Page 28
@CT input
@ Potentiometer * On position-proportional controllers, connect the potentiometer input to input terminal Nos. 31 to 33. On other types of controllers, connect CT input
(heater current detection) to these terminals.
The functions of these terminals are fixed, and cannot be changed by operation assignment, for example.
@ @o [he @w ) @c
CT input Potentiometer input
¢ Connect auxiliary inputs 1 to 3 (including COM terminal) to terminal Nos.
20 to 23. Run (DI1), reset (DI2) and hold (DI3) are assigned as switch 35 | inputs to these terminals before shipment from the factory. These terminals are enabled only on models ES100P-D0OD., - - > @ Dit (run), - @ Di (reset) Lb gs @ Di (hold)
me = @ com
¢ Auxiliary inputs are insulated from internal circuits. However, note that auxiliary inputs are not insulated from transfer output and control output when a current or voltage output unit is installed.
@ Output wiring
@ Control output ¢ Connect control outputs 1 to terminal Nos.4 and 5, and control outputs 2 to terminal Nos.13 and 14. Connect the control outputs to suit the output unit mounted on the ES100P. When connecting voltage or current output, check the polarity of the connection before wiring.
35] For details on output units, see page 2-2. + + fee pee -O® -0@ 12 VDC 24 VDC 40 mA 20 mA © Oo® ‘06 '‘-0© Relay output SSR output Voltage Voltage output (12 V) output (24 V)
“OO -0® “eo -00
4to20 mA 0 to20mA 0 to 10 VDC 0 to 5 VDC, O®, O®, O®, O® Linear output Linear output Linear output Linear output
¢ When carrying out heating-cooling control, use control output 1 as heating output, and control output 2 as cooling output.
Control output (position-proportional)
2-6
Page 29
@ Auxiliary * Connect auxiliary outputs 1 to terminal Nos.1 to 3, and auxiliary outputs output 2 to terminal Nos.11 and 12. These terminals are assigned as deviation upper limit alarm output before shipment from the factory.
250 VAC | ;=§ - @ 250 VAC ¢e 3A 3A ®
Auxiliary output 1 Auxiliary output 2
35 |
¢ Terminal Nos. 9, 10, 18 and 19 can be used for auxiliary output only on ES100P- OOD models. So, check the model type before wiring outputs. Connect auxiliary outputs 3 and 4 to terminal Nos.9 and 10. The +24 V power supply should be connected to terminal Nos.18 and 19. These terminals are assigned as time signals 1 (DO3) and 2 (DO4) before shipment from the factory.
Auxiliary outputs 3, 4
¢ Auxiliary outputs are insulated from internal circuits.
@ Transfer outputs ¢ Connect transfer output to terminal Nos.34 and 35. These terminals are enabled only on models ES100P-DO.OFO.
+ ptt 20 mA @ @
Transfer outputs
¢ Transfer outputs are insulated from internal circuits. However, note that transfer outputs are not insulated from control output and auxiliary input when a current or voltage output unit is installed.
@ Wiring communi-_ -’ Terminal Nos. 15 to 17, 24 and 25 are used for wiring communication cation terminals terminal. The terminals of models ES100P-C1111 010 are arranged for RS-232C communication, and the terminals of models ES100P-000 040 are arranged for RS-422/485 communication. Check which model communication terminals are to be wired to before wiring.
e ®
6 @ e ©®
RS232C RS422 RS485
2-7
Page 30
2.4 Wiring Expanded I/O Connectors
@ Connections
2-8
Expanded I/O connectors can be used on models ES100P-CIMOE. Either of the digital I/O terminals or BCD communications terminals can be selected for use in the parameter settings. (The ES100P is set for digital I/O before shipment from the factory.)
The following description assumes that the ES100P has been set for digital I/O. For details on using the ES100P for BCD communications, see the ES100 Digital Controller User’s Manual (Communications Guide) (Cat. No. H072-E1-1).
Digital inputs 1 to 8 and digital outputs 3 to 10 are provided for expanded I/O connectors. External 24 V DC power supplies are required for each of digital input and output.
Vv GND 1 | 2 |GNDI 424 VDC for hoxiiay H - 4| - - plcavi] 3 | 4 [+24 VI) finput (run) --o-O - >} pit | 5 | 6 | DI2 }¢ - O~O-+ (reset)
(hold) +-o-O - » DI3| 7 | 8 | DI4 k# - O~O oO, >) DIS | 9 | 10 | DIG }# - O-~O, oO - > DIZ | 11 | 12 | Dis } - d~O - 13 | 14 15 | 16 17 | 18 19 | 20 Tiaavod te On 424VO| 23 | 24 |s24vojfoueut
(time signal 1)
pos} 25 | 26 | poat+ - (L)- time signal 2)
DO5| 27 | 28 | DOG, (L}- po7| 29 | 30 | pos+ - (L}4 H - ()4
DO9} 31 | 32 | DOI10 33 | 34 iaaaa
¢ The following pins are connected to each other internally. 1-2, 3-4, 21-22 and 23-24
¢ Items in parentheses (_) indicate the defaults assigned to terminals before shipment from the factory.
Page 31
= Compatible connectors
Use an OMRON XG4M-3430 connector or equivalent product as the connector for the cable for connecting to the expanded I/O connectors.
a Connecting to I/O > We recommend the following connection configurations when connecting I/O of the expanded I/O connectors to a terminal block.
terminal block
@ When connecting output to the I/O relay terminal:
ES100P
@ When connecting input to the terminal block and output to the
I/O relay terminal:
m n _* SLT TT ATTY] i=) 8
@ When connecting both input and output to the terminal block:
LITT |
LEE ETT TT
ES100P
Output cable (G79-200C-ES1)
00000000
QB] @/ @/@/@/@/O/@/@/@ @/@| @/@/@/@/O/@/@/@
I/O relay terminal (G7T-OCO8)
400 mm (yellow lead) __, - - > 150 mm (red lead)
/O cable (G79-200C-175-ES1)
G5
Te]
Sie] ry
Kr
Te
200 cm Stel | | ee ret 2!
18
Te ary
V/O cable ny (XW2Z-200C) S18) rate
-~ ®
@ + - __|
CC]
8/2/9/0/8/e/2/2/2/9)
[e[e|e|e|e/e/e/9/8/e
Input terminal block (XW2B-20G5)
OOO00000
@]@/@/@) @/@/@/@/@/@
Q|@] @/ @©/@/@/@/8/@\@
I/O terminal block (XW2B-34G5)
I/O relay terminal (G7TC-OC08)
CHAPTER 2
Page 32
@ Terminal block When using one of the above recommended connection configurations, the wiring diagram wiring at the terminal block is as follows.
V/O terminal block (XW2B-34G5)
GNDI}+24Vii Dit | DI3| DI5} DI7 GNDO}+24 VO] DO3] DOS} DO7]| DOS 1 3 5 7 9 i1 113 [| 15 | 17 | 19 | 21 | 23 | 25 | 27 | 29 | 31 | 33 2 4 6 8 10 | 12 | 14 | 16 | 18 | 20 | 22 | 24 | 26 | 28 | 30 | 32 | 34
GNDI}+24 Vl] DI2 | Dl4 | DI6 | DI8 GNDO}+24 VO] DO4] DO6] DOS] D10
Input terminal block (XW2B-20G5)
+24VI1GNDI} DI1 | DI3| DI5] DI7
1 3 7} 9 111 113 | 15 | 17 | 19 2 41,6 | 8 | 10} 12 114 116 | 18 | 20
+24 VI}GNDI] Di2 | Di4 | DIG | DI8
/O Relay Terminal (G7TC-OC08)
24 VO DO3] DO4} DOS] DO6! DO7| DO8} DOY] DO10
+ 0 1 2 3 4 5 6 7 = co | Ci | C2 | C3 | C4 { C5 | C6 | C7
GNDO
2-10
Page 33
CHAPTER 3
BASIC OPERATION
3.1 3.2 3.3
3.4
3.5,
3.6
3.7
3.8
Operation Flow
How to Use the Panel Keys ------ Setting I/O Specifications -------- Analog input
Direct/reverse action -------------- Control output cycle --------------- Key Display and Assignments --- PF key Bar graph
Setting Events What is an “event’’? ---------------
Event specifications ---------------
Event settings Setting up Programs --------------- How programs are configured --- Pattern parameters ----------------- Step parameters
Editing steps Starting and Stopping Control
Starting operation ------------------ Stopping operation ---------------- Adjusting Control Operation ----- Changing currently executing patterns Manual operation ------------------ Auto-tuning --
Fine tuning
3-12 3-13 3-13 3-14 3-17 3-20
3-21 3-21 3-21 3-22
3-22 3-23 3-24 3-26
CHAPTER 3
Page 34
3.1 Operation Flow
(
Set the specifications.
Set up the program.
(_
Start control.
( a
Make adjustments.
Stop control.
Check control operation. = rin
Designate the input type, and set scaling, event specifications settings and other parameters matched to how the ES100P is to be applied.
Note that the setting level must be switched between setting level 1 and 2 by the parameters.
Various patterns are available on the ES100P. These patterns can be switched and linked. Set up the program using the desired patterns.
When you have finished setting the specifications and operating conditions, Start operation.
Change and adjust settings such as SP and events while monitoring the control status. If necessary, switch to manual control.
When the program has stopped running, control stops. To forcibly stop operation, reset the ES100P.
Initializing Follow the procedure below to restore the ES100P parameter settings to the parameters defaults set before shipment from the factory. (1) Set switches SW1 and SW2-3 to ON.
(2) The No.1 display indicates €t Er. (3) Press the key. This executes initialization of the ES100P. (4) When the No.1 display indicates £ & ad this indicates that initialization has ended.
(5) Restore the switches to their original positions.
3-2