1.5 SP Mode

@ Local SP mode

@ Remote SP mode

@ Fixed SP mode

On the ES100P, you can use one of local SP (LSP), remote SP (RSP) and fixed (FSP) as the set point (SP). Each of these SPs is designated in an “SP mode.”

Execution of programs is started in the local SP mode. In the local SP mode, the SP is calculated from the “local SP” parameter set for each of the programmed steps.

When another mode is switched to from the local SP mode during program execution, the SP changes. The program, however, continues to advance as instructed.

In the remote SP mode, the result of analog operations that takes the assignment destination as the “RSP” is used as the SP. This SP is called the “remote SP.”

The remote SP mode is set, for example, when controlling extemal analog input data (using analog input 2) as the SP.

In the fixed SP mode, the setting of the “fixed SP” parameter is used as the SP. The fixed SP mode is set when performing control by a fixed value.

The SP change rate can be limited in the remote SP and fixed SP modes.

Analog operation

RSP

, FSP°:. [SP change Fixed SP rate limit '

SP

You can choose between settings made on the front panel, by serial communication and by BCD communications for use in parameter settings. Settings made on the front panel are called “local settings”, serial communications (serial and BCD)

settings are called “remote settings”, and BCD communication settings are called “external settings”.

Note that the terms “local” and “remote” differ from “local” and “remote” used in the SP modes. Remember this when setting the SP mode and parameters.

1-9

CHAPTER 1

Page 20 read from a scan by OCR; it may hold reading errors

1.6 Operation Assignment Function

What is an “op- eration assign- ment”?

@ Operation assignment table

@ About operations

¢ ES100P I/O data is used according to the values set to tables. These tables describe how I/O data are is to be handled. Accordingly, you can use I/O data as it is as control data in the same way as on conventional digital controllers. Data can be further manipulated by “operations,” so the optimum I/O functions can be achieved for the control target. This is referred to as the “operation assignment function.”

Tables describing how I/O data is to be handled are called “operation assignment tables.”

There are two operation assignment functions: the “digital operation assignment function” and “analog operation assignment function.” The function to be used depends on the type of data that is to be handled. Moreover, “mixed analog/digital operation” for exchanging data between analog and digital operations also is possible.

¢ The content of operation assignment tables are described in the “‘digital/ analog operation assignment” parameters.

* Operation assignment tables are made up of “operation blocks” and

“assignment destinations.”

Table 4 Table 2 Table n Assignment Assignment [|, - «& Assignment Destination Destination [To Destination Operation Operation Operation block block block

¢ At the operation block, an operation that is executed using two arguments is handled as the basic unit. Each of these operations is given a No.

¢ Operations are executed from the smallest operation No. upwards, and end when the program reaches the operation END code.

¢ The result of each operation is output to the assignment destination. ¢ Table settings are executed in table No. order.

Operation When the END code is pcestination | ; 2 instructed, the result at

Operation 1 [Operation ode the end of operation i ; 1 is transferred to the oreouton Operation 2. Argument Pe rane destination. sequence | | Operation 3 Argument 2 ' Operation n

Page 21 read from a scan by OCR; it may hold reading errors

Digital operation

The digital operation processes external digital inputs, flags for internal assi gnments ON/OFF timers, events and control status as arguments 1” or “0, and outputs to assignment destinations such as digital outputs, operating instructions and the digital user buffers.

* The ES100P is provided with 30 operation assignment tables. The settings of assignment destinations in unused tables should be set to “0” (disabled). The results of digital operations can also be used as the arguments for the subsequent operation.

* The operation block is made up of operations 1 to 4. This is shown in the following diagram.

Table 1 Table 2 Table 30 ‘Assignment Assignment [| Assignment destination destination | oe destination Operations Operations Operations 1to4 1to4 1to4 @ Anal og * The analog operation process external analog inputs, SP, PV and control re) peration operation data as arguments, and assigns the external results of operations . to assignment destinations such as control outputs, transfer outputs and assignments 6 P P the analog user buffers.

¢ The ES100P is provided with 15 operation assignment tables. The settings of assignment destinations in unused tables should be set to “0” (disabled).

The operation block is made up of operations 1 to 15. This is shown in the following diagram.

Table 1 Table 2 Table 15 Assignment Assignment [|, - «& Assignment destination destination Jo destination Operations Operations Operations 1to 15 1to 15 1to15 @ Mixed ¢ The ES100P is provided with a common data area for sharing the results analog/digital of digital and analog operations. . * Up to eight sets of data for expressing the states “0” and “1” can be set to operation : this data area.

¢ In digital operations, this area can be used for arguments or assignment destinations.

+ In analog operations, the results of comparing the sizes of arguments are set as data “1” or “0”. Also, arguments can be selected according to the value set to this data.

¢ Accordingly, you can select either of two sets of analog data using the results of digital operation, and assign the results of comparing the analog data to digital outputs.

Assignment Comparison of destination operation results . . Mixed operation ; Digital operation data “1” or “0” Analog operation

Argument Selection conditions

Page 22 read from a scan by OCR; it may hold reading errors

1.7 Fine Tuning

Fine tuning is executed in the following cases:

¢ If you are not satisfied with the control performance of the ES100P after executing A.T. (auto-tuning)

¢ When PV disturbance orcontrol cancellation caused by A.T. is not allowed in the system

With the fine tuning function, three improvement required levels are set for improvement of control performance. Fuzzy logic inference is executed from the improvement requirements and the control state up to that point to automatically correct PID parameters.

There are three improvement required levels:

Hunting inhibit required level Overshoot inhibit required level Response improvement required level

The strength of each of these required levels can be designated in five stages.

If two levels of control are required for a control target, two required levels can be set simultaneously. For example, you can set the required level for the “hunting inhibit” and “overshoot inhibit” parameters if both hunting and overshoot need to be improved. You cannot set three levels of control simultaneously for a control target.

Hunting inhibit required level

Hunting inhibit required level: 4 + Overshoot inhibit required level: 3

= wp oO fk Ow

Response improvement Overshoot inhibit required level required level

Page 23 read from a scan by OCR; it may hold reading errors

CHAPTER 2

PREPARATIONS

2.1

2.2

2.3

2.4

Installing the ES100P -------------

Output unit

External dimensions ---------------

Drilling mounting panels --------- Mounting the ES100P ------------- Setting the Switches ---------------

Switch names

Switch functions

Wiring Terminals ------------------

Precautions when wiring ----------

Input wiring

Output wiring

Wiring communication terminals

Wiring Expanded I/O

Connectors

Connections

Compatible connectors ------------

Connecting to I/O terminal block

2-2

2-3 2-3 2-3 2-4 2-4 2-4

2-5

2-5

2-7

2-8

2-8

2-9

2-9

CHAPTER 2

Page 24 read from a scan by OCR; it may hold reading errors

2.1 Installing the ES100P

|_| Output unit Four types of output unit are available for the ES100P. Select the output unit appropriate for how your ES100P is applied. @ Types of out- The following table shows the output units and their ratings. put unit Unit Type Model Rating Relay Output Unit E53-R 1c 250 V AC, 5 A (resistive load)

Mechanical life: 1,000,000 uses or more Electrical life: 100,000 uses or more

SSR Output Unit E53-S 1a 75 to 250 V AC, 1 A Gesistive load) Voltage Output Unit E53-Q NPN type 12 V DC, 40 mA

E53-Q3 NPN type 24 V DC, 20 mA

E53-Q4 PNP type 24 V DC, 20 mA Linear Output Unit E53-C3 4 to 20 mA DC (load 600 2 or less)

Possible for approx. 2600 resolution

E53-C3D 0 to 20 mA DC (load 600Q or less)

e Mounting the Possible for approx. 2600 resolution ; E53-V34 0 to 10 VDC (load 1 kQ or more)

output unit Possible for approx. 2600 resolution

E53-V35 0 to 5 VDC (load 1 kQ or more) Possible for approx. 2600 resolution

Insert the output unit into the on-board socket following the procedure below.

(1) Pull out the controller body. Push in the catch at the bottom of the controller to unlock the front panel from the rear panel. Pull out the body with the catch pushed in.

Pull out the body while pushing in : the catch at the Control output 2 (2) Mount the output unit. ;

bottom of the Insert the output unit for control output 1 into the on-board controller. socket marked “OUTPUT!” and the output unit for control output 2 into the on-board socket marked “OUTPUT2.”

(3) Snap in the attachment clips to hold the output unit firmly in place.

Be sure to attach the attachment clip.

Output unit With position-proportional controllers (model ES100P-RRP), a relay output unit of position- is provided at purchase. Therefore, this relay output unit does not need to be proportional purchased separately.

controllers

2-2

Page 25 read from a scan by OCR; it may hold reading errors

@ External dimensions

C96

Toa | Stet | sun BED sP soit =-BG88 nye St 2 RMT FSP AT WAIT MAN

PTN sTeP rat = {| | ee Ee

ES100P

DIGITAL CONTROLLER seeseee Seecces PUSH-OPEN

Lo | @ Drilling mounting panels | 100 mm or more | | | 5 en oe 8 ee | | | 120 mm | 92 mm ‘ or more | | 4-- - --+.- - -}.| 92mm | | | @ Securing the ES100P in position

13 169

160

112

| | ral ey mon

[191 to ‘ile

Recommended thickness of mounting panel: 1 to 8 mm Mounting cutout: 92 mm square

When mounting two or more ES100P, mount the controllers at intervals of at least 100 mm in the horizontal direction and at least 120 mm in the vertical direction.

Slot the two fixtures (supplied) into the fixing slot on the rear case with the ES100P pushed into the mounting hole.

The fixing slots are located on the top and bottom of the rear case.

Tighten the fixture screw until the ratchet turns idly.

CHAPTER 2

Page 26 read from a scan by OCR; it may hold reading errors

2.2 Setting the Switches

@ Switch names

OFF ON

Top of controller body

| ||

I

@ Switch functions, Thetable below shows the combination of DIP switch settings for achieving the following six functions.

. Switch Positions

Function Swi | SW2-1 | SW2-2| sw2.3|Sw24 Setting level 2 Technical mode (enabled) ° - © x x Setting level 2 Technical mode (disabled) O ~ x x x Setting level 1 x O _ Technical mode (enabled) ~ ~ Setting level 1 x x Technical mode (disabled) ~ ~ 7 Communications test O _ _ O (disabled/enabled) ~ Initialization mode ©) - - ©) x

O: ON X: OFF - - : ON/OFF

* All DIP switches are set to OFF before shipment from the factory.

¢ The “initialization mode” returns parameter settings to factory defaults.

* Set items marked “-” to the more frequently used switch setting. For example, if both switches SW2-1 and SW2-2 are set to ON, both the setting level 2 and 1 technical modes are enabled just by switching SW1.

@ Executing the switch functions Switch functions excluding the communications test can be executed in the ES/TOOLS Support Software. However, note that when you execute a switch function from the ES/ TOOLS Support Software, the switch settings may differ from the function (e.g. setting level) set on the switch. To execute the function set on the switch as instructed in the switch settings, turn the power supply OFF then back ON again.

@ Operation limitations Note that regular functions such as setting operations and communications do not work when executing the communications test and when in the initialization mode.

2-4

Page 27 read from a scan by OCR; it may hold reading errors

2.3 Wiring Terminals

@ Precautions when . Use ducts to separate input leads and power lines in order to protect the wiring

Input wiring

@ Analog input controller and its lines from external noise.

¢ We recommend using solderless terminals when wiring the controller.

¢ Tighten the terminal screws using a torque no greater than 78 N/cm (8 kgf/ cm). Take care not to tighten the terminal screws too tightly.

¢ Use solderless terminals applicable to M3.5 screws.

i Ht = TO) = orless

¢ When using soldered terminals, strip back the tip of the lead about 6 to 12 mm, and solder the tips of the exposed lead wire.

6~12 mm

* Connect analog input 1 to terminal Nos. 26 to 30. The input type determines how terminals are wired.

0) Q@ -®@ S S @ aA @ es Ee Le p< ]+ ®8 OOO ® mV

Le Thermocouple Platinum resistance Current Volgate Voltage input thermometer input input input (V) input (mV)

* Terminal Nos. 9, 10, 18 and 19 can be used for analog input only on 2-input type ES100P. So, check the model type before wiring inputs. Connect analog input 2 to terminal Nos. 9, 10, 18 and 19. The input type determines how terminals are wired.

; mae + ee ° ay ; | co} . ©! On ®. too ttosnee 41020mAinput = 4 to 8 Vinput

¢ Analog input 2 is insulated from internal circuits.

CHAPTER 2