Page 81

E5CK

CHAPTER 5 PARAMETERS

Setup Mode Input type

• Match the setting (software) of this parameter with the setting (hardware) of the input type jumper connector. Function

• Set the input types to be connected to terminal Nos. 6 to 8 by the input type codes in the table below. • Set the code according to the following table. Default is “2: K1 thermocouple”. Input Type

Set value

Comment

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

JPt -199.9 to 650.0 (_C) Pt -199.9 to 650.0 (_C) K1 -200 to 1300 (_C) K2 0.0 to 500.0 (_C) J1 -100 to 850 (_C) J2 0.0 to 400.0 (_C) T -199.9 to 400.0 (_C) E 0 to 600 (_C) L1 -100 to 850 (_C) L2 0.0 to 400.0 (_C) U -199.9 to 400.0 (_C) N -200 to 1300 (_C) R 0 to 1700 (_C) S 0 to 1700 (_C) B 100 to 1800 (_C) W 0 to 2300 (_C) PLII 0 to 1300 (_C) 4 to 20mA 0 to 20mA 1 to 5V 0 to 5V 0 to 10V

/-199.9 to 999.9 (_F) /-199.9 to 999.9 (_F) /-300 to 2300 (_F) /0.0 to 900.0 (_F) /-100 to 1500 (_F) /0.0 to 750.0 (_F) /-199.9 to 700.0 (_F) /0 to 1100 (_F) /-100 to 1500 (_F) /0.0 to 750.0 (_F) /-199.9 to 700.0 (_F) /-300 to 2300 (_F) /0 to 3000 (_F) /0 to 3000 (_F) /300 to 3200 (_F) /0 to 4100 (_F) /0 to 2300 (_F)

Jumper Position Platinum resistance thermometer

TC⋅PT

Thermocouple

TC⋅PT

Current input

I

Voltage input

V

F Related article 3.2 Setting Input Specifications (page 3-3) See

5--22

F Related parameters When input type is set to temperature input: “_C/_F selection” (setup mode) When input type is set to voltage input or current input: “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode)

Page 82

E5CK

Setup Mode Scaling upper limit

Conditions of Use The input type must be set to analog input (voltage or current input).

Scaling lower limit Decimal point

• This parameter can be used only when voltage input or current input is selected as the input type. Function

• When voltage input or current input is selected as the input type, scaling is carried out. Set the scaling upper limit in the “scaling upper limit” parameter and the scaling lower limit in the “scaling lower limit” parameter. • The “decimal point” parameter specifies the decimal point position of parameters (set point, etc.) whose unit is set to EU (Engineering Unit). • Scaling upper limit, Scaling lower limit

Comment

Parameter Scaling upper limit Scaling lower limit

Setting Range Scaling lower limit +1 to 9999 -1999 to scaling upper limit -1

Unit EU EU

Default 100 0

• Decimal point : default : 0 Set Value 0 1 2 3

Setting

Example

0 digits past decimal point 1 digit past decimal point 2 digits past decimal point 3 digits past decimal point

1234 123.4 12.34 1.234

F Related article 3.2 Setting Input Specifications (page 3-3) See

F Related parameter “Input type” (setup mode)

Parameter initialize

Function

• Returns parameter settings to their defaults. However, note that the following parameters are not affected by execution of this parameter: “input type”, “scaling upper limit”, “scaling lower limit”, “decimal point” and “_C/_F selection”. • When this parameter is selected, [ ters, press the

Example of use key to specify [

] (“no”) is first displayed. To initialize parame] (“yes”). 5--23

Page 83

E5CK

CHAPTER 5 PARAMETERS

Setup Mode _C/_F selection

Conditions of Use The input type must be set to temperature input (thermocouple or platinum resistance thermometer).

• This parameter can be used when thermocouple or platinum resistance thermometer is selected as the input type. Function

• Set the temperature input unit to either of “_C” or “_F”. Setting Range : _C /

Default

: _F

Comment

F Related article 3.2 Setting Input Specifications (page 3-3) See

F Related parameter “Input type” (setup mode)

Control output 1 assignment Control output 2 assignment • Assigns the output functions to either of control output 1 or 2. • The following six output functions can be assigned as outputs: Function

Control output (heat), Control output (cool), Alarms 1 to 3, and LBA. • Errors 1 and 2 cannot be assigned as outputs. • When the output function assigned to control output 1 is ON, the OUT1 LED lights. However, note that the OUT1 LED does not light when control output (heat) or control output (cool) are assigned to linear outputs such as current and voltage. • When the output function assigned to control output 2 is ON, the OUT2 LED lights. Symbol Function

Comment

Control output (heat)

Defaults: “Control output 1” = [

Control output (cool)

], “Control output 2” = [

F Related article 3.3 Setting Output Specifications (page 3-5) See

F Related parameters • Alarm-related parameters • Heating and cooling related parameter “LBA detection time” (level 2 mode)

5--24

Alarm 1

Alarm 2

]

Alarm 3

LBA

Page 84

E5CK

Setup Mode Auxiliary output 1 assignment

Function

• Assigns output functions to auxiliary output 1. The following six output functions can be assigned as outputs: Alarms 1 to 3, LBA, Error 1 (input error), and Error 2 (A/D converter error). • Control output (heat) and control output (cool) cannot be assigned as outputs. • When the output function assigned to auxiliary output 1 is ON, the SUB1 LED lights. Symbol

Comment

See

Function

Alarm 1

Defaults: [

]

Alarm 2

Alarm 3

LBA

Error 1

Error 2

F Related article 3.3 Setting Output Specifications (page 3-5) F Related parameter • Alarm-related parameter “LBA detection time” (level 2 mode)

Alarm 1 type

Conditions of Use Alarms must be assigned as outputs. For example, if alarm outputs 1 and 2 only are assigned as outputs, the ”alarm 3 type” parameter cannot be used.

Alarm 2 type Alarm 3 type

• “Alarm 1 to 3 type” parameters specify the operation of the alarm by the one of the set values in the following table. For details of operation at an alarm, see page 3-7. Function

Comment

Set Value 1

Settings Upper-and lower-limit alarm (deviation)

2 3 4

Upper-limit alarm (deviation)

5

Upper-and lower-limit alarm with standby sequence (deviation)

6

Upper-limit alarm with standby sequence (deviation)

Lower-limit alarm (deviation) Upper-and lower-limit range alarm (deviation)

Set Value 7

Settings Lower-limit alarm with standby sequence (deviation)

8 9 10

Absolute-value upper-limit alarm

11

Absolute-value lower-limit alarm with standby sequence

Absolute-value lower-limit alarm Absolute-value upper-limit alarm with standby sequence

Defaults: Deviation upper limit

See

F Related article 3.4 Setting Alarm Type (page 3-7) F Related parameters “Alarm value 1” “Alarm value 2” “Alarm value 3” (level 1 mode) “Alarm 1 hysteresis” “Alarm 2 hysteresis” “Alarm 3 hysteresis” (level 2 mode) “Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm” “Control output 1 assignment” “Control output 2 assignment” (setup mode) 5--25

Page 85

E5CK

CHAPTER 5 PARAMETERS

Setup Mode Alarm 1 open in alarm

Conditions of Use Alarms must be assigned as outputs. For example, if alarm outputs 1 and 2 only are assigned as outputs, the “alarm 3 open in alarm” parameter cannot be used.

Alarm 2 open in alarm Alarm 3 open in alarm

• Selects the output states of alarms 1 to 3. Function

• When the controller is set to ”close in alarm,” the status of the alarm output function is output as it is. When set to ”open in alarm,” the status of the alarm output function is output inverted. The following table shows the relationship between alarm output functions, output and output LEDs.

Close in alarm Open in alarm

Output ON OFF OFF ON

Alarm ON OFF ON OFF

Default

Setting Range : Close in alarm/

Output LED Lit Not lit Lit Not lit

:Open in alarm

Comment

F Related article 3.3 Setting Output Specifications (page 3-5) See

F Related parameters “Alarm value 1” “Alarm value 2” “Alarm value 3” (level 1 mode) “Alarm 1 hysteresis” “Alarm 2 hysteresis” “Alarm 3 hysteresis” (level 2 mode) “Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm” “Control output 1 assignment” “Control output 2 assignment” (setup mode)

Direct/Reverse operation

Function

• “Direct operation” (or normal operation) refers to control where the manipulated variable is increased according to the increase in the process value. Alternatively, “reverse operation” refers to control where the manipulated variable is increased according to the decrease in the process value. Setting Range : Reverse operation/

Default :Direct operation

Comment

F Related article 3.3 Setting Output Specifications (page 3-5) See

5--26

Page 86

E5CK

Expansion Mode • The parameters in this mode can be used only when the “security” parameter (protect mode) is set to “0” and “1”. • This mode contains the parameters for setting expanded functions. These parameters include parameters for setting ST (self-tuning), setting the SP setting limiter, selecting advanced PID and ON/OFF control, specifying the standby sequence reset method, and automatic return of display mode. • To select this mode when in the levels 0 to 2, setup, option and calibration modes, key for 1 second minimum. The display changes to the menu display.

press the If you select [

] using the key then press the key for 1 second mini- mum, the controller enters the expansion mode. • To select parameters in this mode, press the use the or key. To change parameter settings, keys.

• The following table shows the parameters supported in this mode and the page where the parameter is described. Symbol

Parameter Name

Page

Set point upper limit

5-28

Set point lower limit

5-28

PID / ON/OFF

5-28

ST

5-29

ST stable range

5-29

α

5-29

AT calculated gain

5-30

Standby sequence reset method

5-30

Automatic return of display mode

5-31

AT hysteresis

5-31

LBA detection width

5-31

5--27

Page 87

E5CK

CHAPTER 5 PARAMETERS

Expansion Mode Set point upper limit Set point lower limit

Function

• Limits the upper and lower limits of the set point. When the set point exceeds the settings of the “Set point upper limit” and “Set point lower limit” parameters, the E5CK controller regards the settings of the “Set point upper limit” and “Set point lower limit” parameters as the set points. • When the input type is changed to temperature input, the set point upper and lower limits are changed to the upper and lower limits of the currently selected sensor. And when the input type is changed to analog input, the set point upper and lower limits are changed to the scaling upper and lower limits. • During temperature input, the decimal point position is dependent on the currently selected sensor, and during analog input on the results of scaling.

Comment

Parameter SP setting upper limit SP setting lower limit

Setting Range SP setting lower limit +1 to scaling upper limit Scaling lower limit to SP setting upper limit -1

Unit

Default

EU EU

1300 -200

During temperature input, the range becomes the range of use of the selected sensor instead of the scaling upper and lower limit values. F Related article 4.2 Operating Condition Restrictions (page 4-5)

See

F Related parameters “Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode)

PID / ON/OFF

• Selects advanced PID control or ON/OFF control. Function

Setting Range : advance PID/

Default :ON/OFF

Comment

F Related article 4.1 Selecting the Control Method (page 4-3) See

5--28

F Related parameters “Hysteresis (heat)” “Hysteresis (cool)” (level 1 mode)

Page 88

E5CK

Expansion Mode ST

Conditions of Use The input type must be set to temperature input, and the control must be either standard control or advanced PID control.

ST stable range

Function

• When the “ST” parameter is set to “ON”, the self-tuning (ST) function is active. During operation of the ST function, the power on the load side connected to the control output must be turned ON at the same time or before start of E5CK operation. • The “ST stable range” parameter sets the stable range width during self-tuning. However, note that this parameter cannot be used when the “ST” parameter is set to “OFF”.

Parameter ST ST stable range

Comment

Setting Range : ST function OFF/ : ST function ON 0.1 to 999.9

Unit

Default

None _C or _F

15.0

F Related article Fuzzy self-tuning (page A-10) See

F Related parameters “Input type” (setup mode) “PID / ON/OFF” (expansion mode)

α

Conditions of Use The control must be advanced PID control, and ST must be set to OFF.

• Sets advanced PID-control parameter α. Function

Setting Range 0.00 to 1.00

Unit

Default

None

0.65

Comment

F Related parameter “PID / ON/OFF” (expansion mode) See

5--29

Page 89

E5CK

CHAPTER 5 PARAMETERS

Expansion Mode Conditions of Use The control must be advanced PID control, and ST must be set to OFF.

AT calculated gain

• Sets the gain when adjusting the PID parameters by auto-tuning. Function

• To give priority to response, decrease the set value of this parameter. To give priority to stability, increase the set value of this parameter. Setting Range 0.1 to 10.0

Unit

Default

None

1.0

Comment

See

F Related parameters “AT Execute/Cancel” (level 1 mode) “PID / ON/OFF” (expansion mode)

Standby sequence reset method

• Selects the conditions for enabling reset after the standby sequence of the alarm has been canceled. Function

• Condition A: Control started (including power ON), and set point, alarm value or input shift value changed, and when set points 1 and 2 are switched. • Condition B: Power ON Setting Range 0: Condition A / 1: Condition B

Default 0

Comment

F Related parameters “Alarm 1 type” “Alarm 2 type” “Alarm 3 type” (setup mode) See

5--30

Page 90

E5CK

Expansion Mode Automatic return of display mode

• If you do not operate any of the controller keys for the time set in this parameter when in levels 0 to 2 modes, the display automatically returns to the PV/SP display. Function

• When this parameter is set to “0”, this function is disabled. • This parameter is invalid while the menu is displayed. Setting Range 0 to 99

Unit

Default

Second

0

Comment

AT hysteresis

Conditions of Use The control must be advanced PID control, and ST must be set to OFF.

• The levels of limit cycle operations during AT execution are given hysteresis at event ON/OFF switching. This parameter sets this hysteresis width. Function

Setting Range 0.1 to 9.9

Unit

Default

%FS

0.2

Comment

LBA detection width

Conditions of Use The LBA (Loop Break Alarm) function must be assigned as an output.

• This parameter can be used when LBA is assigned as an output. Function

• When the change width of the manipulated variable is below the width set in this parameter, the controller regards this as detection of an LBA.

Setting Range 0.0 to 999.9

Unit

Default

%FS

0.2

Comment

5--31