Manual · Omron
ES100P Digital Controller User Manual
Manual34 pagesPDF 3.5 MB
Opening part of the OMRON ES100P digital controller user manual: features, parts, installation, switch settings and wiring.
Filed with · 4 models
Also filed with these models on the old site
Summary
What is in it
The first part of OMRON's user manual for the ES100P programmable digital controller. This file holds the front matter, the full table of contents, installation precautions, Chapter 1 (features, names of parts, input and output, setting levels, operation assignment and fine tuning) and Chapter 2 (installing the ES100P, switch settings, wiring terminals and expanded I/O connectors), ending at the start of Chapter 3, Basic Operation. Communications and support software are covered in separate manuals. The text is OCR.
Its parts
- Chapter 1 What is the ES100P?
- Chapter 2 Preparations
- Chapter 3 Basic Operation
- Chapter 4 Applied Operation
- Chapter 5 Parameters
- Chapter 6 Typical Examples
- Chapter 7 Troubleshooting
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
This is the ES100P Digital Controller User Manual for the ES100P series, the programmable type of the ES100 digital controller. It describes the features, front panel, inputs and outputs, output units, panel mounting, DIP switch settings and terminal wiring. This file holds only the opening chapters, ending at the start of basic operation, so the troubleshooting chapter and specification appendix are not in it.
- Device
- ES100P programmable digital controller, the programmable type of the ES100 p. 1, 3
- Power supply
- 100 to 240 V AC at 50 to 60 Hz; the voltage must be reached within two seconds of power ON p. 6
- Analog input 1
- 26 input types: 17 temperature sensor (thermocouple and platinum resistance thermometer), seven voltage, two current p. 16
- Control outputs
- Two; relay, SSR, voltage or current output, set by the output unit installed p. 17
- Output units
- E53-R relay (1c 250 V AC, 5 A resistive); E53-S SSR (1a 75 to 250 V AC, 1 A); E53-Q (NPN 12 V DC, 40 mA), E53-Q3 (NPN 24 V DC, 20 mA), E53-Q4 (PNP 24 V DC, 20 mA) voltage p. 24
- Linear output units
- E53-C3 4 to 20 mA DC, E53-C3D 0 to 20 mA DC, E53-V34 0 to 10 VDC, E53-V35 0 to 5 VDC; approx. 2600 resolution p. 24
- Programs
- Up to 99 program patterns of up to 100 steps (a maximum of 400 steps) in a single pattern p. 12
- Auxiliary outputs
- Ten: outputs 1 and 2 relay (250 VAC, 3A), outputs 3 to 10 open-collector; 3 to 10 are not on every model p. 17, 29
- Auxiliary inputs
- Up to eight on models with expanded I/O connectors, up to three on models without p. 16
- Communications
- Rear terminals for RS-232C or RS-422/485, depending on model; front RS-232C jack for ES/TOOLS support software p. 15, 29
- Panel mounting
- 92 mm square cutout in a 1 to 8 mm panel; space units at least 100 mm apart horizontally, 120 mm vertically p. 25
- Operating environment
- -10°C to 55°C, 35%RH to 85%RH (no ice or condensation); storage -25°C to 65°C p. 6
- Terminal screws
- M3.5 solderless terminals; torque no greater than 78 N/cm (8 kgf/cm) p. 27
- Expanded I/O
- Digital inputs 1 to 8 and digital outputs 3 to 10, each needing an external 24 V DC supply; can be set for BCD communications instead p. 30
What this manual walks you through
- Installing an output unit in the controller p. 24
- Mounting the controller in a panel p. 25
- Setting the DIP switches for setting levels, technical modes and initialization p. 26
- Switching between setting levels 1 and 2 p. 18
- Wiring analog inputs p. 27
- Wiring control, auxiliary and transfer outputs p. 28, 29
- Wiring the expanded I/O connectors p. 30
- Reading the front panel displays and indicators p. 14, 15
- Restoring factory default parameters p. 34
- Reducing electrical noise when wiring p. 6
Good to know
- Do not use the controller where there is icing, condensation, dust or corrosive gas. p. 6
- Setting operations and communications do not work during the communications test or in initialization mode. p. 26
- Auxiliary inputs are not insulated from transfer and control outputs when a current or voltage output unit is installed. p. 28
- On models with expanded I/O connectors, the auxiliary inputs cannot be used with BCD communications. p. 16
- Only the dedicated cable works with the ES/TOOLS support software. p. 15
Questions this manual answers
How do I reset the ES100P to factory default settings?
Set DIP switches SW1 and SW2-3 to ON, run initialization from the front keys when the No.1 display prompts, then restore the switches. p. 34
What supply voltage does the ES100P need?
A stable 100 to 240 V AC at 50 to 60 Hz, reaching that level within two seconds of power ON. p. 6
Which output units fit the ES100P?
Four types: relay (E53-R), SSR (E53-S), voltage (E53-Q, E53-Q3, E53-Q4) and linear (E53-C3, E53-C3D, E53-V34, E53-V35). p. 24
What panel cutout does the ES100P need?
A 92 mm square cutout in a panel 1 to 8 mm thick. p. 25
What sensors can the ES100P read?
Analog input 1 accepts 26 types: thermocouples and platinum resistance thermometers (17 types), seven voltage and two current inputs. p. 16
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 4 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file