The text of a manual · part 4 of 14

E5CK Digital Controller User's Manual, pages 31 to 40

Pages 31 to 40 of 138

The original document is the PDF (1.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron E5CK

Page 31

E5CK

CHAPTER 3 BASIC OPERATION

J Control period

• When the output unit is pulse output such as relay output, set the pulse output cycle (control period). Though a shorter pulse period provides better control performance, the control period should be set taking the life expectancy of the output unit into consideration when the output unit is relay. • The control period is set in the “control period (heat)” parameter (level 1 mode). Factory setting is “20:20 seconds.”

Setting Example

In this example, let’s set the parameters as follows: “control output 1 assignment” = “control output (heat)” “control output 2 assignment” = “alarm output 1” “direct/reverse operation” = “reverse operation” “control period” = “20 seconds” All of the above settings in this example are factory settings. So, in this example, we are only going to check the parameter settings.

(1) Select the menu display, and select [ or

] (setup mode) using the keys. For details on selecting the menu display, see page

1-7. (2) Press the setup mode [ key to enter the setup mode. The top parameter in the ] “input type” is displayed. In this example, the parameter setting is “17: 4 to 20 mA.” (3) Press the key until [

] (“control output 1 assignment” parameter) is displayed. The parameter default is [

]. key.

(4) As the setting in this example is to be left as it is, press the

] (“control output 2 assignment” The display changes to [ ]. parameter). The parameter default is [ key

(5) As the setting in this example is to be left as it is, press the 1 second min.

] (“direct/reverse operation” parameter) is displayed. until [ ]. The parameter default is [ (6) As the setting in this example is to be left as it is, press the or keys to select [ ] (level 1 mode). For details on selecting the menu display, see page 1-7. (7) Press the level 1 mode [ (8) Press the key to enter the level 1 mode. The top parameter in the ] “AT execute/cancel” is displayed. key until [

] (“control period” parameter) is dis- played. The parameter default is “20”. As the setting in this example is to be left as it is, quit key operation.

3--6

Page 32

E5CK

3.4 Setting Alarm Type

3.4 Setting Alarm Type • Three alarm outputs are supported: alarms 1 to 3. Of these, only the alarm assigned as the output can be used. • Alarm output conditions are determined according to the combination of the “alarm type”, “alarm value” and “alarm hysteresis” parameter settings. • The contact conditions when alarm output is ON can be set to “open” or “closed” in the “close in alarm/open in alarm” parameter.

J Alarm type

• The following table shows the alarm types supported by the E5CK controller and their respective operations. Alarm Type

Alarm Output Operation When X is positive

1

Upper-and lower-limit alarm (deviation)

ON OFF

2

Upper-limit alarm (deviation)

ON OFF

3

Lower-limit alarm (deviation)

ON OFF

Upper-and lower-limit alarm with standby sequence (deviation)

ON OFF

Upper-limit alarm with standby sequence (deviation)

ON OFF

7

Lower-limit alarm with standby sequence (deviation)

ON OFF

8

Absolute-value upper-limit alarm

5 6

9

Absolute-value lower-limit alarm

10

Absolute-value upper-limit alarm with standby sequence Absolute-value lower-limit

11 alarm with standby sequence

SP X SP X

ON OFF

Upper-and lower-limit range alarm (deviation)

4

X X

ON OFF ON OFF ON OFF ON OFF

SP X X

When X is negative

Always ON ON OFF

X

ON OFF

SP X SP

Always OFF

SP X X

Always OFF

SP X SP X SP X 0 X 0 X 0 X 0

ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF

X SP X SP X 0 X 0 X 0 X 0

• Alarm types are set independently for each alarm in the “alarm 1 to 3” parameters (setup mode). Factory setting is “2: Upper-limit alarm (deviation)”.

J Alarm value

• Alarm values are indicated by “X” in the table above. Alarm output operation differs according to whether the value of the alarm is positive or negative. • Alarm values are set independently for each alarm in the “alarm value 1 to 3” parameters (level 1 mode). Factory setting is “0”.

3--7

Page 33

E5CK

CHAPTER 3 BASIC OPERATION

J Alarm hysteresis

• The hysteresis of alarm outputs when alarms are switched ON/OFF can be set as follows. Upper limit alarm

Lower limit alarm

Alarm hysteresis ON

Alarm hysteresis ON

OFF

OFF Alarm value

Alarm value

• Alarm hysteresis is set independently for each alarm in the “alarm 1 to 3 hysteresis” parameters (level 2 mode). Factory setting is “0.02: 0.02%FS”.

F Standby sequence

• “Standby sequence” is a function for unconditionally turning alarm output OFF when the process value has left the alarm range once and it next enters the alarm range. • For example, when the alarm type is set to “deviation lower limit,” generally the process value is within the alarm range, and alarm output become ON as it is as the process value when the power is turned ON is smaller than the set point. However, if the alarm type is set to “deviation lower limit with standby sequence”, alarm output first becomes ON when the process value exceeds the alarm setting value to leave the alarm range and once again falls below the alarm value.

J Close in alarm/open in alarm • When the controller is set to “close in alarm,” the status of the alarm output function is output as it is. When set to “open in alarm,” the status of the alarm output function is output inverted.

Close in alarm Open in alarm

Alarm ON OFF ON OFF

Output ON OFF OFF ON

Output LED Lit Not lit Lit Not lit

• Alarm type and close in alarm (normally open)/open in alarm (normally close) can be set independently for each alarm. • Close in alarm/open in alarm is set in the “alarm 1 to 3 open in alarm” parameters (setup mode). Factory setting is [ ] “close in alarm”.

F Summary of alarm operations

The figure below visually summarizes the above description of alarm operations (when alarm type is set to “lower limit alarm (deviation) with standby sequence”): Alarm type: lower limit alarm (deviation) with standby sequence PV Alarm value Alarm hysteresis

Time Standby sequence canceled Alarm output (close in alarm)

3--8

Close (ON) Open (OFF)

Page 34

E5CK

3.4 Setting Alarm Type

Setting Example

When a set point for a humidity exceeds 10.0%, alarm1 will be output. In this example, let’s set the parameters as follows: “alarm type 1” = “1: (deviation upper-and lower-limit)” “alarm value 1” = “10.0” “alarm hysteresis” = “0.20” : close in alarm” “close in alarm/open in alarm”= “

Meanings of parameters, “alarm histeresis” and “open in alarm/close in alarm” are the same settings at the shipment, so settings for operations are omitted. (1) Select the menu display, and select [ or

] (setup mode) using the keys. For details on selecting the menu display, see page 1-7.

(2) Press the setup mode [ key to enter the setup mode. The top parameter in the ] “input type” is displayed. In this example, the parameter setting is “17: 4 to 20 mA”. (3) Press the key until [

] (“alarm type 1” parameter) is dis- played. The parameter default is “2: deviation upper limit”. (4) Press the key to return to “1: deviation upper and lower limit”.

(5) Select the menu key, and select [ 1 second min.

or

] (level 1 mode) using the keys. For details on selecting the menu display, see page 1-7.

(6) Press the level 1 mode [ (7) Press the key to enter the level 1 mode. The top parameter in the ] “AT execute/cancel” is displayed. key until [

] (“alarm value 1” parameter) is dis- played. (8) In this example, the parameter setting is “0.0” so press the key until “10.0” is displayed.

About the Decimal Point of the Alarm Value

The decimal point of the alarm value conforms to the setting of the “decimal point” parameter (setup mode). In this example, the “decimal point” parameter is set to “1”. (During temperature input, the decimal point of the alarm value conforms to the set sensor.)

3--9

Page 35

E5CK

CHAPTER 3 BASIC OPERATION

3.5 Protect Mode J Security

• This parameter allows you to protect until start of operation parameters that do not change during operation to prevent unwanted modification. • The set value of the “security” (protect) parameter specifies the range of protected parameters. • When this parameter is set to “0”, parameters are not protected. • When this parameter is set to “1” to “3”, the number of modes that can be displayed on the menu display is limited. When set to “1”, level 0 to 2, setup, expansion and option modes only can be selected. When set to “2”, only level 0 to 2 modes can be selected. When set to “3”, only level 0 and 1 modes can be selected. • When this parameter is set to “4” to “6”, operations in only the level 0 mode can be selected, and the mode is not displayed on the menu display. • When this parameter is set to “5”, only the “PV/SP” parameter can be used. • When this parameter is set to “6”, only the “PV/SP” parameter can be used. (The set point can not change.) • Default is “1”.

J A/M key protect

• This parameter disables use of the A/M key during operation. For example, if you protect use of the A/M key by the “A/M key protect” parameter (protect mode) during auto operation, the controller cannot be set to the manual mode, preventing manual operation of the controller during operation.

Setting Example

A/M

• Let’s protect the setup, expansion, option and calibration modes. Set the parameters as follows: “security” = “2: Usable only in level 0 to 2 modes” (1) Press for 1 second minium the A/M and keys simultaneously, the controller enters the protect mode. (2) In the protect mode, the top parameter in the protect mode “security” key to change is displayed. The parameter default is “1”. Press the the parameter setting to “2”. (3) Press for 1 second minium the A/M and A/M

3--10 keys simultaneously, the display changes to the “PV/SP monitor” parameter (level 0 mode).

Page 36

E5CK

3.6 Starting and Stopping Operation

3.6 Starting and Stopping Operation • You can start and stop operation by changing the setting of the “run/ stop” parameter (level 0 mode). • You can switch the RUN/STOP function up to 100,000 times. • To stop operation, set the “run/stop” parameter to [ stop state, the “STOP” LED lights.

F Manipulated variable at stop

Setting Example

] (stop). In a

• To set output during a stop, specify the manipulated variable (Standard: -5.0 to 105.0%, Heating and cooling: -105.0 to 105.0%) in the “MV at stop” parameter (level 2 mode). Factory setting is “0.0: 0.0%”.

The following example describes the procedure to follow to stop control during operation of the controller.

(1) Select the menu display, and select [ or

] (level 0 mode) using the keys. For details on selecting the menu display, see page

1-7. (2) Press the key to enter the level 0 mode. The PV and SP are displayed. (3) Press the key until [

(4) Press the key to select [

] (“run/stop” parameter) is displayed. ] (stop). The “STOP” LED lights, and operation stops. To resume operation, follow the above procedure to select [ The “STOP” LED goes out and operation starts.

] (“run”).

3--11

Page 37

E5CK

CHAPTER 3 BASIC OPERATION

3.7 Adjusting Control Operation J Changing the set point

• You can change the set point in the “set point” parameter (level 0 mode). • However, note that you cannot change the set point when the “security” parameter (protect mode) is set to “6”. • To change the set point, press the or keys to select the desired value. If you leave the setting for two seconds, the set point is updated to the new setting.

Setting Example

In the following example, let’s change the humidity set point from “60%” to “50%”.

(1) Select the PV/SP monitor display. (2) Press the

J Manual operation key to change the setting to “50.0: 50.0%”.

• To set manual operation and manually set the manipulated variable, press for 1 second minimum the A/M key. The controller enters the manual mode. • The manipulated variable is displayed on the No.2 display. To change the manipulated variable, press the or keys. After two seconds, the manipulated variable is updated to the new setting. • Other modes cannot be selected while in the manual mode. To select other modes, press for 1 second minimum the A/M key. The manual mode is quit. • The automatic return of display function does not work while in the manual mode. • When switching between manual and auto operation, the manipulated variable is subject to balance-less, bump-less operation. • If the power is interrupted during manual operation, manual operation is resumed at the manipulated variable at power interruption when the power is reset. • You can switch the AUTO/MANUAL function up to 100,000 times.

Balance-less, Bump-less Operation

3--12

To prevent sudden changes in the manipulated variable when switching between manual and auto operation, operation is resumed using the value that was active immediately before operation was switched, and the value is brought gradually closer to the value immediately after operation was switched.

Page 38

E5CK

3.7 Adjusting Control Operation

The following diagram summarizes manual operation. Manipulated variable (%) Balance-less, bump-less points

Time

0

Manipulated variable switched

Manual

OFF

ON

Power interruption

A/M

Auto

J Auto-tuning (A.T.)

• AT (auto-tuning) cannot be executed while operation is canceled or during ON/OFF control. • When you execute auto-tuning, the optimum PID parameters are automatically set by forcibly changing the manipulated variable to calculate the characteristics (called the “limit cycle method”) of the control target. During auto-tuning, the AT LED flashes. • 40%AT or 100%AT can be selected by the limit cycle of MV change width. Specify [ ] or [ ], respectively, in the “AT execute/cancel” parameter (level 1 mode). • During heating and cooling control, only 100%AT can be executed. (So, ] (40%AT) will not be displayed.) [ • To cancel AT execution, specify [ ] (“AT cancel”).

F 40%AT

In order to set the limit cycle of MV change width to 40%, select 40%AT to execute auto-tuning with fluctuations in the process value kept to a minimum. However, note that auto-tuning takes longer to execute compared with 100%AT. The timing by which limit cycles are generated varies according to whether or not the deviation (DV) at the start of AT execution is 10% full-scale or less. Deviation at start of AT execution ≧ 10% full-scale

Deviation at start of AT execution < 10% full-scale

Limit cycle of MV change width 40% Set point

Limit cycle of MV change width 40% Set point

Deviation 10% full-scale

Deviation 10% full-scale

Start of AT execution

End of AT

Time

Start of AT execution

End of AT

Time

3--13

Page 39

E5CK

CHAPTER 3 BASIC OPERATION

F 100%AT

In order to set the limit cycle of MV change width to 100%, select 100% AT to shorten the AT execution time without worrying about fluctuations in the process value. Limit cycle of MV change width 100%

Set point

Time Start of AT execution

Setting Example

End of AT

In this example, let’s execute 40%AT.

(1) Select [

] (level 1 mode) using the or keys. For details on selecting the menu display, see page 1-7. (2) Press the setup mode [ key to enter the level 1 mode. The top parameter in the ] “AT execute/cancel” is displayed. In this example, the parameter setting is [ (3) Press the

AT execute key to specify [

] “AT cancel” ].

(4) The AT LED flashes, and AT execution starts. When the AT LED goes out (end of AT execution), the parameter automatically returns to ] (“AT cancel”). [ • In addition to AT, the E5CK is also provided with fuzzy self-tuning (ST) that allows automatic calculation of the PID parameters suited to the control target. However, note that the ST function operates only during standard control by temperature input. For further information regarding the ST, please see page 5-29 and A-10.

About PID Parameters

3--14

When control characteristics are already known, the PID parameters can be set directly to adjust control. PID parameters are set in the “proportional band” (P), “integrated time” (I) and “derivative time” (D) parameters (level 1 mode). For details on the setting ranges of these parameters, see chapter 5 Level 1 Mode (page 5-11).

Page 40

CHAPTER 4 APPLIED OPERATION

4

CHAPTER 4 APPLIED OPERATION This chapter describes each of the parameters required for making full use of the features of the E5CK. Read this chapter while referring to the parameter descriptions in chapter 5.

4.1 Selecting the Control Method . . . . . . . . . . . .

4---2

Heating and cooling control . . . . . . . . . . . . .

4---2

ON/OFF control . . . . . . . . . . . . . . . . . . . . . . .

4---3

4.2 Operating Condition Restrictions . . . . . . . .

4---4

Manipulated variable restrictions . . . . . . . .

4---4

Set point limiter . . . . . . . . . . . . . . . . . . . . . . .

4---5

SP ramp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4---5

4.3 How to Use Option Functions . . . . . . . . . . .

4---7

Event input . . . . . . . . . . . . . . . . . . . . . . . . . . .

4---7

Transfer output . . . . . . . . . . . . . . . . . . . . . . . .

4---8

4.4 LBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4---9

4.5 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4---11 Calibrating thermocouple . . . . . . . . . . . . . . . 4---12 Calibrating platinum resistance thermometer . . . . . . . . . . . . . . . . . 4---15 Calibrating current input . . . . . . . . . . . . . . . 4---17 Calibrating voltage input . . . . . . . . . . . . . . . 4---18 Checking indication accuracy . . . . . . . . . . . . 4---20

4--1