CHAPTER 1
1.1 1.2
1.3
1.4 1.5 1.6
1.7
WHAT IS THE ES100P?
Features Names of Parts Main parts
Front panel
Front panel (inside cover) -------- Input and Output ------------------- Layout of I/O terminals ----------- Input Output Parameters and Setting Levels --- SP Mode Operation Assignment Function - What is an
“operation assignment”? -------
Digital operation assignments ---- Analog operation assignments --- Mixed analog/digital operation -- Fine Tuning
1-3 1-3 1-4
1-6 1-6 1-6
1-8 1-9 1-10
1-10 1-11 1-11 1-11 1-12
CHAPTER 1
Page 12
1.1 Features
@ Easy Operation ¢ You can easily set and adjust parameter settings using the support software (*1). * You can quickly set operating instructions or frequently used parameters using programmable function keys. * You can easily make optimum adjustments to control using the auto-tuning and fine tuning functions.
@ Almost All Types of Control are Possible on a Single Unit.
* Control is facilitated by using the para’ clusively for heating-cooling control.
¢ You can choose between floatin roportional control system. :
¢ Control is facilitat controller. Operation assign orward control.
an use the digital operation assignment and sign the optimum I/O functions to the desired
+ Digital I/O sig: ed by the digital operation assignment function.
+ You can use the an ‘ation assignment function to process data to achieve control operation for analog input. You can also use the analog operation assignment function to process control operation in order to output the control operation results as analog output.
@ Enhanced Programming Functions ¢ You can set up to 99 program patterns consisting of up to 100 steps (a maximum of 400 steps) in a single pattern. ¢ You can not only use the pattern by switching, but can also run the same programs using the repeat function and linking patterns together.
*1 ES/TOOLS Support Software is sold separately. *2 See the ES100 Digital Controller User’s Manual, Communications Guide.
1-2
Page 13
1.2 Names of Parts
@ Main parts The figure below shows the main parts of the ES100P, and describes each of their functions. For more details on these main parts, see the page numbers for each description. CHAPTER 1
Rear case Contains the main unit.
DIP switches
These are located on the PCB inside the main unit. Used for switching the setting level.
Rear panel
Here are located terminals for wiring and expanded I/O connectors.
Output unit
Install this on the sockets inside the main unit. Select the output unit matched to the output specification.
* This is already installed on _ position- proportional controllers (ES100P-RRPLJ- -().
Front panel
Holds the keys and displays for indicating settings and control status. Indicators and keys not required during running of programs are located inside the cover.
Page 14
@ Front panel
No.1 display
No.2 display
Bar graph
Output indicators
Operation status indicators 1
Operation status indicators 2
Program No. display
1-4
PUT
Output ouTt four] § Pv r () , ] , j , ( No.1 display ad LDL)?, -_ - <> < ~ indicators 90 g
=t_ [Baal sae] “Ae G
No.2 display
40)
Operation o 30 Operation status indicators 2 status 20 : indicators 1 i) 0 = jr Program No. display fa Oye ey Bar graph | PF 1 PTN RUN PF 2 Front panel keys LSP status PUSH-OPEN indicators ES100P
DIGITAL CONTROLLER
Displays parameter symbols when setting parameters. During setting of parameters, the PV and SP LEDs do not light.
Displays the process value (PV) or the set point (SP) during monitoring. Either of the PV or SP LEDs lights according to the display content.
Displays settings when setting parameters. During setting of parameters, the SP and MV LEDs do not light.
Displays the process value (PV), elapsed time and the manipulated variable (MV) during monitoring. One of the SP or MV LEDs lights according to the display content.
This bar graph indicates the manipulated variable, valve opening position, elapsed-time%, and deviation. The user can designate in parameters which items are displayed on the bar graph.
The corresponding LEDs lights depending on which control outputs (OUT1, OUT2) and auxiliary outputs (SUB1, SUB2) are ON.
These indicators display the operation status. RUN lights when the program is running. HOLD lights when the program is in hold status. RST lights when the control is in reset status.
These indicators display the current control status.
* RMT LED : Lights when the current mode is set to remote or external.
*FSPLED _ : Lights when the SP mode is set to a fixed value.
e ATLED __ : Flashes when auto-tuning is being executed.
¢ WAIT LED : Lights when the program is in wait status, and flashes when a wait alarm occurs.
* MAN LED : Lights when the current mode is the manual mode.
When setting and running the program, the PTN display indicates the pattern No. and the STEP display indicates the step No. When setting table parameters, the STEP display indicates the table No.
Page 15
LSP status indicators
Front panel keys i
These indicators display the status of the local SP during execution of the program for the currently executing step.
* c - : Lights when the running program step is ramp up.
* c - =: Lights when the running program step is soak.
¢ C= : Lights when the running program step is ramp down.
The and keys are programmable function keys. The user can assign functions to these keys.
The [PtN) key advances patterns.
The RUN key starts execution of a program.
@ Front panel (inside cover)
Setting level 1 mode indicators
Set key
Shift keys
Up/Down keys
Enter key
Edit key
Auto/Manual key
RS-232C jack
Setting level 1 mode Up/Down keys indicators OPR TUNE PRGM PID ea (a) A Set key SE BD) Ce i INS | > [FSP jack O fe Vv IS) L DEL (Edit key Shift keys Fenter key
The LED corresponding to the mode set in setting level 1 lights. Correspondence between the LED and setting mode is as follows:
OPR LED _ : Operation mode
TUNELED : Tuning mode
PRGM LED : Program setting mode
PID LED : PID set setting mode
ADJ LED _ : Adjustment mode
CHECK LED: Check mode
Designates the first parameter in each setting mode. Pressing the [w] key designates the next parameter. Pressing the [a] key designates the previous parameter. Pressing the [pb] key designates the next table No. Pressing the [<4] key designates the previous table No.
Each press of the [A] key increments values by 1, andeach press of the [§4] key decrements values by 1. The display remains dim until the key is pressed.
This key is used to enter a setting. When pressed, the dim display changes to a lit display. This key is used for editing programs.
Each press of this key switches between auto and manual modes.
This RS-232C interface jack is for communicating with the ES/TOOLS support software
(sold separately). Cables other than the dedicated cable (sold separately) cannot be used with the ES/Tools support software.
CHAPTER 1
Page 16
1.3 Input and Output
@ Layout of I/O terminals
Hi Input @ Analog input 1
@ Analog input 2 @CT input
@ Potentiometer input
@ Auxiliary input (digital input)
1-6
The ES100P rear panel is provided with terminals and expanded I/O connectors. Input and output terminals are arranged in groups as shown in the figure below. The rear panel can be configured in a variety of ways depending on the model you have purchased.
Ba Input £2] output fH Input or output
* A total of 26 analog input terminals are available: 17 temperature sensor inputs (thermocouple and platinum resistance thermometer), seven voltage inputs, and two current inputs. You can choose one of these 26 analog inputs in the “analog input 1 type” parameter.
These terminals are available only on 2-input ES100P. You can choose either of voltage input or current input in parameter settings.
Terminals are provided on standard ES100P (including heating-cooling models) for CT input for use in heater current detection.
Terminals are provided on position-proportional ES100P for potentio-menter input for use in valve opening measurement.
Of the ES100P on which auxiliary inputs can be used, up to eight auxiliary input terminals can be used on models provided with expanded I/O connectors, and up to three auxiliary input terminals can be used on models not provided with expanded I/O connectors.
The application of the auxiliary input terminals can be designated by the digital operation assignment function. Before shipment from the factory, switch inputs for run, reset and advance are assigned to the auxiliary input terminals
¢ On ES100P provided with expanded I/O connectors, the auxiliary input terminals cannot be used when using BCD communications. BCD communications is switched to in parameter settings.
Page 17
@ Output
@ Control output (analog output)
@ Transfer output (current output)
@ Auxiliary output (digital output)
¢ Two control output terminals are provided: control output 1 and control output 2. You can choose between relay output, SSR output, voltage output and current output for each of these terminals depending on the type of output unit installed on the main unit.
¢ This terminal is exclusively for current output. Output data can be designated to this terminal by the analog operation assignment function.
In position-proportional control systems, control output | is used for open output and control output 2 is used for closed output. So, arelay output unit is used as the output unit. This output unit is already installed in position-proportional controllers before shipment from the factory, so the user need not to obtain a separate output unit.
PV is assigned to this terminal before shipment from the factory.
10 are for open-collector output.
« Auxiliary outputs 3 to 10 sometimes cannot be used depending on the model of ES100P.
* Output data can be designated to auxiliary outputs by the digital operation assignment function. Event output is assigned to auxiliary outputs 1 and 2 before shipment from the factory.
* When using BCD communications on ES100P provided with expanded
Ten auxiliary output terminals are provided: auxiliary outputs 1 to 10. ¢ Auxiliary outputs 1 and 2 are for relay output, and auxiliary outputs 3 to
I/O connectors, auxiliary outputs 3 to 10 cannot be used.
Terminal
= names and operation assignments
On the ES100P, the functions of I/O terminals are determined by the “operation assignment function.” That is, inputs correspond to arguments, and outputs correspond to assignment destinations. Sometimes, however, the terminal name differs from the name used in operation assignment. The purpose of this is to match the terminology used in conventional temperature controllers and digital controllers. The following table shows the correspondence between terminal names and the name used in operation assignment.
Argument or Assign-
Argument or
Terminal Name | ment Destination Terminal Name Assignment Destination Control output 1 Analog output 1 Transfer output Analog output 3 Control output 2 Analog output 2 Auxiliary input 1 Digital input 1 Auxiliary output 1 Digital output 1 Auxiliary input 2 Digital input 2 Auxiliary output 2 Digital output 2 Auxiliary input 3 | Digital input 3
For details on the operation assignment function, see page 1-10.
1-7
CHAPTER 1
Page 18
1.4 Parameters and Setting Levels
The ES100P has two setting levels, setting level 1 and setting level 2. These two setting levels support different parameters.
@ Setting level 2
This setting level is for determining the specifications of the controller. Running of programs is stopped when this setting level is entered.
Of the parameters in setting level 2, unit or reference information used in setting level 1 parameters must be set before the related setting level 1 parameter is accessed.
In setting level 2, parameters are distributed among the following setting modes:
Specification setting mode
Event setting mode
ON/OFF timer setting mode
Digital operation assignment setting mode Analog operation assignment setting mode Setting level 2 technical mode
@ Setting level 1
This setting level is for setting performance or operating conditions. In setting level 1, parameters are distributed among the following setting modes:
Manual mode parameter setting mode (available only in the manual mode)
Operation mode
Tuning mode
Program setting mode
PID set setting mode
Adjustment mode
Check mode
(Setting level 1 technical mode) Each of these modes except setting level 1 technical mode can be verified by lighting of their respective LEDs.
@ Switching between setting levels
To switch between setting levels 1 and 2, you need to change the settings of the DIP switches located inside the main unit of the ES100P.
Setting levels 1 and 2 are each provided with a technical mode to set the technical parameters. You can enable (and disable) access and display of the technical modes by changing the DIP switch settings.