Page 11
E5CK
CHAPTER 1 INTRODUCTION
1.2 Input and Output
Temperature input Voltage input
Controller Input type jumper
Control output (heat) Control output (cool)
Alarm 1 Current input
Event input
Alarm 2 Alarm 3 LBA
Control output 1 Control output 2 Auxiliary output 1 Transfer output 1
Error 1 Error 2
J Input
The E5CK supports four inputs.
F Temperature input/Voltage input/Current input • Only one of temperature input, voltage input and current input can be selected and connected to the controller. The above figure shows temperature input connected to the controller. • The following input sensors can be connected for temperature input: Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII Platinum resistance thermometer: JPt100, Pt100 • The following currents can be connected for current input: 4 to 20 mA, 0 to 20 mA • The following voltages can be connected for voltage input: 1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC
F Event input
1--4
When using event input, add on the input unit (E53---CKB). You can select from the following five event inputs: Multi-SP Run/Stop Auto/Manual
Page 12
E5CK
1.2 Input and Output
J Output
The E5CK supports the following four outputs. Control output 1 Control output 2 Auxiliary output 1 Transfer output When using control outputs 1 and 2, set the output unit (sold separately). Eight output units are available to suit the output circuit configuration. When using transfer output, add on the communication unit (E53---CKF). Note: The output functions of the E5CK do not operate for five seconds after the E5CK is turned ON.
F Output assignments
The E5CK supports the following eight output functions. Control output (heat) Control output (cool) Alarms 1 to 3 LBA Error 1 (input error) Error 2 (A/D converter error) Assign these output functions to control outputs 1 and 2 and auxiliary output 1. Only control output (heat), control output (cool), alarms 1 to 3, and LBA can be assigned to control outputs 1 and 2. Also, only alarms 1 to 3, LBA, and errors 1 and 2 can be assigned to auxiliary output 1. In the example on the previous page, “control output (heat)” is assigned to “control output 1”, “alarm 1” is assigned to “control output 2”, and “alarm 2” is assigned to “auxiliary output 1”. Accordingly, the configuration is such that heating control output is connected to control output 1, and alarm output is connected to control output 2 and auxiliary output 1. In a heating and cooling control, assign “control output (cool)” to either of “control output 1” or “control output 2”.
F Transfer output
The E5CK supports the following five transfer outputs. Set point Set point during SP ramp Process value Heating side manipulated variable Cooling side manipulated variable These transfer outputs can be output after being scaled. Setting of an upper limit value smaller than the lower limit value is allowed, so reverse scaling can also be carried out.
1--5
Page 13
E5CK
CHAPTER 1 INTRODUCTION
1.3 Parameters and Menus
J Parameter types
E5CK parameters are distributed between the following nine modes. Protect mode Manual mode Level 0 mode Level 1 mode Level 2 mode Setup mode Expansion mode Option mode Calibration mode The settings of parameters in each of seven modes (excluding the protect mode and manual mode) can be checked and modified by selection on the menu display.
F Protect mode
This mode is used to limit use of the menu and A/M keys. The protect function is for preventing unwanted modification of parameters and switching between the auto and manual operation.
F Manual mode
In this mode, the controller can be switched manual operation. The manipulated variable can be manipulated manually only in this mode.
F Level 0 mode
Set the controller to this mode during normal operation. In this mode, you may change the set point during operation, and stop and start operation. You can also monitor (not change) the process value, ramp SP and manipulated variable.
F Level 1 mode
This is the main mode for adjusting control. In this mode, you can execute AT (auto-tuning), and set alarm values, the control period and PID parameters.
F Level 2 mode
This is the auxiliary mode for adjusting control. In this mode, you can set the parameters for limiting the manipulated variable and set point, switch between the remote and local modes, and set the loop break alarm (LBA), alarm hysteresis and the digital filter value of inputs.
F Setup mode
This is the mode for setting the basic specifications. In this mode, you can set parameters that must be checked or set before operation such as the input type, scaling, output assignments and direct/reverse operation.
F Expansion mode
This is the mode for setting expanded functions. In this mode, you can set ST (self-tuning), SP setting limiter, selection of advanced PID or ON/OFF control, specification of the standby sequence resetting method, initialization of parameters, time for automatic return to the monitoring display.
1--6
Page 14
E5CK
1.3 Parameters and Menus
F Option mode
This is the mode for setting option functions. You can select this mode only when the option unit is set in the controller. In this mode, you can set the communications conditions, transfer output and event input parameters to match the type of option unit set in the controller.
F Calibration mode
This mode is provided so that the user can calibrate inputs and transfer output. When calibrating input, the selected input type is calibrated. Whereas, transfer output can be calibrated only when the communications unit (E53---CKF) is set in the controller.
J Selecting modes
The following diagram shows the order in which modes are selected.
Power ON A/M 1 second min.
1 second min.
Level 0 mode 1 second min.
1 second min.
Manual mode A/M
Level 1 mode Level 2 mode
1 second min.
A/M
+
A/M
1 second min. 1 second min.
1 second min.
1 second min.
1 second min.
F Menu display
Setup mode
+
1 second min.
Protect mode
Expansion mode
A/M
+
1 second min.
Option mode Calibration mode
• To select the menu display in any of the above modes (excluding the protect mode and manual mode), press the key for 1 second minimum.
If you select the desired mode using the or keys and press the key, the top parameter in the specified mode is displayed. • When you have selected the menu display, the previous mode is selected. For example, if you selected the menu display while in the level 0 mode, ] as shown on the left. the No.2 display changes to [ • Protected modes cannot be selected. Also, the menu display does not appear when modes are protected up to the level 1 mode.
F Level 0 to 2 modes
• If you select [ ][ ] or [ ] in the menu display, the level 0, level 1 and level 2 modes, respectively, are selected. • These modes are selected with control still continuing.
1--7
Page 15
E5CK
CHAPTER 1 INTRODUCTION
F Setup mode F Expansion mode F Option mode F Calibration mode
][ ][ ] or [ ] in the menu display, the • If you select [ setup, expansion, option and calibration modes, respectively, are selected.
F Protect mode
• To set the controller to the protect mode or to return to the level 0 mode from the protect mode, press the A/M key and key for 1 second mini-
• When these modes are selected, the control is reset. So, control outputs and auxiliary output are turned OFF. When another mode is selected while in these modes, reset is canceled.
mun simultaneously.
F Manual mode
• To set the controller to the manual mode, press the A/M key for 1 second minimun in the level 0 to 2 mode. To return to the level 0 mode from the manual mode, press the A/M key for 1 second minimum.
J Selecting parameters
• When not in the manual mode, each press of the key switches the parameter. • If you press the key when at the final parameter, the display returns to the first parameter. Parameter 1
J Fixing settings
Parameter 2
Parameter 3
Parameter n
• When you have changed a parameter setting, specify the parameter or keys, and either leave the setting for at least two using the seconds or press the key. This fixes the setting.
• When another mode is selected, the content of the parameters before the mode was selected is fixed. • When turning the power OFF, you must first fix the settings and parameter contents (by pressing the key or selecting another mode). The settings and parameter contents are sometimes not changed by merely pressing the or keys.
1--8
Page 16
E5CK
1.4 About the Communications Function
1.4 About the Communications Function The E5CK can be provided with a communications function that allows you to check and set controller parameters from a host computer. If the communications function is required, add on the communications unit. For details on the communications function, refer to Chapter 6.
F RS-232C
When using the communications function on the RS---232C interface, add on the communications unit (E53---CK01).
F RS-485
When using the communications function on the RS---485 interface, add on the communications unit (E53---CK03).
1--9
Page 17
E5CK
CHAPTER 1 INTRODUCTION
1.5 About Calibration The E5CK controller is calibrated before shipment from the factory. So, the user need not calibrate the E5CK controller during regular use. However, if the E5CK controller must be calibrated by the user, use the parameters provided for user to calibrate temperature input, analog input (voltage, current) and transfer output. Also, note that calibration data is updated to the latest value each time the E5CK controller is calibrated. Calibration data set before shipment from the factory cannot be returned to after calibration by the user.
F Calibrating inputs
The input type selected in the parameter is the item to be calibrated. The E5CK is provided with the following four calibration parameters. • Thermocouple • Platinum resistance thermometer • Current input • Voltage input Two parameters are provided for thermocouple and voltage input.
F Calibrating transfer output
Transfer output can be calibrated when the communications unit (E53---CKF) is added on.
F Registering calibration data
When calibrating each item, the calibration data is temporarily registered. This data can be registered as final calibration data only when all items have been newly calibrated. So, all items must be temporarily registered when calibrating the E5CK controller. When registering data, information regarding whether or not calibration has been carried out is also registered. To calibrate these items, the user must prepare separate measuring devices and equipment. For details on handling these measuring devices and equipment, refer to the respective manuals. For details, see 4.5 Calibration (page 4---11).
1--10
Page 18
CHAPTER 2 PREPARATIONS
2
CHAPTER 2 PREPARATIONS This chapter describes the operations you should carry out before turning the E5CK ON.
2.1 Setting up . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2---2
Draw-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2---2
Setting the input type . . . . . . . . . . . . . . . . . .
2---2
Setting up the output unit . . . . . . . . . . . . . .
2---3
Setting up the option unit . . . . . . . . . . . . . . .
2---3
2.2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2---4
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2---4
Panel cutout . . . . . . . . . . . . . . . . . . . . . . . . . . .
2---4
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2---5
2.3 Wiring Terminals . . . . . . . . . . . . . . . . . . . . . .
2---6
Terminal arrangement . . . . . . . . . . . . . . . . .
2---6
Precautions when wiring . . . . . . . . . . . . . . .
2---6
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2---6
2--1
Page 19
E5CK
CHAPTER 2 PREPARATIONS
2.1 Setting up This section describes how to set the input type jumper, and set up the output unit or option unit.
J Draw-out
First, draw out the internal mechanism from the housing (1) Pull out the internal mechanism while pressing the hooks on the left and right sides of the front panel. (2) Draw out the internal mechanism towards you holding both sides of the front panel.
J Setting the input type • For details on the jumper connector position, see page 1-2. • Set the input type jumper connector to one of temperature input, voltage input or current input matched to the sensor connected to the input terminal. I : Current input
V : Voltage input
TC.PT : Temperature input
• The factory setting is “TC/PT (temperature input).” • When removing or inserting the jumper connector, do not touch the pins directly with your fingers. • When you have set the jumper connector, insert the internal mechanism into the rear case. • When inserting the internal mechanism, push in until you hear the hooks on the front panel click into place. 2--2
Page 20
E5CK
2.1 Setting up
J Setting up the output unit F Output unit list
The following table shows the output units that can be set in the E5CK controller. Model E53-R4R4 E53-Q4R4 E53-Q4HR4 E53-C4R4 E53-C4DR4 E53-V44R4 E53-Q4Q4 E53-Q4HQ4H
Specifications (control output 1/control output 2) Relay/Relay Voltage (NPN)/Relay Voltage (PNP)/Relay 4 to 20 mA/Relay 0 to 20 mA/Relay 0 to 10 V/Relay Voltage (NPN)/Voltage (NPN) Voltage (PNP)/Voltage (PNP)
F Setup (1) Two rectangular holes for slotting are provided on the power board (on right side of controller). Fit the two protrusions on the output unit into these two holes. (2) With the output unit fitted into the power board, fit the output unit into the connector on the control board (on left side of controller).
J Setting up the option unit F Option unit list
F Setup
The following table shows the option units that can be connected to the E5CK controller. Unit
Model
Communications unit Communications unit Input unit Communications unit
E53-CK01 E53-CK03 E53-CKB E53-CKF
Specifications Communications (RS-232C) Communications (RS-485) Event input: 1 input Transfer output: 4 to 20 mA
(1) Place the controller with its bottom facing up, and fit the board horizontally into the connector on the power board (on right side of controller). (2) With the power board connected, fit the board vertically into the connector on the control board (on left side of controller).
2--3