The text of a manual · part 7 of 14
E5CK Digital Controller User's Manual, pages 61 to 70
Pages 61 to 70 of 138
The original document is the PDF (1.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron E5CK
Page 61
E5CK
CHAPTER 5 PARAMETERS
Conventions Used in this Chapter J The meaning of icons used in this chapter Describes the functions of the parameter.
Function
Describes the range and defaults of the parameter setting. Comment
Used for monitor-dedicated parameters. Describes the range of the monitor values. Monitor
Describes a procedure using parameters in operating instructions.
Example of use
Describes related parameters and items. See
Describes models of the E5CK or option units supporting the parameter being described. Model
J About parameter display On the E5CK controller, only parameters that can be used are displayed. These parameters are displayed only when the “Conditions of Use” on the right of the parameter heading are satisfied. However, note that the settings of protected parameters are still valid, and are not displayed regardless of the conditions of use.
AT Execute/cancel
5--2
Conditions of Use The controller must be in operation.
Page 62
E5CK
Protect Mode • The protect mode is for disabling (protecting) the functions of the menu key or A/M key. Before changing parameters in this mode, first make sure that protecting the menu key or A/M key will not cause any problems in operation. • To select this mode, press the A/M key and key simultaneously for 1 second mini- mum. To exit this mode, press the A/M key and key down again simultaneously for 1 second minimum. • The following table shows the parameters supported in this mode and the page where the parameter is described. Symbol
Parameter Name Security [A/M] key protect
Page 5-3 5-4
Security
• This parameter specifies which parameters are protected. However, note that the protect mode and manual mode cannot be protected. Function
Comment
• When this parameter is set to “0” to “3”, only the modes indicated by the “f” mark in the table below can be selected on the menu display. For example, when this parameter is set to “2”, only level 0 to 2 modes can be selected. Mode Calibration Option Expansion Setup Level 2 Level 1 Level 0
0 f f f f f f f
Set value 3 4
1
2 f f f f f f f f f f f f
5
6 f
∗
• When this parameter is set to “4” to “6”, operations in only the level 0 mode can be selected, and the mode is not displayed on the menu display. • When this parameter is set to “5”, only the “PV/SP” parameter in the level 0 mode can be used. • When this parameter is set to “6”, only the “PV/SP” parameter in the level 0 mode can be used. (The set point cannot change.) • Default is “1”. (Only the calibration mode is protected.)
F Related article 3.5 Protect Mode (page 3-10) See
5--3
Page 63
E5CK
CHAPTER 5 PARAMETERS
Protect Mode
[A/M] key protect
• Invalidate the function of the key. In other words, you cannot switch between the auto and manual operations by key operation. Function
Comment
•[
] : A/M key protect ON
•[
] : A/M key protect canceled
• Default = [
]
F Related article 3.5 Protect Mode (page 3-10) See
5--4
Page 64
E5CK
Manual Mode • In this mode, manual operations are possible, and the “MANU” LED lights. • When this mode is selected, the manipulated variable that was active immediately before the mode was switched to is output. When changing the manipulated variable, change it using the or keys. When this mode is selected during auto-tuning, auto-tuning is canceled. • To select this mode when in the level 0 to 2 modes, press the A/M key for 1 second minimum. To exit this mode, press the A/M key for 1 second minimum. The mode changes to the level 0 mode. • “Manual MV” is the only parameter available in this mode.
Manual MV
• Set the manipulated variable for manual operation. • The process value is displayed on the No.1 display, and the manipulated variable is Function displayed on the No.2 display. Change the manipulated variable using the or keys. Process value Manipulated variable [MANU] LED
The manual manipulated variable is held when the power is interrupted.
Comment
Control Method Standard Heating and cooling
Setting Range -5.0 to 105.0 -105.0 to 105.0
Unit
Default
% %
0 0
F Related article 3.7 Adjusting Control Operation (page 3-12) See
5--5
Page 65
E5CK
CHAPTER 5 PARAMETERS
Level 0 Mode • The parameters in this mode can be used only when the “security” parameter (protect mode) is set to “0” to “4”. • The “PV/SP” parameter can also be used when the “Security” parameter is set to “5” or “6”. However, note that when set to “6”, the SP cannot be changed. • This mode is used for monitoring the process value, set point and manipulated variable during operation, and for checking and setting the SP setting value. It is also used for starting and stopping controller operation. • To select this mode when in the levels 1 and 2, setup, expansion, option and calibration modes, press the key for 1 second minimum. The display changes to the menu display. If you select [ ] then press controller enters the level 0 mode. • To select parameters in this mode, press the or keys. use the key for 1 second minimum, the key. To change parameter settings,
• The following table shows the parameters supported in this mode and the page where the parameter is described. Symbol
Parameter Name
Page
PV/SP
5-6
Set point during SP ramp
5-7
MV monitor (heat)
5-7
MV monitor (cool)
5-7
Run/Stop
5-8
Process value
PV/SP
Function
Set point
• The process value is displayed on the No.1 display, and the set point is displayed on the No.2 display. The set point can be set. • When the multi-SP function is in use, the value of whichever is set, set point 0 or 1, is linked. • The decimal point position is dependent on the selected sensor during temperature input and on the results of scaling during analog input. • Process value Monitor Range
Comment
Scaling lower limit -10%FS to scaling upper limit +10%FS
Unit EU
During temperature input, the range of the currently selected sensor is taken as the monitor range. • Set point Setting Range SP setting lower limit to SP setting upper limit
See
5--6
Unit
Default
EU
0
F Related article 3.7 Adjusting Control Operation (page 3-12) F Related parameters “Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode) “SP setting upper limit” “SP setting lower limit” (expansion mode)
Page 66
E5CK
Level 0 Mode Set point during SP ramp
Conditions of Use The SP ramp function must be enabled.
• Sets the set point. Function
Unit EU
Moniter Range SP setting lower limit to SP setting upper limit
Default 0
Monitor
F Related article 3.7 Adjusting Control Operation (page 3---12) See
F Related parameters “PV/SP” (level 0 mode) “SP ramp time unit” “SP ramp set value” (level 2 mode) “Set point upper limit” “Set point lower limit (expansion mode)
MV monitor (heat) MV monitor (cool)
• This parameter cannot be set. • Monitors the manipulated variable on the heating or cooling side. Function
• The manipulated variable in a standard control system is checked in the “MV monitor (heat)” parameter. • The “MV monitor (cool)” parameter can be used only during heating and cooling control. • MV monitor (heat) Control
Monitor
Standard Heating and cooling
Monitor Range -5.0 to 105.0 0.0 to 105.0
Unit
Monitor Range 0.0 to 105.0
Unit
% %
• MV monitor (cool) Control Heating and cooling
%
5--7
Page 67
E5CK
CHAPTER 5 PARAMETERS
Level 0 Mode Run/Stop
• This parameter is used for checking the operating status of the controller, and for specifying start and stop of operation. Function
• When the “run/stop” function is assigned to event input, “stop” is set when event input is ON, and “run” is set when event input is OFF. Parameter setting follows event input, even if attempting to change settings by key operation. • To start operation, set this parameter to [
Example of use operation, set this parameter to [ LED lights. • Default is [
] press the
5--8 keys. To stop
]. When operation is stopped, the “STOP”
]
F Related article 3.6 Starting and Stopping Operation (page 3-11) See or
Page 68
E5CK
Level 1 Mode • The parameters in this mode can be used only when the “security” parameter (protect mode) is set to “0” to “3”. • This mode contains the main parameters for adjusting control. These parameters include parameters for executing AT (auto-tuning), setting the alarm values, setting the control period, and setting PID parameters. • To select this mode when in the levels 0 and 2, setup, expansion, option and calibrakey for 1 second minimum. The display changes to the tion modes, press the menu display. If you select [
] then press the key for 1 second minimum, the controller enters the level 1 mode. • To select parameters in this mode, press the use the or key. To change parameter settings, keys.
• The following table shows the parameters supported in this mode and the page where the parameter is described. Symbol
Parameter Name
Page
AT Execute/Cancel
5-10
Set point 0
5-10
Set point 1
5-10
Alarm value 1
5-11
Alarm value 2
5-11
Alarm value 3
5-11
Proportional band
5-11
Integral time
5-11
Derivative time
5-11
Cooling coefficient
5-12
Dead band
5-12
Manual reset value
5-13
Hysteresis (heat)
5-13
Hysteresis (cool)
5-13
Control period (heat)
5-14
Control period (cool)
5-14
5--9
Page 69
E5CK
CHAPTER 5 PARAMETERS
Level 1 Mode AT Execute/Cancel
Function
Conditions of Use The controller must be in operation, control must be advanced PID control, and ST must be set to OFF.
• Selects the limit cycle of MV change width (40% or 100%) for execution. After AT execution, the “PID” and the “LBA detection time” (LBA: Loop Break Alarm) parameters are set automatically. • During heating and cooling control, only 100%AT can be executed. • When this parameter is selected, the setting becomes [
Example of use
].
• To execute 40%AT, select [ ], and to execute 100%AT, select [ ]. During execution of auto-tuning, the AT LED flashes. However, note that during heating and cooling control, [ ] is not displayed. • When AT execution ends, the parameter setting automatically returns to [
].
F Related article 3.7 Adjusting Control Operation (page 3-13) See
F Related parameters “Run/Stop” (level 0 mode) “Proportional band” “Integral time” “Derivative time” (level 1 mode) “LBA detection time” (level 2 mode)
Set point 0 Set point 1
Conditions of Use The multi-SP function must be in operation.
• When event input is OFF, the “set point 0” parameter is used, and when ON, the “set point 1” parameter is used. Function
• When the “set point” parameter has been changed, the setting of whichever is selected in event input, “set point 0” or “set point 1”, is linked and changed. • The decimal point position is dependent on the selected sensor during temperature input and on the results of scaling during analog input. Setting Range Scaling lower limit to Scaling upper limit
Unit
Default
EU
0
Comment
F Related article 4.3 How to Use Option Functions (page 4-8) See
5--10
F Related parameters “Multi-SP function” (option mode) “Set point” (level 0 mode) “Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode)
Page 70
E5CK
Level 1 Mode Alarm value 1
Conditions of Use Alarms must be assigned as outputs. For example, if alarm outputs 1 and 2 only are assigned as outputs, the “alarm value 3” parameter cannot be used.
Alarm value 2 Alarm value 3
Function
• This parameter is used for monitoring or changing the alarm values of alarm outputs 1 to 3. • During temperature input, the decimal point position is dependent on the currently selected sensor, and during analog input on the results of scaling. Setting Range -1999 to 9999
Unit
Default
EU
0
Comment
See
F Related article 3.7 Adjusting Control Operation (page 3-12) F Related parameters “Input type” “Scaling upper limit” “Scaling lower limit” Decimal point” “Control output 1 assignment” “Control output 2 assignment” “Auxiliary output 1 assignment” “Alarm 1 type” “Alarm 2 type” “Alarm 3 type” “Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm” (setup mode) “Alarm 1 hysteresis” “Alarm 2 hysteresis” “Alarm 3 hysteresis” (level 2 mode) “Standby sequence reset method” (expansion mode)
Proportional band
Conditions of Use Control must be advanced PID control, and ST must be set to OFF.
Integral time Derivative time
• Sets the PID parameters. However, note that the PID parameter settings are changed to optimum values when auto-tuning is executed, and self-tuning is selected. Function
Comment
Parameter Proportional band Integral time Derivative time
Setting Range 0.1 to 999.9 0 to 3999 0 to 3999
Unit
Default
%FS Second Second
10.0 233 40
F Related parameter “AT Execute/Cancel” (level 1 mode) See
5--11