The text of a manual · part 8 of 14

E5CK Digital Controller User's Manual, pages 71 to 80

Pages 71 to 80 of 138

The original document is the PDF (1.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron E5CK

Page 71

E5CK

CHAPTER 5 PARAMETERS

Level 1 Mode Cooling coefficient

Function

Conditions of Use The control must be heating and cooling control, and advanced PID control.

• In heating and cooling control, P at the cooling side is calculated by the following formula: Cooling side P = cooling coefficient ¢ P

Setting Range 0.01 to 99.99

Unit

Default

None

1.00

Comment

See

F Related article 4.1 Selecting the Control Method (page 4-2) F Related parameter “Proportional band” (level 1 mode)

Dead band

Conditions of Use The control system must be heating and cooling control.

• Sets the output dead band width in a heating and cooling control system. A negative setting sets an overlap band. Function

Setting Range -19.99 to 99.99

Unit

Default

%FS

0.00

Comment

F Related article 4.1 Selecting the Control Method (page 4-2) See

5--12

Page 72

E5CK

Level 1 Mode Manual reset value

Conditions of Use The control must be standard control, advanced PID control, ST must be set to OFF, and the “integral time” parameter must be set to “0”.

• Sets the required manipulated variable to remove offset during stabilization of P or PD control. Function

Setting Range 0.0 to 100.0

Unit

Default

%

50.0

Comment

Hysteresis (heat)

Conditions of Use The control system must be ON/OFF control.

Hysteresis (cool)

• Sets the hysteresis for ensuring stable operation at ON/OFF switching. Function

• In standard control, use the “hysteresis (heat)” parameter. The “hysteresis (cool)” parameter cannot be used. • In heating and cooling control, the hysteresis can be set independently for heating and cooling. Use the “hysteresis (heat)” parameter to set the heating side hysteresis, and use the “hysteresis (cool)” parameter to set the cooling side hysteresis.

Comment

Parameter Hysteresis (heat) Hysteresis (cool)

Setting Range 0.01 to 99.99 0.01 to 99.99

Unit %FS %FS

Default 0.10 0.10

F Related article 4.1 Selecting the Control Method (page 4-3) See

F Related parameters “Control output 1 assignment” “Control output 2 assignment” (setup mode) “PID / ON/OFF” (expansion mode)

5--13

Page 73

E5CK

CHAPTER 5 PARAMETERS

Level 1 Mode Control period (heat) Control period (cool)

Conditions of Use Relay or voltage output must be set as the outputs, and the control must be set to advanced PID control.

• Sets the pulse output period. Set the control period taking the control characteristics and life expectancy of the controller into consideration. Function

• In standard control, use the “control period (heat)” parameter. The “control period (cool)” parameter cannot be used. • In heating and cooling control, the control period can be set independently for heating and cooling. Use the “control period (heat)” parameter to set the heating side control period, and use the “contrlo period (cool)” parameter to set the cooling side control period.

Comment

Parameter Control period (heat) Control period (cool)

Setting Range 1 to 99 1 to 99

Unit

Default

Second Second

20 20

F Related article 3.3 Setting Output Specifications (page 3-5) See

5--14

F Related parameters “Control output 1 assignment” “Control output 2 assignment” (setup mode)

Page 74

E5CK

Level 2 Mode • The parameters in this mode can be used only when the “security” parameter (protect mode) is set to “0” to “2”. • This mode contains the auxiliary parameters for adjusting control. These parameters include parameters for limiting the manipulated variable and set point, parameters for switching between remote and local operation, and parameters for setting the LBA (Loop Break Alarm), alarm hysteresis, and input digital filter values. • To select this mode when in the levels 0 and 1, setup, expansion, option and calibrakey for 1 second minimum. The display changes to the tion modes, press the menu display. If you select [

] using the key then press the key for

1 second minimum, the controller enters the level 2 mode. • To select parameters in this mode, press the use the or key. To change parameter settings, keys.

• The following table shows the parameters supported in this mode and the page where the parameter is described. Symbol

Parameter Name

Page

Remote/Local

5-16

SP ramp time unit

5-16

SP ramp set value

5-16

LBA detection time

5-17

MV at stop

5-17

MV at PV error

5-17

MV upper limit

5-18

MV lower limit

5-18

MV change rate limit

5-18

Input digital filter

5-19

Alarm 1 hysteresis

5-19

Alarm 2 hysteresis

5-19

Alarm 3 hysteresis

5-19

Input shift upper limit (temperature)

5-20

Input shift lower limit (temperature)

5-20

5--15

Page 75

E5CK

CHAPTER 5 PARAMETERS

Level 2 Mode Remote/Local

Conditions of Use The communications function must be in use.

• Switches between remote and local operation. Function

• To change the parameter setting during remote operation, use the communications function. To change the parameter setting during local operation, change the setting on the E5CK controller. • You can check the parameter setting by both communications and on the E5CK controller regardless of whether the controller is switched to remote or local operation.

Default

Setting Range [

]: remote / [

[

]: local

]

Comment

SP ramp time unit

Conditions of Use ST must be set to OFF.

SP ramp set value

Function

• Specifies the change rate during SP ramp operation. Set the maximum permissible change width per unit of time (minute or hour) as the “SP ramp set value”. However, note that when set to “0”, the SP ramp function is disabled. • The time unit and SP ramp set value are independent of each other. For example, when setting “30 per minute”, set the “SP ramp set value” parameter to “30” and the ] (“minute”). However, if you change the “SP ramp time unit” parameter to [ time unit only to [

] (“hour”), the set time becomes “30 per hour.”

• During temperature input, the decimal point position of the SP ramp set value is dependent on the currently selected sensor, and during analog input on the results of scaling. Parameter SP ramp time unit Comment

SP ramp set value

[

Unit

Setting Range ]: minute/ [ ]: hour

None

0 to 9999

EU

Default 0

During temperature input, the range of the currently selected sensor it taken as the setting range for the “SP ramp set value” parameter. F Related article 4.2 Operating Condition Restrictions (page 4-5) See

5--16

F Related parameters “Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode)

Page 76

E5CK

Level 2 Mode

LBA detection time

Conditions of Use The LBA (Loop Break Alarm) function must be assigned as an output.

• This parameter is automatically set by AT execution. Function

• The LBA is output if the change width of the process value falls below 0.2 %full-scale of the time preset to this parameter when the manipulated variable is set in the “MV upper limit” or “MV lower limit” parameters. • The LBA function is disabled when this parameter is set to “0”. Setting Range 0 to 9999

Unit

Default

Second

0

Comment

See

F Related article 4.4 LBA (page 4-9) 7.3 How to Use Error Output (page 7-5) F Related parameters “AT Execute/Cancel” (level 1 mode) “Control output 1 assignment” “Control output 2 assignment” “Auxiliary output 1 assignment” (setup mode)

MV at stop MV at PV error

• The “MV at stop” parameter sets the manipulated variable when operation stops. Function

• The “MV at PV error” parameter sets the manipulated variable when an input error occurs. • The setting ranges during standard control and heating and cooling control are different.

Comment

• The manipulated variable at the cooling side during heating and cooling control is expressed as a negative value. Control Method Standard Heating and cooling

See

F Related articles MV at stop MV at PV error

Setting Range -5.0 to 105.0 -105.0 to 105.0

Unit

Default

% %

0 0

: 3.6 Starting and Stopping Operation (page 3-11) : 7.2 How to Use the Error Display (page 7-3) 5--17

Page 77

E5CK

CHAPTER 5 PARAMETERS

Level 2 Mode MV upper limit

Conditions of Use The control must be advanced PID control, and ST must be set to OFF.

MV lower limit MV change rate limit

Function

• The “MV upper limit” and “MV lower limit” parameters set the upper and lower limits of the manipulated variable. When the manipulated variable calculated by the E5CK controller is outside of the upper-and lower-limit range, the upper limit or lower limit set to these parameters is output, respectively. • The “MV change rate limit” parameter sets the maximum permissible change width per second of the manipulated variable. If a change in the manipulated variable causes this parameter setting to be exceeded, the calculated value is reached while changing the value by the per-second value set in this parameter. The “MV change rate limit” function is disabled when this parameter is set to “0.0”.

Comment

• MV upper limit The setting ranges during standard control and heating and cooling control are different. Also, the manipulated variable at the cooling side during heating and cooling control is expressed as a negative value. Control Method Standard Heating and cooling

Setting Range MV lower limit +0.1 to 105.0 0.0 to 105.0

Unit

Default

% %

105.0 105.0

• MV lower limit The setting ranges during standard control and heating and cooling control are different. Also, the manipulated variable at the cooling side during heating and cooling control is expressed as a negative value. Control Method Standard Heating and cooling

Setting Range -5.0 to MV upper limit -0.1 -105.0 to 0.0

• MV change rate limit Setting Range 0.0 to 100.0

Unit

Default

%

0.0

F Related article 4.2 Operating Condition Restrictions (page 4-4) See

5--18

Unit

Default

% %

-5.0 -105.0

Page 78

E5CK

Level 2 Mode Input digital filter

• Sets the time constant of the input digital filter. The following figures shows the effect on data after passing through the digital filter. Function

PV before passing through filter

A PV after passing through filter

0.63A Time constant

Time

Input digital filter

Setting Range 0 to 9999

Unit

Default

Second

0

Comment

Alarm 1 hysteresis

Conditions of Use Alarms must be assigned as outputs. For example, if alarm outputs 1 and 2 only are assigned as outputs, the “alarm 3 hysteresis” parameter cannot be used.

Alarm 2 hysteresis Alarm 3 hysteresis

• This parameter is for checking the hysteresis of alarm outputs 1 to 3. Function

Setting Range 0.01 to 99.99

Unit

Default

%FS

0.02

Comment

F Related article 3.4 Setting Alarm Type (page 3-7) See

F Related parameters “Alarm 1 type” “Alarm 2 type” “Alarm 3 type” “Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm” (setup mode) “Alarm value 1” “Alarm value 2” “Alarm value 3” (level 1 mode) 5--19

Page 79

E5CK

CHAPTER 5 PARAMETERS

Level 2 Mode Input shift upper limit Input shift lower limit

Conditions of Use The input type must be set to temperature input (thermocouple or platinum resistance thermometer).

• Sets each of the shift amounts for the input shift upper and lower limit values. Function

Setting Range -199.9 to 999.9

Unit _C or _F

Default 0.0

Comment

F Related article 3.2 Setting Input Specifications (page 3-3) See

5--20

F Related parameter “Input type” (setup mode)

Page 80

E5CK

Setup Mode • The parameters in this mode can be used only when the “security” parameter (protect mode) is set to “0” and “1”. • This mode contains the parameters for setting the basic specifications of the E5CK controller. These parameters include parameters for specifying the input type, scaling, output assignments, and direct/reverse operation. • To select this mode when in the levels 0 to 2, expansion, option and calibration modes, key for 1 second minimum. The display changes to the menu display.

press the If you select [

] using the key then press the key for 1 second mini- mum, the controller enters the setup mode. • To select parameters in this mode, press the use the or key. To change parameter settings, keys.

• The following table shows the parameters supported in this mode and the page where the parameter is described. Symbol

Parameter Name

Page

Input type

5-22

Scaling upper limit

5-23

Scaling lower limit

5-23

Decimal point

5-23

_C/_F selection

5-24

Parameter initialize

5-23

Control output 1 assignment

5-24

Control output 2 assignment

5-24

Auxiliary output 1 assignment

5-25

Alarm 1 type

5-25

Alarm 1 open in alarm

5-26

Alarm 2 type

5-25

Alarm 2 open in alarm

5-26

Alarm 3 type

5-25

Alarm 3 open in alarm

5-26

Direct/Reverse operation

5-26

5--21