp function is enabled when the power is turned ON, and when “run” is switched to from “stop,” process value may reach the set point after SP ramp in the same way as when the set point is changed. In this case, operation is carried out with the process value regarded as the set point before the change was made. The direction of the SP ramp changes according to the relationship between the process value and the set point. PV < SP
PV > SP
SP Set point
SP SP ramp
SP ramp PV
Same change rate
Set point PV
Time
Time Power ON
Power ON
F Restrictions during SP ramp
• Execution of auto-tuning starts after the end of SP ramp. • When the controller is switched to the manual mode, the set point changes continuously until SP ramp ends. • When an error occurs, the SP ramp function becomes invalid.
Parameters
4--6
Symbol
Parameter Name: Mode
Description
MV upper limit
: Level 2
Manipulated variable restrictions
MV lower limit
: Level 2
Manipulated variable restrictions
MV change rate limit : Level 2
Manipulated variable restrictions
SP setting upper limit: Expansion
SP setting restrictions
SP setting lower limit : Expansion
SP setting restrictions
SP ramp set value
: Level 2
SP changing restrictions
SP ramp time unit
: Level 2
SP changing restrictions
Page 46
E5CK
4.3 How to Use Option Functions
4.3 How to Use Option Functions • For details on the communications function, refer to Chapter 6 Using the Communications Function.
J Event input
• When using event input, add on the input unit (E53-CKB).
F Input assignments Multi-SP function 0 Run/Stop
1 Multi-SP
Auto/Manual
• You can choose from the following three event input functions: Run/Stop Auto/Manual Multi-SP • When selecting an option function, first determine whether or not the multi-SP function is to be used. You can select two of the remaining option functions only when the multi-SP function is not in use. • When using the multi-SP function, set the “multi-SP function” parameter (option mode) to “1: ON”. When using other functions, set this parameter to “0: OFF”. • When specifying event input other than the multi-SP function, specify event input in the “event input assignmen 1” parameter (option mode). The following table shows the relationship between parameter settings and event input functions. Setting
F Run/Stop
Function ON : Stop
/OFF : Run
ON : Manual
/OFF : Auto
• When event input is set to “ON”, controller operation is stopped and the “STOP” LED lights. The content of event input is reflected in the “run/ stop” parameter (level 0 mode). • Run/Stop can be switched up to 100,000 times.
F Auto/Manual
• When event input is set to “ON”, the controller is switched for manual operation, and the “MANU” LED lights. • Turn event input ON/OFF while the controller is ON. • Auto/Manual can be switched up to 100,000 times.
About the event input and key operation
There is no order of priority when inputting events and operating the keys. However, because event input of run/stop or auto/manual must be carried out in either of the physical ON/OFF states, parameters ultimately conform to event input even if an attempt is made to switch the setting by key operation.
4--7
Page 47
E5CK
CHAPTER 4 APPLIED OPERATION
F Multi-SP
• The set points set to the “set point 0” and “set point 1” parameters (level 1 mode) can be switched for use. However, note that these parameters cannot be set when the multi-SP function is not selected. • The set point can be switched up to 100,000 times. • When event input is “OFF”, set point 0 is used, and when “ON” set point 1 is used. • When you have changed the set point, the set point of the currently selected parameter is changed. • When you have switched between “set point 0” and “set point 1”, the SP ramp function works if the SP ramp function is enabled. The following examples shows how the set point changes when you switch from set point 0 and set point 1. SP
SP ramp set point 1 set point 0 Time Event input
J Transfer output
OFF
ON
• When using transfer output, add on the communications unit (E53-CKF). • You can select the following data items in the “transfer output type” parameter (option mode) as the transfer outputs: Set point Set poing during SP ramp Process value Manipulated variable (heat), and Manipulated variable (cool). • These transfer outputs can be scaled according to the settings of the “transfer output upper limit” and “transfer output lower limit” parameters before output. Setting of an upper limit value smaller than the lower limit value is allowed, so reverse scaling can also be carried out. Also, the scale can be enlarged by the upper-and lower-limit width specified for each data item. The following example shows scaling of the reading side manipulated variable.
Transfer output (mA)
Transfer output (mA)
Reverse scaling
20
20
4
4
Transfer output upper limit: 0
Parameters
Symbol
Transfer output lower limit: 100
Manipulated variable (%)
0
Transfer output lower limit: 10
100 Transfer output upper limit: 80
Parameter Name: Mode
Manipulated variable (%)
Application
Multi-SP function
: Option
Event input functions
Event input assignment 1
: Option
Event input functions
Set point 0
: Level 1
Multi-SP
Set point 1
: Level 1
Multi-SP
Transfer output type
: Option
Transfer output designation
Transfer output upper limit
: Option
Transfer output scaling
Transfer output lower limit
4--8
Enlarged scale
: Option
Transfer output scaling
Page 48
E5CK
4.4 LBA
4.4 LBA • The LBA (Loop Break Alarm) function can be used only when assigned as an output. Also, the LBA function does not work when a memory error or A/D converter error occurs. • LBA (Loop Break Alarm) is a function for judging that an error has occurred somewhere on the control loop and outputting an alarm when the process value does not change with the manipulated variable at a maximum or minimum state. Accordingly, the LBA function can be used as a means for detecting a malfunctioning control loop.
F LBA detection time
• Normally, when output is set to maximum or minimum, the process value rises or falls after the dead time has elapsed. LBA is output if the process value does not change in the predicted direction after a fixed amount of time has elapsed. This fixed amount of time is the “LBA detection time.”
F LBA detection width
• LBA operation sometimes becomes unstable when the process value fluctuates considerably due to the control characteristics. The LBA detection width is provided so that changes with respect to output can be correctly detected. Changes smaller than the detection width due to LBA detection timing are not regarded as changes.
F LBA detection example
• The following example describes what happens when a heater burnout at maximum output. LBA detection time
LBA detection time
PV LBA detection width Output
Time Heater burnout
LBA=ON
• LBA judgment is carried out at each LBA detection time from the point of maximum output. In above figure, the process value (PV) is changing greatly at the 1st judgment timing, so LBA remains OFF. • At the 2nd judgment timing, the process value increases as indicated by the broken line of the process value is normal. This means that the change width exceeds the LBA detection width, and LBA output remains OFF. • If the heater burns out at the point shown in the above figure, the process value “decreases.” Accordingly, it is judged that “the process value is not changing in the increasing direction” at the 2nd judgment timing and the LBA output becomes ON. 4--9
Page 49
E5CK
CHAPTER 4 APPLIED OPERATION
F Setting the LBA detection time
• The LBA detection time is automatically set by auto-tuning (except in heating and cooling control). • If the optimum LBA detection time cannot be obtained by auto-tuning, set the time in the “LBA detection time” parameter (level 2 mode).
F Determining the LBA detection time
• Calculate the LBA detection time as follows: (1) Set output to maximum. (2) Measure the time it takes for the input change width to reach the LBA detection width (default: 0.2 % full-scale). (3) Take a value twice that of the measurement time as the LBA detection time. Measurement time Tm
PV
0.2%FS Output
Time LBA detection time = Tm x 2
(4) In the case of ON/OFF operation, set the LBA detection time to a value longer than the control period.
Parameters
Symbol
Parameter Name: Mode
Automatic setting of LBA detection time
LBA detection time
Setting of LBA detection time
: Level 2
LBA detection width : Expansion
4--10
Application
AT Execute/Cancel : Level 1
Changing of LBA detection width
Page 50
E5CK
4.5 Calibration
4.5 Calibration • To calibrate the E5CK controller, select [ ] in the menu display to ] is displayed. select the calibration mode. [ • However, note that [ ] may not be displayed on the menu display when, for example, the user is calibrating the E5CK controller for the ] is displayed by changing the “secufirst time. If this happens, [ rity” parameter (protect mode) to “0”. • The parameters in the calibration mode are configured as follows. Thermocouple
Thermocouple 1
Platinum resistance thermometer
Current input
Voltage input
0 to 5V 1 to 5V
Thermocouple 2
0 to 10V
Transfer output
Only when transfer output function is supported
Thermocouple 1 Thermocouple 2
: K1/J1/L1/E/N/W/PLII : K2/J2/L2/R/S/B/T/U
Platinum resistance thermometer
: JPt100/Pt100
Data save
• To select the desired parameter, press the key. Parameters are displayed in the following order: Calibration of inputs → Calibration of transfer output → Saving of calibration data If the E5CK controller does not support the transfer output function, calibration of transfer output is automatically deleted from the calibration procedure as follows: Calibration of inputs → Saving of calibration data • Only inputs that have been set in the “input type” parameter (setup mode) can be calibrated. To temporarily save data for each of the calibrakey for 1 second. tion parameters, press the • Transfer output can be calibrated only when the communications unit (E53-CKF) is set in the controller. To adjust data items, press the or keys. • The data save menu is displayed only when all calibration items have temporarily been saved. • After calibrating input, you must always check indication accuracy. For details, see page 4-20. 4--11