The text of a spec sheet · part 1 of 2
Switch Mode Power Supply S82J (10/25/50/100/150/300/600-W Models), pages 1 to 10
Pages 1 to 10 of 20
The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron S82J-02505 and Omron S82J-10024
Page 1
Switch Mode Power Supply
S82J (10/25/50/100/150/300/600-W Models) CSM_S82J_DS_E_3_1
Low-cost Global Power Supply with CE Marking • Safety standards: UL: UL508 (Class 2), No.60950-1, cUL: CSA C22.2 No. 14 (Class 2), cUR: 60950-1, EN50178 (= VDE0160) EMC: Conforms to EN61204-3 Class A • Mounting bracket available for standard models Front-mounting bracket type DIN Rail mounting type (except 300 W and 600 W) • RoHS-compliant ! Refer to Safety Precautions for All Power Supplies.
Model Number Structure ■ Model Number Legend Note: Not all combinations are possible. Refer to List of Models in Ordering Information on page 2 and 3.
S82J 1 1. Power Ratings 010: 10 W 025: 25 W 050: 50 W 100: 100 W 150: 150 W 300: 300 W 600: 600 W
2
3
4 3. Configuration 10-/25-/50-/100-/150-W models A: Open-frame type, front terminals D: Covered type, front terminals
4. Mounting Bracket None: Front-mounting bracket type D: DIN Rail mounting bracket type
Mounting bracket None: With mounting bracket N: Without mounting bracket
2. Output Voltage 05: 5V 12: 12 V 15: 15 V 24: 24 V
1
Page 2
S82J
Ordering Information ■ List of Models Note: For details on normal stock models, contact your nearest OMRON representative.
Front-mounting Bracket Models Configuration
Open-frame type
Input Voltage
100 to 240 VAC (free)
Power ratings
10 W
25 W
50 W
100 or 200 VAC (selected automatically)
100 W
100 to 240 VAC (free)
Covered type
100 or 200 VAC (selected automatically)
150 W
100 to 240 VAC (free)
10 W
25 W
50 W
100 or 200 VAC (selected automatically)
100 W
100 to 240 VAC (free)
Output voltage Output current
Front-mounting bracket models (Front terminals)
5V
2A
S82J-01005A
12 V
1A
S82J-01012A
15 V
0.7 A
S82J-01015A
24 V
0.5 A
S82J-01024A
5V
5A
S82J-02505A
12 V
2.1 A
S82J-02512A
15 V
1.7 A
S82J-02515A
24 V
1.1 A
S82J-02524A
5V
10 A
S82J-05005A
12 V
4.2 A
S82J-05012A
24 V
2.1 A
S82J-05024A
5V
20 A
S82J-10005A
12 V
8.5 A
S82J-10012A
15 V
7A
S82J-10015A
24 V
4.5 A
S82J-10024A
24 V
6.5 A
S82J-15024A
5V
2A
S82J-01005D
12 V
1A
S82J-01012D
15 V
0.7 A
S82J-01015D
24 V
0.5 A
S82J-01024D
5V
5A
S82J-02505D
12 V
2.1 A
S82J-02512D
15 V
1.7 A
S82J-02515D
24 V
1.1 A
S82J-02524D
5V
10 A
S82J-05005D
12 V
4.2 A
S82J-05012D
24 V
2.1 A
S82J-05024D
5V
20 A
S82J-10005D
12 V
8.5 A
S82J-10012D
15 V
7A
S82J-10015D
24 V
4.5 A
S82J-10024D
100 or 200 VAC (selected automatically)
150 W
24 V
6.5 A
S82J-15024D
100 or 200 VAC (selectable)
300 W
24 V
14 A
S82J-30024
27 A
S82J-60024
S82J-30024N 600 W
S82J-60024N
2
Page 3
S82J DIN Rail Mounting Bracket Models Configuration
Open-frame type
Input Voltage
100 to 240 VAC (free)
Power ratings Output voltage Output current
10 W
25 W
50 W
100 or 200 VAC (selected automatically)
100 W
100 to 240 VAC (free)
Covered type
DIN Rail mounting bracket models (Front terminals)
5V
2A
12 V
1A
S82J-01005AD S82J-01012AD
15 V
0.7 A
S82J-01015AD
24 V
0.5 A
S82J-01024AD
5V
5A
S82J-02505AD
12 V
2.1 A
S82J-02512AD
15 V
1.7 A
S82J-02515AD
24 V
1.1 A
S82J-02524AD
5V
10 A
S82J-05005AD
12 V
4.2 A
S82J-05012AD
24 V
2.1 A
S82J-05024AD
5V
20 A
S82J-10005AD
12 V
8.5 A
S82J-10012AD
15 V
7A
S82J-10015AD
24 V
4.5 A
S82J-10024AD
100 or 200 VAC (selected automatically)
150 W
24 V
6.5 A
S82J-15024AD
100 to 240 VAC (free)
10 W
5V
2A
S82J-01005DD
12 V
1A
S82J-01012DD
15 V
0.7 A
S82J-01015DD
25 W
50 W
100 or 200 VAC (selected automatically)
100 W
100 to 240 VAC (free) 100 or 200 VAC (selected automatically)
150 W
24 V
0.5 A
S82J-01024DD
5V
5A
S82J-02505DD
12 V
2.1 A
S82J-02512DD
15 V
1.7 A
S82J-02515DD
24 V
1.1 A
S82J-02524DD
5V
10 A
S82J-05005DD
12 V
4.2 A
S82J-05012DD
24 V
2.1 A
S82J-05024DD
5V
20 A
S82J-10005DD
12 V
8.5 A
S82J-10012DD
15 V
7A
S82J-10015DD
24 V
4.5 A
S82J-10024DD
24 V
6.5 A
S82J-15024DD
■ Accessories (Order Separately) Front Mounting Bracket (for the S82J-10024A and S82J-10024D) S82Y-J10F
Replacement Fan S82Y-JFAN
3
Page 4
S82J
Specifications ■ Ratings/Characteristics Power ratings (See note 1.)
100 to 240 V (Free) 10 W
25 W
50 W
Efficiency (typical)
67% min. (Varies depending on specifications)
Input
100 to 240 VAC (85 to 264 VAC)
Voltage (See note 2.)
100/200 (Selected automatically) 100 W (24 V) 83% min.
100 W (5 V, 12 V, 15 V) 75% min.
150 W
100/200 (Selected) 300 W
600 W
82% min.
100 VAC (85 to 132 VAC) 100 VAC (85 to 132 VAC) 110 to 170 VDC (10-W and 25-W models only) (See 200 VAC (170 to 264 VAC) 200 VAC (170 to 253 VAC) (selected automatically) (selectable) note 11.)
Frequency (See note 2.)
50/60 Hz (47 to 450 Hz)
Current (See note 3.)
100-V input
0.35 A max. 0.8 max.
1.4 A max.
2.5 A max. 2.5 A max.
3.5 A max.
8 A max.
14 A max.
200-V input
0.3 A max.
0.8 A max.
1.5 A max. 1.4 A max.
2.1 A max.
4 A max.
7 A max.
0.6 A max.
Leakage current 100-V input (See note 3.) 200-V input
0.5 mA max.
Inrush current (See note 3.)
100-V input
25 A max. (for a cold start at 25°)
30 A max. (for a cold start at 25°)
200-V input
50 A max. (for a cold start at 25°)
60 A max. (for a cold start at 25°)
Noise filter
1 mA max.
Yes
Output Voltage Adjustment Range (See note 5.) (See note 4.) Ripple (See note 3.)
±10% (with V. ADJ) 2% (p-p) max.
Input variation influence
0.4% max.
Load variation influence
0.8% max. (10% to 100% load, rated input voltage)
Temperature variation influence 0.05%/°C max. (at rated input and output) Startup time
Additional functions
Other
500 ms max. (up to 90% of output voltage at rated input and output)
300 ms max. (up to 90% of output voltage at rated input and output)
Hold time (See note 3.)
20 ms min.
Overload protection (See note 6.)
105% to 160% of rated load current, voltage/current drop, intermittent operation (10-W and 25-W models) gradual current increase/ voltage drop, intermittent operation (50-W, 100-W (24 V) models), automatic reset
105% of rated load current, Inverted L voltage drop, automatic reset (For the 600-W model, the circuit will be shut OFF when the overload exceeds 5 s.)
Overvoltage protection
No
Yes (See note 8.)
Overheat protection
No
Parallel operation
No
Yes (up to 5 units)
Protection-ON alarm indicator
No
Yes (color: red)
Yes (See note 7.)
Yes (5-V No output only) (See note 7.)
Yes (See note 8.)
Ambient operating temperature Refer to the derating curve in Engineering Data. (with no icing or condensation) Storage temperature
−25 to 65°C (with no icing or condensation)
Ambient operating humidity
25% to 85% (Storage humidity: 25% to 90%)
Dielectric strength
3.0 k VAC for 1 min. (between all inputs and all outputs) 2.2 k VAC for 1 min. (between all inputs and all outputs/PE terminals) 1.0 k VAC for 1 min. (between all outputs and PE terminal)
Insulation resistance
100 MΩ min. (between all outputs and all inputs/ PE terminals) at 500 VDC
Vibration resistance
10 to 55 Hz, 0.375-mm single amplitude for 2h each in X, Y, and Z directions
Shock resistance
300m/s2, 3 times each in ±X, ±Y, ±Z directions
Output indicator EMI
Yes (color: green) Conducted Conforms to EN61204-3 EN55011 Class A and based on FCC Class A Emissions (See note 3.) Radiated Emissions
Conforms to EN61204-3 EN55011 Class A (See note 9.)
EMS
Conforms to EN61204-3 Low severity levels
Approved standards
UL: UL508 (Listing; Class 2: Per UL1310 Class 2 approved for 10-W, 25-W (except for 5-V output)), and 50-W (only for 24-V output) models.), UL60950-1 cUL: CSA C22.2 No.14 (Class 2 approved for 10-W, 25-W (except for 5-V output), and 50-W (only for 24-V output) models.) cUR: CSA No. 60950-1 EN/VDE: EN50178 (=VDE0160) Terminal types (only terminal part): VDE0106/P100 Based on VE0106/P100
Models with Terminals UL: UL508 (Listing), UL1012, UL60950-1 cUL: CSA C22.2 No. 14 (Listing) cUR: CSA No. 60950-1 EN/VDE: EN50178 (=VDE0160) Terminal types (only terminal part): VDE0106/P100 Based on VE0106/P100 Models with Connectors UL: UL508, UL1012, UL60950-1 CSA: CSA C22.2 No.14 CSA No. 60950-1 EN/VDE: EN50178 (=VDE0160)
UL: UL508, UL1012 CSA: EB1402C, C22.2 No. 14 EN/VDE: EN50178 (=VDE0160) Terminal types (only terminal part): VDE0106/P100 Based on VE0106/P100
Weight (See note 10.)
250 g max.
500 g max. 1,000 g max.
2,000 g max.
350 g max.
400 g max.
2,500 g max.
4
Page 5
S82J Note: 1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the power supply may not start. Be sure to select a Power Supply with sufficient capacity. Refer to Overload Protection on page 10 for details. 2. Do not use the Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning. 3. Defined with a 100% load and the rated input voltage (100 or 200 VAC.) 4. The output specification is defined at the power output terminals. 5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +10% of the voltage adjustment range. When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged. 6. Refer to Overload Protection on page 10 for details. 7. For resetting, turn OFF the power, leave for more than one minute, and then turn it ON again. 8. The protection-ON alarm indicator will light as soon as the output is interrupted. For resetting, turn OFF the input power, leave for more than three minutes (90 seconds min. for the 300-W models), and then turn it back ON again. 9. Radiated emissions: The noise value is affected by factors such as the wiring method. For 300-W and 600-W models, use shielded wire for all wiring, and insert one noise clamp filter (TDK, ZCAT3035-1330) on the input wire, and two noise clamp filters on the load wire. 10.The weight indicated is the weight of the open-frame type. (Includes the covers for 300-W and 600-W models)
Connections ■ Block Diagrams S82J-010@@@@ (10 W) S82J-025@@@@ (25 W) Fuse (See note.)
Rectification
Smoothing +V
AC (L)
Input
Noise Noisefilter filter
DC Output −V
AC (N)
Inrush current protection circuit
Rectifier/ smoothing circuit
Note: Fuse capacity: 10 W, 1 A 25 W, 2 A Control circuit
Overcurrent detection circuit
Detection circuit Photocoupler
S82J-050@@@@ (50 W) Fuse (3A)
Rectification
Smoothing +V
AC (L)
Input
Noise Noisefilter filter
DC Output −V
AC (N)
Inrush current protection circuit
Rectifier/ smoothing circuit
Control circuit
Overcurrent detection circuit
Detection circuit Photocoupler
5
Page 6
S82J S82J-100@@@@ (100 W, 5-/12-/15-V Output) Fuse (5A) +V
AC (L)
Input
Noise Noisefilter filter
DC Output −V
AC (N) 100 or 200 V
Rectifier/ smoothing circuit
Inrush current (selected protection circuit automatically)
Rectifier/ smoothing circuit
Control circuit Detection circuit
Overcurrent detection circuit
Photocoupler Overvoltage detector
Overvoltage protection circuit (5 V only)
S82J-10024@@ (100 W, 24-V Output) Fuse (5 A)
Smoothing
Rectification
+V
AC (L)
Input
Noise Noisefilter filter
DC Output −V
AC (N)
Inrush current protection circuit
Rectifier/ smoothing circuit
Control circuit
Overcurrent detection circuit
Detection circuit Photocoupler
Photocoupler
Overvoltage detector
S82J-15024@@ (150 W)
Fuse (8 A) +V
AC (L)
Input
Noise Noisefilter filter
DC Output −V
AC (N) 100 or 200 V
Inrush current (selected protection circuit automatically)
Rectifier/ smoothing circuit
Rectifier/ smoothing circuit
Control circuit
Overcurrent detection circuit
Detection circuit Photocoupler
6
Page 7
S82J S82J-30024@ (300 W) Rectifier/ smoothing circuit
Fuse (10 A) Input
DC Output
Noise filter Inrush current protection circuit
Rectifier/ smoothing circuit
100/200 V (selectable) Control circuit
Detection circuit
Overcurrent detection circuit Photocoupler
Photocoupler
Overvoltage detection circuit Note: Short-circuit the input voltage selector terminals if the input is 100 to 120 VAC. Keep the terminals open if the input is 200 to 230 VAC.
Parallel operation selector
S82J-60024@ (600 W) Rectifier/ smoothing circuit
Fuse (20 A) Input
Noise filter
DC Output Inrush current protection circuit
Rectifier/ smoothing circuit
100/200 V (selectable) Fan Control circuit
Detection circuit
Overcurrent detection circuit Photocoupler Overheat detection circuit Photocoupler
Overvoltage detection circuit
Note: Short-circuit the input voltage selector terminals if the input is 100 to 120 VAC. Keep the terminals open if the input is 200 to 230 VAC.
Parallel operation selector
7
Page 8
S82J
Construction and Nomenclature ■ Nomenclature 10-/25-/50-/100-/150-W Models
5 6 +V
1
−V 3 AC (L) 2 AC (N)
300-W Models 1. DC Output Terminals (+V), (−V): Connect the load lines to these terminals. 2. AC Input Terminals (L), (N): Connect the input lines to these terminals.
5 6 1
+V
AC (L)
+V
2
AC (N)
−V
4
−V
Side view
3 7
8
600-W Models 6 5
1
−V −V +V +V
7
Side view
8
Note: 1. The fuse is located on the (L) side. It is NOT user replaceable. 2. For DC input (10-W, 25-W models), use the (L) terminal as the positive terminal. 3. Protective Earthing Terminal ( ): Connect the ground line to this terminal. 4. Input Voltage Selector Terminals: Short-circuit the terminals if the input is 100 to 120 VAC and open the terminals if the input is 200 to 230 VAC 5. Output Indicator (DC ON: Green): Lights while a Direct Current (DC) output is ON. 6. Output Voltage Adjuster (V.ADJ): It is possible to increase or decrease the output voltage by 10%. 7. Protection-ON Alarm Indicator (DC ON: Red): The red indicator will be lit if the overvoltage (for a 300-/600-W model) or overheat protection (for a 600-W model) circuit is triggered. This indicator will also be lit when overload (for a 600-W model) is detected. 8. Selector of Parallel Operation: Set the selector to PARALLEL if the Units are in parallel operation.
AC (L) AC (N)
4
2
3
8
Page 9
S82J
Engineering Data ■ Derating Curve (for Standard Mounting) 10-/25-/50-/100-/150-W Model Open-frame Type
Covered Type
Standard Mounting Forced air-cooling (1 m3/min)
Natural air-cooling
Load ratio (%)
Load ratio (%)
Forced air-cooling (1 m3/min)
Natural air-cooling
Note: The derating curve shown is for standard mounting. The derating curve depends on the mounting direction of the Power Supply. Ambient temperature (°C)
Ambient temperature (°C)
300-W Model
Single-unit Operation 120
Parallel Operation
20 mm min.
Load ratio (%)
Load ratio (%)
20 mm min.
Forced air-cooling (1 m3/min) (Standard mounting)
100
100
Natural air-cooling (Standard mounting) Forced air-cooling (1 m3/min) (Side mounting) Natural cooling (Side mounting)
Standard Mounting
120
Forced air-cooling (1 m3/min) (Standard mounting)
Natural air-cooling (Standard mounting) Forced air-cooling (1 m3/min) (Side mounting)
20 mm min.
20 mm min.
Natural cooling (Side mounting)
Ambient temperature (°C)
Ambient temperature (°C)
Note: Provide a minimum clearance of 20 mm between the Power Supplies.
600-W Model
Parallel Operation
Standard Mounting
120
120
20 mm min.
100
100
Load ratio (%)
Load ratio (%)
Single-unit Operation
20 mm min.
Ambient temperature (°C)
20 mm min.
20 mm min.
Ambient temperature (°C)
Note: Provide a minimum clearance of 20 mm between the Power Supplies.
9
Page 10
S82J 10- to 300-W Models The Power Supply is provided with an overload protection function that protects the Power Supply from possible damage by overcurrent. When the output current rises above 105% to 160% of the rated output current, the protection function is triggered, automatically decreasing the output voltage. When the output current falls within the rated range, the overload protection function is automatically cleared.
Output voltage (V)
10 W, 25 W Models
Note: Internal parts may occasionally deteriorate or be damaged if a short-circuited state continues during operation. Eliminate the overcurrent state as soon as possible.
■ Overvoltage Protection 100-W (5-, 24-V Output) Models Consider the possibility of an overvoltage and design the system so that the load will not be subjected to an excessive voltage even if the feedback circuit in the Power Supply fails. When an excessive voltage that is approximately 120% of the rated voltage or more is output, the output voltage is shut OFF, preventing damage to the load due to overvoltage. Reset the input power by turning it OFF for at least one minute and then turning it back ON again. Output voltage (V)
■ Overload Protection
Intermitted operation
0
50
100 Output current (%)
Rated output voltage
Voltage adjustable range
Output voltage (V)
50 W, 100 W (24-V) Models
Overvoltage protection operates
The values shown in the above diagram are for reference only.
Intermitted operation
0
50
100 Output current (%)
Output voltage (V)
100 W (5-V, 12-V, 15-V), 150 W, 300 W Models
300- and 600-W Models When an excessive voltage that is approximately 120% of the rated voltage or more is output, the output voltage will be turned OFF and simultaneously the protection-ON alarm indicator will be lit. Reset the input power by turning it OFF for at least three minutes (90 seconds for 300-W models) and then turning it back ON again.
■ Overheat Protection Function 600-W Models Only
0
50
100
Output current (%)
The values shown in the above diagrams are for reference only. Note: 1. If the S82J is connected to a load with a built-in DC-DC converter, the overload protection function may be triggered at startup, and consequently the S82J may not operate. 2. Internal parts may occasionally deteriorate or be damaged if a short-circuited or other overcurrent state continues during operation. Eliminate the overcurrent state as soon as possible. 3. In actual operation, the output voltage may not fall to 0 V when the overload protection function is triggered. Even with short-circuits on the load side, the drop in voltage will vary depending on factors such as the impedance in the load line. 4. The overload protection function is specified at 105% or more of the rated output current for 300-W models.
600-W Models
If the internal temperature rises excessively as a result of fan failure or any other reason, the overheat protection circuit will be triggered to protect the internal parts and simultaneously the protection-ON alarm indicator will be lit. Reset the input power by turning it OFF for at least three minutes and then turning it back ON again.
■ Inrush Current, Startup Time, Hold Time Input ON
Input OFF
AC input voltage
Inrush current on input application AC input current 96.5%
Output voltage (V)
90% Output voltage
Output interrupted 0
Startup time
Hold time (20 ms min.)
Note: Models with a 100 to 240 V (free) input have a higher inrush current energy than models with a single rated input voltage or models with a switchable input voltage. Be sure to coordinate breaker with the inrush current energy.
50 100 Output current (%)
If an excessive current flows for 5 s or more, the output will be turned OFF and simultaneously the protection-ON alarm indicator will be lit. To reset the S82J, turn OFF the power, leave the S82J for at least three minutes, and then turn it ON again.
10