Page 51
E5CK
CHAPTER 4 APPLIED OPERATION
F Calibration item menu Calibration item parameter
Process value
• Parameters are displayed on the No.1 display, and the process value is displayed in Hexadecimal on the No.2 display. • Normally, the process value changes by several digits. The process value flashes, for example, when a sensor error causes the process value to stray from the calibration target range. • When the process value display is flashing, the process value is not saved key is pressed. as data even if the
F Calibration save mark
• Once the E5CK controller has been calibrated by the user, [ ceded by the “.” mark when the calibration mode is selected.
] is pre- calibration save mark
J Calibrating thermocouple
F Preparations
• Calibrate according to the type of thermocouple, thermocouple 1 group (K1, J1, L1, E, N, W, PLII) and thermocouple 2 group (K2, J2, L2, R, S, B, T, U). • When calibrating, do not cover the bottom or top of the controller. Also, do not touch the input terminals (Nos. 6 and 7) and compensating conductor on the E5CK controller.
AC100-240V (AC/DC24V ) SOURCE
5
11 12
10
4 3
9 8
2 1
7 6
13 14
STV Cold junction compensator 0°C/32°F Compensating conductor
DMM
• Set the cold junction compensator to 0_C. However, make sure that internal thermocouples are disabled (tips are open). • In the above figure, STV refers to a standard DC current/voltage source, and DMM refers to a precision digital multimeter. • Use a compensating conductor selected thermocouple. However, note that when thermocouple R, S, E, B, W or PLII is used, the compensating conductor can be substituted with the cold junction compensator for thermocouple K and compensating conductor. Connecting the Cold Junction Conductor
Correct process values cannot be obtained if you touch the contact ends of the compensating conductor during calibration of a thermocouple. Accordingly, short (enable) or open (disable) the tip of the compensating conductor inside the cold junction compensator as shown in the figure below to create a contact or non-contact state for the cold junction compensator. Cold junction compensator E5CK controller
0°C/32°F
Compensating conductor
4--12
Cold junction compensator
Short E5CK controller
0°C/32°F
Compensating conductor
Open
Page 52
E5CK
4.5 Calibration
F Calibration: thermocouple 1
This example describes how to calibrate a thermocouple when the transfer output function is supported. If the transfer output function is not supported, skips steps (7) to (10). (1) When [ ] is displayed, the 30-minute timer is displayed on the No.2 display and counts down. This timer serves as a guide for the aging time when aging is required. (2) First, calibrate the main input. Press the key to display [ ] (50mV calibration display). Set STV output to 50mV. When the value on the No.2 display has stabilized (changes of several digits max.), key to temporarily save the calibration data. press the (3) Press the key to display [ ] (0mV calibration display). Set STV output to 0mV. When the value on the No.2 display has stabilized (changes of several digits max.), press the key to temporarily save the calibration data. (4) Next, calibrate the cold junction compensator. Press the key to display [ ] (310mV calibration display). Set STV output to 310mV. When the value on the No.2 display has stabilized (changes of several digits max.), press the key to temporarily save the calibration data. (5) Press the key to display [ ] (0mV calibration display). Set STV output to 0mV. When the value on the No.2 display has stabilized (changes of several digits max.), press the key to temporarily save the calibration data. (6) Finally, calibrate the bias compensation value. Disconnect the STV, and enable the thermocouple of the cold junction compensator. When carrying this out, make sure that the wiring on the STV is disconnected. Make sure that the cold junction compensator is set to 0_C and press key. The display changes to [ ] (calibration display for the the bias compensation value). When the value on the No.2 display has stabilized (changes of several digits max.), press the key to temporarily save the calibration data. (7) Next, calibrate the transfer output function. If the transfer output key. The disfunction is not supported, skip to step (11). Press the play changes to [ ] (20mA calibration display). (8) Set the output to 20mA by the or keys while monitoring the voltage on the digital multimeter. In the example on the left, the display indicates that the value two digits smaller than before calibration is “20mA”. (9) Press the key. The display changes to [ ] (4mA calibration display). or keys while monitoring the (10) Set the output to 4mA by the voltage on the digital multimeter. In the example on the left, the display indicates that the value two digits smaller than before calibration is “4mA”. key until the display changes to the data save display. (11) Press the key. The No.2 display changes to [ ], and two Press the seconds later the calibration data is saved to internal memory. If you key when the No.2 display reads [ ], the calibration press the data is invalidated. (12) This completes calibration of the thermocouple 1 group. Press the key to return the display to [ ]. 4--13
Page 53
E5CK
CHAPTER 4 APPLIED OPERATION
F Calibration: thermocouple 2
This example describes how to calibrate a thermocouple when the transfer output function is supported. If the transfer output function is not supported, skips steps (7) to (10). (1) When [ ] is displayed, the 30-minute timer is displayed on the No.2 display and counts down. This timer serves as a guide for the aging time when aging is required. (2) First, calibrate the main input. Press the key to display [ ] (20mV calibration display). Set STV output to 20mV. When the value on the No.2 display has stabilized (changes of several digits max.), key to temporarily save the calibration data. press the (3) Press the key to display [ ] (0mV calibration display). Set STV output to 0mV. When the value on the No.2 display has stabilized (changes of several digits max.), press the key to temporarily save the calibration data. (4) Next, calibrate the cold junction compensator. Press the key to display [ ] (310mV calibration display). Set STV output to 310mV. When the value on the No.2 display has stabilized (changes of several digits max.), press the key to temporarily save the calibration data. (5) Press the key to display [ ] (0mV calibration display). Set STV output to 0mV. When the value on the No.2 display has stabilized (changes of several digits max.), press the key to temporarily save the calibration data. (6) Finally, calibrate the bias compensation value. Disconnect the STV, and enable the thermocouple of the cold junction compensator. When carrying this out, make sure that the wiring on the STV is disconnected. Make sure that the cold junction compensator is set to 0_C and press key. The display changes to [ ] (calibration display for the the bias compensation value). When the value on the No.2 display has stabilized (changes of several digits max.), press the key to temporarily save the calibration data. (7) Next, calibrate the transfer output function. If the transfer output key. The disfunction is not supported, skip to step (11). Press the play changes to [ ] (20mA calibration display). (8) Set the output to 20mA by the or keys while monitoring the voltage on the digital multimeter. In the example on the left, the display indicates that the value two digits smaller than before calibration is “20mA”. (9) Press the key. The display changes to [ ] (4mA calibration display). or keys while monitoring the (10) Set the output to 4mA by the voltage on the digital multimeter. In the example on the left, the display indicates that the value two digits smaller than before calibration is “4mA”. key until the display changes to the data save display. (11) Press the key. The No.2 display changes to [ ], and two Press the seconds later the calibration data is saved to internal memory. If you key when the No.2 display reads [ ], the calibration press the data is invalidated. (12) This completes calibration of the thermocouple 2 group. Press the key to return the display to [ ].
4--14
Page 54
E5CK
4.5 Calibration
J Calibrating platinum resistance thermometer F Preparation
AC100-240V (AC/DC24V ) SOURCE
5
11 12
10
4 3
9 8
2 1
7 6
13 14
6-dial
DMM • Use leads of the same thickness when connecting to the platinum resistance thermometer. • In the above figure, 6-dial refers to a precision resistance box, and DMM stands for a digital multimeter. However, note that the DMM is required only when the transfer output function is supported. • Connect (short) the leads from terminal Nos. 6 and 7.
F Calibration
This example describes how to calibrate a platinum resistance thermometer when the transfer output function is supported. If the transfer output function is not supported, skips steps (7) to (10). (1) When [ ] is displayed, the 30-minute timer is displayed on the No.2 display and counts down. This timer serves as a guide for the aging time when aging is required. (2) First, calibrate the main input. Press the key to display [ ] (300Ω calibration display). Set the 6-dial to 300Ω. When the value on the No.2 display has stabilized (changes of several digits max.), press key to temporarily store the calibration data. the
Short terminal Nos.6 to 8
Change wiring.
key to switch [ ] (0Ω calibration) display. Short (3) Press the terminal No.6 to 8. When the value on the No.2 display has stabilized key to temporarily (changes of several digits max.), press the store the calibration data. (4) Next, calibrate the B-B’ input. Change the wiring as follows.
10 9 8
Short terminal Nos.6 to 8
7 6
6-dial
Make the connection across terminals 6 and 7 and the 6-dial as short as possible. Short terminals 6 and 8.
Cont’d on next page key to display [ ] (10Ω calibration display). Set the (5) Press the 6-dial to 10Ω.. When the value on the No.2 display has stabilized key to temporarily (changes of several digits max.), press the store the calibration data. key to display [ ] (0Ω calibration display). Set the (6) Press the 6-dial to 10Ω.. When the value on the No.2 display has stabilized (changes of several digits max.), press the key to temporarily store the calibration data. 4--15
Page 55
E5CK
CHAPTER 4 APPLIED OPERATION
From previous page
(7) Next, calibrate the transfer output function. If the transfer output key. The disfunction is not supported, skip to step (11). Press the play changes to [ ] (20mA calibration display). or keys while monitoring the (8) Set the output to 20mA by the voltage on the digital multimeter. In the example on the left, the display indicates that the value two digits smaller than before calibration is “20mA”. (9) Press the key. The display changes to [ ] (4mA calibration display). (10) Set the output to 4mA by the or keys while monitoring the voltage on the digital multimeter. In the example on the left, the display indicates that the value two digits smaller than before calibration is “4mA”. (11) Press the key until the display changes to the data save display. key. The No.2 display changes to [ ], and two Press the seconds later the calibration data is saved to internal memory. If you key when the No.2 display reads [ ], the calibration press the data is invalidated. (12) This completes calibration of the platinum resistance thermometer. Press the key to return the display to [ ].
4--16
Page 56
E5CK
4.5 Calibration
J Calibrating current input F Preparation
AC100-240V (AC/DC24V ) SOURCE
5
11 12
4 3 2 1
10 9 8
13 14
7 6
STV
DMM • In the above figure, STV refers to a standard DC current/voltage source, and DMM refers to a precision digital multimeter. However, note that the DMM is required only when the transfer output function is supported.
F Calibration
This example describes how to calibrate a current input when the transfer output function is supported. If the transfer output function is not supported, skips steps (4) to (7). ] is displayed, the 30-minute timer is displayed on the (1) When [ No.2 display and counts down. This timer serves as a guide for the aging time when aging is required. (2) Press the key. The display changes to [ ] (20mA calibration display). Set the STV output to 20mA. When the value on the No.2 display has stabilized (changes of several digits max.), press the key to temporarily store the calibration data. key. The display changes to [ ] (0mA calibration (3) Press the display). Set the STV output to 0 mA. When the value on the No.2 display has stabilized (changes of several digits max.), press the key to temporarily store the calibration data. (4) Next, calibrate the transfer output function. If the transfer output key. The disfunction is not supported, skip to step (8). Press the play changes to [ ] (20mA calibration display). (5) Set the output to 20mA by the or keys while monitoring the voltage on the digital multimeter. In the example on the left, the display indicates that the value two digits smaller than before calibration is “20mA”. key. The display changes to [ ] (4mA calibration (6) Press the display). (7) Set the output to 4mA by the or keys while monitoring the voltage on the digital multimeter. In the example on the left, the display indicates that the value two digits smaller than before calibration is “4mA”. (8) Press the key until the display changes to the data save display. key. The No.2 display changes to [ ], and two Press the seconds later the calibration data is saved to internal memory. If you key when the No.2 display reads [ ], the calibration press the data is invalidated. (9) This completes calibration of current input. Press the key to return the display to [ ]. 4--17
Page 57
E5CK
CHAPTER 4 APPLIED OPERATION
J Calibrating voltage input F Preparation
AC100-240V (AC/DC24V ) SOURCE
5
11 12
4 3 2 1
10 9 8
13 14
7 6
STV
DMM • In the above figure, STV refers to a standard DC current/voltage source, and DMM refers to a precision digital multimeter. However, note that the DMM is required only when the transfer output function is supported.
F Calibration: 0 to 5 V, 1 to 5 V
This example describes how to calibrate voltage input when the transfer output function is supported. If the transfer output function is not supported, skips steps (4) to (7). ] is displayed, the 30-minute timer is displayed on the (1) When [ No.2 display and counts down. This timer serves as a guide for the aging time when aging is required. key. The display changes to [ ] (5 V calibration dis(2) Press the play). Set the STV output to 5V. When the value on the No.2 display has stabilized (changes of several digits max.), press the key to temporarily store the calibration data. (3) Press the key. The display changes to [ ] (0V calibration display). Set the STV output to 0V. When the value on the No.2 display has stabilized (changes of several digits max.), press the key to temporarily store the calibration data. (4) Next, calibrate the transfer output function. If the transfer output function is not supported, skip to step (8). Press the key. The display changes to [ ] (20mA calibration display). or keys while monitoring the (5) Set the output to 20mA by the voltage on the digital multimeter. In the example on the left, the display indicates that the value two digits smaller than before calibration is “20mA”. key. The display changes to [ ] (4mA calibration (6) Press the display). or keys while monitoring the (7) Set the output to 4mA by the voltage on the digital multimeter. In the example on the left, the display indicates that the value two digits smaller than before calibration is “4mA”. key until the display changes to the data save display. (8) Press the key. The No.2 display changes to [ ], and two Press the seconds later the calibration data is saved to internal memory. If you key when the No.2 display reads [ ], the calibration press the data is invalidated. (9) This completes calibration of voltage input (0 to 5V, 1 to 5V). Press the key to return the display to [ ].
4--18
Page 58
E5CK
4.5 Calibration
F Calibration : 0 to 10V
This example describes how to calibrate voltage input when the transfer output function is supported. If the transfer output function is not supported, skips steps (4) to (7). ] is displayed, the 30-minute timer is displayed on the (1) When [ No.2 display and counts down. This timer serves as a guide for the aging time when aging is required. (2) Press the key. The display changes to [ ] (10V calibration display). Set the STV output to 10V. When the value on the No.2 diskey play has stabilized (changes of several digits max.), press the to temporarily store the calibration data. (3) Press the key. The display changes to [ ] (0V calibration display). Set the STV output to 0V. When the value on the No.2 display key to has stabilized (changes of several digits max.), press the temporarily store the calibration data. (4) Next, calibrate the transfer output function. If the transfer output function is not supported, skip to step (8). Press the ] (20mA calibration display). play changes to [ (5) Set the output to 20mA by the or key. The dis- keys while monitoring the voltage on the digital multimeter. In the example on the left, the display indicates that the value two digits smaller than before calibration is “20mA”. (6) Press the display).
key. The display changes to [
(7) Set the output to 4mA by the or
] (4mA calibration keys while monitoring the voltage on the digital multimeter. In the example on the left, the display indicates that the value two digits smaller than before calibration is “4mA”. (8) Press the Press the key until the display changes to the data save display. key. The No.2 display changes to [
], and two seconds later the calibration data is saved to internal memory. If you press the key when the No.2 display reads [ data is invalidated.
], the calibration
(9) This completes calibration of voltage input (0 to 10V). Press the key to return the display to [ ].
4--19
Page 59
E5CK
CHAPTER 4 APPLIED OPERATION
J Checking indication accuracy
• After calibrating input, make sure that you check indication accuracy to make sure that the E5CK controller has been correctly calibrated. • Operate the E5CK controller in the PV/SP monitor (level 0 mode) mode. • Check the indication accuracy at the upper and lower limits and midpoint.
F Thermocouple
• Preparation The following figure shows the required device connection. Make sure that the E5CK controller and cold junction compensator are connected by a compensating conductor for the input type that is to be used during actual operation.
AC100-240V (AC/DC24V ) SOURCE
5
11 12
4 3 2 1
10 9 8
13 14
Cold junction compensator
7 6
STV Compensating conductor
• Operation Make sure that the cold junction compensator is at 0_C, and set STV output to the voltage equivalent to the starting power of the check value.
F Platinum resistance thermometer
• Preparation The following figure shows the required device connection.
AC100-240V (AC/DC24V ) SOURCE
5
11 12
10
4 3
9 8
2 1
7 6
13 14
6-dial
• Operation Set the 6-dial to the resistance equivalent to the check value.
F Current or voltage input
• Preparation The following figure shows the required device connection.
AC100-240V (AC/DC24V ) SOURCE
5
11 12
10
4 3
9 8
2 1
7 6
13 14
STV
• Operation Set the STV to the current or voltage value equivalent to the check value. 4--20
Page 60
CHAPTER 5 PARAMETERS
5
CHAPTER 5 PARAMETERS This chapter describes the parameters of the E5CK. Use this chapter as a reference guide.
Conventions Used in this Chapter . . . . . . . . . . . .
5-2
Protect Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3
Manual Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-5
Level 0 Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-6
Level 1 Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-9
Level 2 Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-15
Setup Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-21
Expansion Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-27
Option Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-32
Calibration Mode . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-36
5--1