Spec sheet · Omron
Switch Mode Power Supply S82K (3/7.5/15/30/50/90/100-W Models)
Spec sheet15 pagesPDF 1.5 MB
Datasheet for the Omron S82K DIN-rail switch mode power supplies from 3 to 100 W, including the 3 W, 12 V S82K-00312.
Covers · 1 model
The models it covers
Summary
What is in it
Omron datasheet for the S82K family of DIN-rail switch mode power supplies, 3 to 100 W, with 5, 12, 15, 24, plus or minus 12 and plus or minus 15 VDC outputs. It explains the model number structure and lists all models (the S82K-00312 is the 3 W, 12 V version), then gives ratings and characteristics, approvals, block diagrams, terminal names, derating curves, mounting, overload protection, the undervoltage alarm, inrush and hold times, reliability figures and dimensions.
Its parts
- Model Number Structure
- Ordering Information
- Specifications
- Connections
- Construction and Nomenclature
- Engineering Data
- Dimensions
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Omron data sheet CSM_S82K_DS_E_3_1 for the S82K series of DIN-rail switch mode power supplies from 3 W to 100 W, which includes the S82K-00312. It gives the model legend and list, ratings, block diagrams, derating and protection behavior, dimensions, accessories, and mounting and wiring precautions.
- Device
- S82K-00312: DIN-rail switch mode power supply, 3 W, +12 VDC output, no power factor correction p. 1
- AC input
- 100 to 240 VAC (85 to 264 VAC), 50/60 Hz (47 to 450 Hz) p. 1, 2
- Indicators
- Green DC ON lights while the DC output is on; red DC LOW lights when output drops to 75% to 90% of rated voltage p. 6, 8
- Ripple
- 2% (p-p) max. p. 2
- Hold time
- 20 ms min. p. 2, 9
- Overload protection
- Above 105% of rated current the output voltage drops; resets automatically when current returns to the rated range p. 8
- Internal fuse
- 1 A on S82K-003@@ (3 W) and S82K-007@@ single-output models p. 4
- Input variation influence
- 0.5% max. at 85 to 264 VAC input, 100% load p. 2
- Dielectric strength
- 3.0 kVAC for 1 min between all inputs and all outputs p. 2
- Storage and humidity
- Storage -25 to 65°C; operating humidity 25% to 85% (storage 25% to 90%) p. 2
- Reliability
- MTBF 135,000 hrs min.; life expectancy 8 yrs. min. at 40°C and 50% load p. 9
- Terminal screws
- M3.5, tightened to 0.98 N·m p. 13
- DIN rail
- PFP-100N, PFP-50N or PFP-100N2 aluminum rail, ordered separately; mounting brackets supplied for non-rail mounting p. 10, 12
- Noise filter
- S82Y-JF3-N for 3- to 50-W models, ordered separately p. 12
What this sheet walks you through
- Decoding S82K model numbers and choosing a model p. 1
- Reading the derating curves and allowed mounting directions p. 7
- How overload protection behaves p. 8
- Reading the undervoltage alarm indicators p. 8
- Mounting with the supplied brackets p. 10
- Mounting on and removing from a DIN rail p. 13
- Making a plus and minus output from two supplies p. 13
- Series and parallel operation p. 14
Good to know
- Only 90-W and 100-W models can be run in series, and only 100-W models in parallel. p. 14
- Do not power the supply from an inverter output. p. 2
- DC input is outside the conditions of approval and safety standard conformance. p. 2
- A load with a built-in DC-DC converter can trip overload protection at startup so the supply does not start. p. 2
- Multiple units must not be mounted lined up vertically. p. 7
Questions this sheet answers
What is the output of the S82K-00312?
By the model legend, 003 means 3 W and 12 means +12 VDC; with no P prefix it has no power factor correction. p. 1
What input voltage does the S82K-00312 accept?
100 to 240 VAC, with a range of 85 to 264 VAC, at 50/60 Hz. p. 1, 2
What does the red DC LOW light mean on an S82K?
The output voltage has dropped. It first lights between 75% and 90% of the rated voltage at the output terminal. p. 6, 8
Can S82K 3 W supplies be wired in parallel or series?
No. The sheet allows parallel operation only for 100-W models and series operation only for 90-W and 100-W models. p. 14
Which noise filter fits the S82K-00312?
The S82Y-JF3-N, listed for 3- to 50-W models and ordered separately. p. 12
The whole text · 2 parts
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file