Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 3 of 14

E5CK Digital Controller User's Manual, pages 21 to 30

Pages 21 to 30 of 138

The original document is the PDF (1.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron E5CK

Page 21

E5CK

CHAPTER 2 PREPARATIONS

2.2 Installation

J Dimensions 58 53j

13

100

44.8 48 j

J Panel cutout 65 mm min

Unit (mm)

60 mm min

45

+0.6 0

• Recommended panel thickness is 1 to 5 mm.

45

2--4

+0.6 0

• Maintain the specified vertical and horizontal mounting space between each controller. Controllers must not be closely mounted vertically or horizontally.

Page 22

E5CK

2.2 Installation

J Mounting Adapter Panel Watertight packing

(1) Insert the E5CK controller into the mounting hole in the panel at the position shown in the figure above. (2) Push the adapter along the controller body from the terminals up to the panel, and fasten temporarily. (3) Tighten the two fixing screws on the adapter. When tightening screws, tighten the two screws alternately keeping the torque to approximately 0.29 to 0.39 N·m, or 3 to 4 kgf·cm.

About the Terminal Cover

E5CK-AA1-500 controller is provided with a terminal cover (E53-COV07). Fasten the terminal cover as follows by using the snap pin.

2--5

Page 23

E5CK

CHAPTER 2 PREPARATIONS

2.3 Wiring Terminals

J Terminal arrangement AC100-240V (AC/DC24V ) SOURCE

SUB1

OUT1 5 11 12 10 4 9 3 8 2 7 1 13 14 6

OUT2 IN

OPTION

J Precautions when wiring

• Use ducts to separate input leads and power lines in order to protect the controller and its lines from external noise. • We recommend using solderless terminals when wiring the controller. • Tighten the terminal screws using a torque no greater than 0.78 N·m, or 8 kgf·cm max. Take care not to tighten the terminal screws too tightly. • Use the following type of solderless terminals for M3.5 screws. 7.2mm max.

7.2mm max.

J Wiring F Power supply 5 4 3 2 1

11 12

10

13 14

9 8 7 6

About the power blocks

2--6

In the following wiring diagrams, the left side of the terminal Nos. indicates the inside of the controller • Input power to terminal Nos. 4 and 5. Power specifications are as follows: AC100-240V , 50/60Hz, 15VA (AC/DC24V , 50/60Hz, 6VA, 3.5W)

The E5CK has independent power supplies for each of the terminal blocks shown on the right. However, note that the power supplies for blocks C (exclude relay output) and D are shared for the following option unit. • Option unit : E53--- CKB or E53--- CKF

A

C 5 11 12 10 9 4 8 3 C 7 2 1 13 14 6 D B

Page 24

E5CK

2.3 Wiring Terminals

F Input 5 4 3 2 1

11 12

10

13 14

9 8 7 6

• Connect the input to terminal Nos. 6 to 8 as follows according to the input type. +

8

8

7

7

6

6

8

-

7

V

Thermocouple Platinum resistance thermometer

6

+

Voltage input

TC ⋅ PT

7 mA

6

+

8

-

Current input

V

I

• Match the inputs with the internal jumper settings for each input type. For thermocouple or platinum resistance thermometer inputs, set the inputs to a common position (TC/PT) as the temperature input. For details on jumper connector positions, see page 2-2.

F Control output 5 4 3 2 1

11 12

10

13 14

9 8 7 6

• Terminal Nos. 11 and 12 are for control output 1 (OUT1). The five output types and internal equalizing circuits are available according to output unit: 11

+v

11

+

+v

11

+

L 12

GND

Relay E53-R4R4

12

NPN

E53-Q4R4 E53-Q4Q4

11 L

GND

12

+

11 L

V

L mA

12

+

12

PNP

0 to 10V

4 to 20mA/0 to 20mA

E53-Q4HR4 E53-Q4HQ4H

E53-V44R4

E53-C4R4 E53-C4DR4

• Terminal Nos. 9 and 10 are for control output 2 (OUT2). The three output types and internal equalizing circuits are available according to output unit: 10

+v

10

+

+v

10

+

L 9

GND

9

-

Relay

NPN

E53-R4R4 /E53-V44R4 E53-Q4R4 /E53-C4R4 E53-Q4HR4/E53-C4DR4

E53-Q4Q4

L GND

9 PNP

E53-Q4HQ4H

• The following table shows the specifications for each output type. Output Type

Specifications

Relay Voltage (NPN) Voltage (PNP)

250VAC, 3 A 12VDC, 20 mA (with short-circuit protection) 12VDC, 20 mA (with short-circuit protection)

0 to 10V

0 to 10VDC, Permissible load impedance: 1 kΩ min., Resolution: Approx. 2600 4 to 20 mA, Permissible load impedance: 500 Ω max., Resolution: Approx. 2600 0 to 20 mA, Permissible load impedance: 500 Ω max., Resolution: Approx. 2600

4 to 20mA 0 to 20mA

2--7

Page 25

E5CK

CHAPTER 2 PREPARATIONS

F Auxiliary output 1 5 4 3 2 1

11 12

10

13 14

9 8 7 6

F Option 5 4 3 2 1

11 12

10

13 14

9 8 7 6

• Terminal Nos. 2 and 3 are for auxiliary output 1 (SUB1). • The internal equalizing circuit for auxiliary output 1 is as follows: 3 2

• Relay specifications are as follows: SPST-NO, 250VAC, 1A • Terminal Nos. 1, 13 and 14 are valid only when the option unit is set in the controller. • The following four connections are possible depending on the type of option unit. 13 14 1

SD RD SG

13 14

A B

1

13

13

+

14

4 to 20mA 14 --

1

1

RS-232C

RS-485

Event input

Transfer output

E53-CK01

E53-CK03

E53-CKB

E53-CKF

• For details on RS-232C and RS-485 communications functions, see Chapter 6 Using the Communications Function. • Use event inputs under the following conditions Contact input

ON: 1 kΩ max., OFF: 100 kΩ min.

No-contact input ON: residual voltage 1.5V max., OFF: leakage current 0.1mA max.

Polarities during no-contact input are as follows: 13 14

+ --

1

• Transfer output specifications are as follows: 4 to 20 mA, Load 500 Ω max., Resolution approx. 2600

2--8

Page 26

CHAPTER 3 BASIC OPERATION

3

CHAPTER 3 BASIC OPERATION This chapter describes an actual example for understanding the basic operation of the E5CK.

3.1 Control Example . . . . . . . . . . . . . . . . . . . . . . .

3---2

3.2 Setting Input Specifications . . . . . . . . . . . . .

3---3

Input type . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3---3

Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3---3

3.3 Setting Output Specifications . . . . . . . . . . .

3---5

Output assignments . . . . . . . . . . . . . . . . . . . .

3---5

Direct/reverse operation . . . . . . . . . . . . . . . .

3---5

Control period . . . . . . . . . . . . . . . . . . . . . . . . .

3---6

3.4 Setting Alarm Type . . . . . . . . . . . . . . . . . . . .

3---7

Alarm type . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3---7

Alarm value . . . . . . . . . . . . . . . . . . . . . . . . . . .

3---7

Alarm hysteresis . . . . . . . . . . . . . . . . . . . . . . .

3---8

Close in alarm/open in alarm . . . . . . . . . . . .

3---8

3.5 Protect Mode . . . . . . . . . . . . . . . . . . . . . . . . . . 3---10 Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3---10 A/M key protect . . . . . . . . . . . . . . . . . . . . . . . . 3---10 3.6 Starting and Stopping Operation . . . . . . . . 3---11 3.7 Adjusting Control Operation . . . . . . . . . . . . 3---12 Changing the set point . . . . . . . . . . . . . . . . . 3---12 Manual operation . . . . . . . . . . . . . . . . . . . . . . 3---12 Auto-tuning (A.T.) . . . . . . . . . . . . . . . . . . . . . 3---13

3--1

Page 27

E5CK

CHAPTER 3 BASIC OPERATION

3.1 Control Example This chapter describes the following control example to facilitate understanding of the basic operation of the E5CK controller. This description assumes that the controller is operated under the following conditions. • A humidity sensor of output 4 to 20 mA is connected to the controller. The measuring range of the humidity sensor is set to 10 to 95%. • A humidifier is controlled by pulse output to maintain humidity at a constant 60%. • An alarm is output when the humidity exceeds the upper limit value (70%) or lower limit value (50%).

F Setup

• Output unit: relay/relay type (E53-R4R4) • Input type jumper connector: “I (current input)”

Humidity sensor Humidifier

OUT1 AC100-240V (AC/DC24V ) SOURCE

5

10

4

9

3

8

2

7

1 E5CK

3--2

11 12

Control target

13 14

6

OUT2

Alarm 1 (deviation upper-and lower-limit)

4 to 20mA

Page 28

E5CK

3.2 Setting Input Specifications

3.2 Setting Input Specifications J Input type

• Set the type No. (0 to 21) in the “input type” parameter. The factory setting is “2: K1 (thermocouple).” • For details on input types and setting ranges, see page 5-22.

J Scaling

• When the voltage input and current input are selected, scaling matched to the control is required. • The “scaling upper limit”, “scaling lower limit” and “decimal point” parameters (setup mode) are use for scaling. • The “scaling upper limit” parameter sets the physical quantity to be expressed by the upper limit value of input, and the “scaling lower limit” parameter sets the physical quantity to be expressed by the lower limit value of input. The “decimal point” parameter sets the number of digits past the decimal point. • The following figure shows scaling example of 4 to 20 mA input. After scaling, the humidity can be directly read. In this case, the “decimal point” parameter is set to “1”. Readout (humidity)

Scaling upper limit value (95.0%)

Scaling lower limit value (10.0%)

Input (4 to 20 mA)

0

F Input shift

100%FS

• When temperature input is selected, scaling is not required. This is because input is treated as the “temperature” as it is matched to the input type. However, note that the upper and lower limit values of the sensor can be shifted. For example, if both the upper and lower limit values are shifted by 1.2_C, the process value (before shift) is regarded as 201.2_C after shift when input is 200_C before shift. • To set input shift, set shift values in the “input shift upper limit” and “input shift lower limit” parameters (level 2 mode). Temperature Input shift upper limit value Upper limit value After shift Before shift Lower limit value 0

About the temperature unit

Input shift lower limit value

Input (%FS)

100

To switch the temperature unit from “_C” to “_F” for temperature unit, switch the setting of the _C/_F selection” parameter to [ ] from [ ].

3--3

Page 29

E5CK

CHAPTER 3 BASIC OPERATION

Setting Example

In this example, let’s set the parameters as follows: “input type” = “17 (4 to 20 mA)” “scaling upper limit value” = “950” “scaling lower limit value” = “100” “decimal point” = “1”

(1) Select the menu display, and select [ or

] (setup mode) using the keys. For details on selecting the menu display, see page

1-7. (2) Press the setup mode [ key to enter the setup mode. The top parameter in the ] “input type” is displayed. The parameter default is “2”. (3) Press the key until the display indicates “17”.

(4) Press the key to fix the set value. The display changes to [

]

(“scaling upper limit value” parameter). The parameter default is “100”. (5) Press the key until the display indicates “950”.

(6) Press the key to fix the set value. The display changes to [

]

(“scaling lower limit value” parameter). The parameter default is “0”. (7) Press the key until the display indicates “100”.

(8) Press the key to fix the set value. The display changes to [

(“decimal point” parameter). The parameter default is “0”. (9) Press the

3--4 key until the display indicates “1”.

]

Page 30

E5CK

3.3 Setting Output Specifications

3.3 Setting Output Specifications J Output assignments

• Eight output are supported : control output (heat) control output (cool) alarm outputs 1 to 3 LBA, and error 1 (input error) error 2 (A/D converter error). These functions are assigned to control outputs 1 and 2, and auxiliary output 1. • Restrictions on assignment destination are placed on some of the outputs. The following table shows where outputs may be assigned to. Assignment Destination Output Function Control output (heat) Control output (cool) Alarm 1 Alarm 2 Alarm 3 LBA Error 1; Input error Error 2; A/D converter error

Control Output 1

2

F F F F F F

F F F F F F

Auxiliary Output 1

F F F F F F

With control output (cool) the conditions for switching from standard control to heating and cooling control are reached when the output function is assigned at the cooling side during heating and cooling control. In other words, heating and cooling control is carried out when control output (cool) is assigned, and standard control is carried out when output is not assigned. For details on heating and cooling control, see 4.1 Selecting the Control Method (page 4-2). • The same output function can not be assigned to a single destination more than once. • Factory settings are as follows: Control output (heat) = control output 1 Alarm 1 = control output 2 Alarm 2 = auxiliary output 1. • Output assignments are set in the “control output 1 assignment”, “control output 2 assignment” and “aux output 1 assignment” parameters (setup mode).

J Direct/reverse operation

• “Direct operation” (or normal operation) refers to control where the manipulated variable is increased according to the increase in the process value. Alternatively, “reverse operation” refers to control where the manipulated variable is decreased according to the decrease in the process value. For example, when the process value (PV), is lower than the set point (SP), in a heating control system, the manipulated variable increases by the difference between the PV and SP values. Accordingly, this becomes “reverse operation” in a heating control system. Alternatively, this becomes “direct operation” in a cooling control system. ]“direct/reverse operation” • Direct/reverse operation is set in the [ parameter (setup mode). 3--5