Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 1 of 2

Switch Mode Power Supply S82K (3/7.5/15/30/50/90/100-W Models), pages 1 to 8

Pages 1 to 8 of 15

The original document is the PDF (1.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron S82K-00312

Page 1

Switch Mode Power Supply

S82K (3/7.5/15/30/50/90/100-W Models) CSM_S82K_DS_E_3_1

Ultimate DIN-rail-mounting Power Supply with a Power Range of 3 to 100 W • EMI: EN 61204-3 class B • Input: 85 to 264 VAC (except 90-W and 100-W models) • Safety standards: UL 60950-1/508, cUL: CSA C22.2 No. 14 (Class 2: Per No. 223), cUR: CSA No. 60950-1, EN50178 (= VDE 0160) • Undervoltage alarm indication available for standard models.] • RoHS-compliant ! Refer to Safety Precautions for All Power Supplies.

Model Number Structure ■ Model Number Legend Note: Not all combinations are possible. Refer to List of Models in Ordering Information, below.

S82K 1 2 3 1. Power Factor Correction None: No P: Yes

2. Power Ratings 003: 3 W 050: 50 W 090: 90 W 007: 7.5 W 015: 15 W 100: 100 W 030: 30 W

3. Output Voltage 05: +5 VDC 24: +24 VDC 12: +12 VDC 27: ±12 VDC 15: +15 VDC 28: ±15 VDC

Ordering Information ■ List of Models Note: For details on normal stock models, contact your nearest OMRON representative. Power ratings 3W

Output voltage

Output current

50 W 90 W

5V 12 V 15 V 24 V 5V 12 V 15 V 24 V ±12 V ±15 V 5V 12 V 24 V 5V 12 V 24 V 24 V 24 V

0.6 A 0.25 A 0.2 A 0.13 A 1.5 A 0.6 A 0.5 A 0.3 A 0.3 A/0.2 A 0.2 A/0.2 A 2.5 A 1.2 A 0.6 A 5.0 A 2.5 A 1.3 A 2.1 A 3.75 A

100 W

24 V

4.2 A (See note 2.)

7.5 W

15 W

30 W

Output Single output

Function Configuration Undervoltage alarm indicator/output Yes

Models PFC No

Dual output Single output

No Yes No Yes

S82K-00305 S82K-00312 S82K-00315 S82K-00324 S82K-00705 S82K-00712 S82K-00715 S82K-00724 S82K-00727 S82K-00728 S82K-01505 S82K-01512 S82K-01524 S82K-03005 (See note 1.) S82K-03012 S82K-03024 S82K-05024 S82K-09024 S82K-P09024 S82K-10024 S82K-P10024

Note:1. The output capacity of the S82K-03005 is 25 W. 2. The output current for S82K-P10024 during parallel operation is 3.78 A.

1

Page 2

S82K

Specifications ■ Ratings/Characteristics Power ratings (See note 1.)

S82K Dual output Single output Item 3W 7.5 W 7.5 W 15 W 30 W Efficiency (typical) 60% min. (Varies depending 64% min. (Varies depending on specifications) 66% min. (Varies depending on specifications) on specifications) Input Voltage AC 100 to 240 VAC (85 to 264 VAC) (See note 2.) DC 90 to 350 VDC Not possible Frequency 50/60 Hz (47 to 450 Hz) Current 100-V input 0.15 A max. 0.25 A max. 0.45 A max. 0.9 A max. (See note 3.) 200-V input 0.25 A max. 0.6 A max. Power Factor --Harmonic current emissions --Leakage current 100-V input 0.5 mA max. (See note 3.) 200-V input 1 mA max. 25 A max. (for cold start at 25°C) Inrush current 100-V input 15 A max. (for cold start at 25°C) (See note 3.) 50 A max. (for cold start at 25°C) 200-V input 30 A max. (for cold start at 25°C) Noise filter Yes Out- Voltage Adjustment Range ±10% (with V. ADJ) (See note 5.) Not possible (See note 6.) ±10% (with V. ADJ) (−10% to 15% for S82K-03012/-03024) put (See note 5.) (See Ripple (See note 3.) 2% (p-p) max. note 4.) Input variation influence 0.5% max. (at 85 to 264 VAC input, 100% load) Load variation influence 1.5% max. (0 to 100% load) +V: 1.5% max. 1.5% max. (0 to 100% load) (rated input voltage) −V: 3% max. (0 to 100% load) Temperature variation influ- 0.05%/°C max. ence (See note 3.) Startup time 100 ms max. (up to 90% of output voltage at rated input and output)

Hold time (See note 3.) Addi- Overload protection tion- (See note 7.) al functions Overvoltage protection Undervoltage alarm indication Undervoltage alarm output Parallel operation Oth- Operating ambient temperaer ture Storage temperature Operating ambient humidity Dielectric strength

Detection current Insulation resistance Vibration resistance Shock resistance

Single output

20 ms min. 105% to 160% of rated load current (105% to 250% of rated load current for dual output models), gradual current/voltage 105% to 160% of rated load drop, automatic reset (See note 8.) current, gradual current increase, voltage drop intermittent operation, automatic reset No Yes (color: red) No No Refer to the derating curve in Engineering Data. (with no icing or condensation) −25 to 65°C (with no icing or condensation) 25% to 85% (Storage humidity: 25% to 90%) 3.0 kVAC for 1 min. (between all inputs and all outputs) 2.0 kVAC for 1 min. (between all inputs and PE terminals) 1.0 kVAC for 1 min. (between all outputs and PE terminals) 10 mA

20 mA

100 MΩ min. (between all outputs and all inputs, PE terminals) at 500 VDC 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions

300 m/s2, 3 times each in ±X, ±Y, ±Z directions Output indicator Yes (color: green) EMI Conducted Conforms to EN61204-3 EN55011 Class B and based on FCC Class B Emissions

EMS Approved standards

Weight

Radiated Emissions

Conforms to EN61204-3 EN55011 Class B

UL cUL cUR EN/VDE

Conforms to EN61204-3 High severity levels UL 508 (Listing; Class 2: Per UL1310), Class 2 (excluding Dual Output models), UL60950-1 CSA C22.2 No.14 (Class 2: Per No. 223, excluding Dual output models) CSA No. 60950-1 EN50178 (VDE0160) Based on VDE0160/P100 150 g max. 260 g max.

380 g max.

Note:1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the power supply may not start. Refer to Overload Protection on page 8 for details. 2. Use with DC voltage input is beyond the conditions of approval or conformance to applicable safety standards. (DC input possible with 15 W max. Use the 7.5-W single-output models under the load of 90% max. if the voltage range is between 90 and 110 VDC. Do not use the Inverter output for the Power Supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning. There is no polarity. 3. Defined with a 100% load and the rated input voltage (100 or 200 VAC.) 4. The output specification is defined at the power supply output terminals. 5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +10% of the voltage adjustment range. (+15% for S82K-03012/-03024) When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged. 6. The settings for the output voltage must be within the following range: +V: ±1% of the rated value −V: ±5% of the rated value 7. Refer to Overload Protection on page 8 for details. 8. When using the 7.5-W single-output models within the input voltage range between 90 and 110 VDC, the protection function will operate at a current of 95% to 160% of the rated load current.

2

Page 3

S82K

Power ratings (See note 1.) Item Efficiency (typical) Input Voltage (See note 2.) Frequency Current (See note 3.)

Output (See note 4.)

S82K 50 W 90 W 80% min. (Varies depending on specifications)

AC DC 100-V input 200-V input

Power Factor Harmonic current emissions Leakage current 100-V input (See note 3.) 200-V input Inrush current 100-V input (See note 3.) 200-V input Noise filter Voltage Adjustment Range Ripple (See note 3.) Input variation influence Load variation influence (rated input voltage) Temperature variation influence (See note 3.) Startup time

Hold time (See note 3.) Addi- Overload protection tion- (See note 6.) al functions Overvoltage protection Undervoltage alarm indication Undervoltage alarm output Parallel operation Oth- Operating ambient temperaer ture Storage temperature Operating ambient humidity Dielectric strength

Detection current Insulation resistance Vibration resistance Shock resistance

S82K-P Single output 100 W

90 W

100 W

100 to 240 VAC (85 to 264 VAC) 100 V (85 to 132 VAC)/200 V (170 to 264 VAC) Selectable Not possible 50/60 Hz (47 to 450 Hz) 50/60 Hz (47 to 63 Hz) 1.3 A max. 2.5 A max. 0.8 A max. 1.5 A max. --0.7 min. (at 200 VAC input, at rated output), 100 V: unlimited --Conforms to EN6100-3-2 (200-V only) 0.5 mA max. 1 mA max. 25 A max. (for cold start at 25°C) 50 A max. (for cold start at 25°C) Yes ±10% (with V. ADJ) (−10% to 15% for S82K-05024) (See note 5.) ±10% (with V. ADJ) (See note 5.) 2% (p-p) max. 0.5% max. (at 85 to 264 VAC in- 0.5% max. (at 85 to 132 VAC input /170 to 264 VAC input, 100% load) put, 100% load) 1.5% max. (0 to 100% load) 0.05%/°C max. 100 ms max. (up to 90% of out- 200 ms max. put voltage at rated input and output) 20 ms min. 105% to 160% of rated load 105% to 160% of rated load current, inverted L drop, automatic reset (See note 7.) current, gradual current increase, voltage drop intermittent operation, automatic reset No Yes (color: red) No Yes No Yes (up to 2 units.) Refer to the derating curve in Engineering Data. (with no icing or condensation)

No

Yes (up to 2 units.) (See note 8.)

−25 to 65°C (with no icing or condensation) 25% to 85% (Storage humidity: 25% to 90%) 3.0 kVAC for 1 min. (between all inputs and all outputs) 2.0 kVAC for 1 min. (between all inputs and PE terminals) 1.0 kVAC for 1 min. (between all outputs and PE terminals) 20 mA 100 MΩ min. (between all outputs and all inputs, PE terminals) at 500 VDC 10 to 55 Hz, 0.375-mm single amplitude for 2 h each in X, Y, and Z directions

300 m/s2, 3 times each in ±X, ±Y, ±Z directions 150 m/s2, 3 times each in ±X, ±Y, ±Z directions Output indicator Yes (color: green) EMI Conducted Conforms to EN61204-3 Conforms to EN61204-3 EN55011 Class B and based on FCC Class A Emissions EN55011 Class B and based on FCC Class B Radiated Conforms to EN61204-3 EN55011 Class B Emissions EMS Conforms to EN61204-3 High severity levels Approved stan- UL UL508 (Listing; Class 2: Per UL1310), Class 2 (excluding dual output models) (See note UL508 (Listing; Class 2: Per UL1310), Class 2 (excluding dards 9.), UL60950-1 dual output models) (See note 9.), UL60950-1 cUL CSA C22.2 No.14 (Class 2: Per No. 223, excluding dual output models) (See note 9.) CSA C22.2 No.14 (Class 2: Per No. 223, excluding dual output models) (See note 9.) cUR CSA No. 60950-1 CSA No. 60950-1 EN/VDE EN50178 (= VDE0160), EN60950-1 (= VDE0805 Teil 1) EN50178 (= VDE0160), EN60950-1 (= VDE0805 Teil 1) Based on VDE0106/P100 Based on VDE0106/P100 Weight 400 g max. 600 g max. 1000g max.

Note: 1. When a load is connected that has a built-in DC-DC converter, the overload protection may operate at startup and the power supply may not start. Refer to Overload Protection on page 8 for details. 2. Use with DC voltage input is beyond the conditions of approval or conformance to applicable safety standards. Do not use the Inverter output for the Power supply. Inverters with an output frequency of 50/60 Hz are available, but the rise in the internal temperature of the Power Supply may result in ignition or burning. There is no polarity. 3. Defined with a 100% load and the rated input voltage (100 or 200 VAC.) 4. The output specification is defined at the power output terminals. 5. If the output voltage adjuster (V. ADJ) is turned, the voltage will increase by more than +10% of the voltage adjustment range. (+15% for S82K-03012/-03024) When adjusting the output voltage, confirm the actual output voltage from the Power Supply and be sure that the load is not damaged. 6. Refer to Overload Protection on page 8 for details. 7. When using the 90-W model at an ambient temperature of 25°C or less, the overload protection function will operate at 101% to 111% of the rated output current. When using the 90-W model at an ambient temperature exceeding 25°C, the overload protection function will operate at 92% to 111% of the rated output current. 8. Parallel operation is set with the Parallel/Single Operation Selector. 9. To meet Class-2 requirements with the 100-W, either a fuse or circuit breaker that is UL listed or CSA certified, and rated at 4.2 A max. should be wired in series with the load to be connected to the Power Supply. Only then can the Power Supply output be considered as meeting Class 2.

3

Page 4

S82K

Connections ■ Block Diagrams S82K-003@@ (3 W) S82K-007@@ (7.5 W, Single Output) Fuse (1 A) +V

AC (L)

Noise filter −V

AC (N)

Inrush current Rectifier/ protection smoothing circuit circuit

Rectifier/ smoothing circuit

Undervoltage alarm indicator

Drive control circuit

Overload detection circuit

Detection

Photocoupler

S82K-007@@ (7.5 W, Dual Outputs) Fuse (1 A) −V

AC (L)

Noise filter AC (N)

Inrush current Rectifier/ protection smoothing circuit circuit

Rectifier/ 3-terminal smoothing REG circuit

+V

Undervoltage alarm indicator

Drive control circuit Rectifier/smoothing circuit Overload detection circuit

Detection

Photocoupler

S82K-015@@ (15 W) S82K-030@@ (30 W) S82K-05024 (50 W) Fuse (3 A) +V

AC (L)

Noise filter −V

AC (N)

Inrush current Rectifier/ smoothing protection circuit circuit

Rectifier/ smoothing circuit

Undervoltage alarm indicator

Drive control circuit

Overload detection circuit

Detection

Photocoupler

4

Page 5

S82K S82K-09024 (90 W) S82K-10024 (100 W)

Rectifier/ smoothing circuit

Fuse (5 A)

+V

AC (L)

Noise filter −V

AC (N)

Inrush current protection circuit

100 or 200 V Selectable terminals (See note.)

Rectifier/ smoothing circuit

Drive control circuit

Overload detection circuit

Undervoltage alarm indicator/output

Detection Photocoupler

Note: Use the short bar to short-circuit terminals 7 and 8 to select 100 to 120 VAC and remove the short bar to select 200 to 240 VAC.

S82K-P09024 (90 W) S82K-P10024 (100 W)

Harmonic current emission control Rectifier/ (By-passed for smoothing 100-V input) circuit

Fuse (5 A)

+V

AC (L)

Noise filter −V

AC (N)

100 or 200 V Selectable terminals (See note.)

Inrush current protection circuit

Rectifier/ smoothing circuit

Drive control circuit

Undervoltage alarm indicator/output

Overload detection circuit

Detection Photocoupler

Note: Use the short bar to short-circuit terminals 7 and 8 to select 100 to 120 VAC and remove the short bar to select 200 to 240 VAC.

5

Page 6

S82K

Construction and Nomenclature ■ Nomenclature S82K-003@@ S82K-007@@ (Single Output)

S82K-007@@ (Dual outputs) 1

1

S82K-015@@

1

1

5

5 7

5 7

7

6

6

2

2

3

3

2

S82K-030@@ S82K-05024

S82K-@09024 S82K-@10024

1

8

5

3

1

5

7

7

6

6

2

3 2

1. 2. 3. 4. 5. 6. 7. 8. 9.

3

DC Output Terminals (−V and +V): Connect the load lines to these terminals. AC Input Terminals (L and N): Connect the input lines to these terminals. Protective Earthing Terminals (PE): Connect a ground line to these terminals. Input Voltage Selector Terminals (VOLTAGE SELECT): Selects a 100 V or 200 V input voltage. Output Indicator (DC ON: Green): Lights while a Direct Current (DC) output is ON. Output Voltage Adjuster(V.ADJ): Use to adjust the voltage. Undervoltage Alarm Indicator Terminal (DC LOW: Red): Lights when there is a drop in the output voltage. Undervoltage Alarm Output Terminals (DC LOW): S82K-@09024/-@10024 only. Parallel/Single Operation Selector: Set to "PARALLEL" for parallel operation.

4

Parallel/Single Operation Selector (Only for S82KP10024)

9

6

Page 7

S82K

Engineering Data ■ Derating Curve (A: Standard mounting, B: Face-up mounting) 100-W Models with PFC (S82K-P10024)

Single-Unit Operation

Parallel Operation

Parallel Operation

Load (%)

Installation A

Installation B 65

Load (%)

100-W Models without PFC (S82K-10024)

Load (%)

3-/7.5-/15-/30-/50-/100-W Models

Installation A 90

Installation A 65

S82K-P10024: 85-VAC input

S82K-P10024: 85-VAC input Installation B

S82K-03005 Installation A

Installation B

Ambient temperature (°C)

Ambient temperature (°C)

Ambient temperature (°C)

Note: When using the 7.5-W single-output models within the input voltage range between 90 and 110 VDC, the load rate will become 90% or less.

90-W Models

Load (%)

Single-Unit Operation

S82K-P09024: 85-VAC input Installation A

65

Installation B

Ambient temperature (°C) Note: 1. The derating curve may vary depending on the installation conditions. 2. Multiple units cannot be installed in a configuration where they are lined up vertically. 3. Use the 7.5-W single-output models under the load of 90% max. if the voltage range is between 90 and 110 VDC. 4. The cold-start time will be longer when using S82K-P09024 or S82K-P10024 with an 85-VAC input.

■ Mounting Top

Top

Note: Installations other than (A) and (B) are not possible.

(A) Standard mounting

(B) Face-up mounting

7

Page 8

S82K ■ Overload Protection

30-/50 W Models Output voltage (V)

90-/100 W Models Output voltage (V)

3-/7.5/15 W Models Output voltage (V)

The Power Supply is provided with an overload protection function that protects the Power Supply from possible damage by overcurrent. When the output current rises above 105% min. of the rated current, the protection function is triggered, automatically decreasing the output voltage. When the output current falls within the rated range, the overload protection function is automatically cleared.

Intermittent operation

0

50

100 Output current (%)

0

50

100

0

Output current (%)

50

100 Output current (%)

The values shown in the above diagrams are for reference only. Note: 1. When connecting a load that has a built-in DC-DC converter, the overload protection function may operate during startup, thus preventing the Power Supply from starting. 2. Internal parts may occasionally deteriorate or be damaged if a short-circuited or other overcurrent state continues during operation. 3. When using the 7.5-W single-output models at the input voltage range of 90 to 110 VDC, the overload protection function will operate at 95% to 160% of the rated output current. 4. When using the 90-W model at an ambient temperature of 25°C or less, the overload protection function will operate at 101% to 111% of the rated output current. When using the 90-W model at an ambient temperature exceeding 25°C, the overload protection function will operate at 92% to 111% of the rated output current. 5. When using the 100-W model with PFC in parallel operation, operation is limited to a load ratio of 90% to 100% of the rated output current at 4.2 A.

When Using ± Output Models The +V output detects the total output power (+V output and −V output) to trigger the short-circuit protection against overcurrent. This protection varies depending on the −V output state. The −V output independently triggers the short-circuit protection.

■ Undervoltage Alarm Indicator and Output Function If the output voltage at the output terminal drops to 75% to 90% of the rated voltage, the red indicator of the S82K will be lit. In the case of the S82K-@09024/@10024, a voltage drop alarm will be output via the relay available in the models. Note: This function detects the voltage at the output terminal of the Power Supply. To check the precise output voltage, measure the voltage at the terminal of the load. Indicator

Voltage

Green lit:

DC ON

Red not lit:

DC LOW

If the voltage at the output terminal is more than 82% of the rated voltage and operation is normal, the green indicator will be lit and the red indicator will not be lit.

Green lit:

DC ON

Red lit:

If the voltage at the output terminal drops to below 82% (See note 1.) of the rated voltage, the red indicator will be lit. (See note 3.) DC LOW

Green not lit:

DC ON

Red not lit:

DC LOW

Operation of @09024/@10024’s output (See note 2.)

If the voltage at the output terminal approaches 0 V, both the green and red indicators will not be lit.

Note: 1. The more the voltage at the output terminal drops, the darker both the green and red indicators will be. 2. The relay contacts have a capacity of 0.1 A at 24 VDC. 3. The red indicator will actually first light at a voltage between 75% and 90% of the rated voltage at output terminal.

8