Page 1
Programmable Relay ZEN V2 Units Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Refer to “Warranty and Application Considerations” on page 36, and “Precautions for Safe Use” on page 34.
Even Broader Applications with Increased Functionality and Higher Precision • Increased functionality in a compact body (70 mm wide × 90 mm high). • Easy programming is available using the LCD and operation buttons. (See note 1.) • This single Unit easily provides relay, timer, counter, and time switch functions. • Expansion is easy with Expansion I/O Units, allowing up to 44 I/O points. (See note 2.) • Economy-type and Communications-type CPU Units have been added to series. • Improved Weekly Timers (See note 1.) Increased timing accuracy with a monthly deviation of ±15 s max. Multiple-day operation and pulse output operation have been added. • Select from two power supply options: 100 to 240 VAC or 12 to 24 VDC.
The information in this document applies to V2 Units. Refer to page 28 for details on differences with previous products.
Note: 1. Not supported for ZEN-@C2@@-@-V2 models. 2. When using CPU Units with 20 I/O points.
Features ■ Easy and Simple Programming for Automatic Small-scale Control Saves Space, Wiring, and Installation Steps
Easy Programming
• Versatile functionality in a compact body (70 mm wide × 90 mm high). • This single Unit easily provides relay, timer, counter, and time switch functions. Wiring work is greatly reduced because separate wiring is not required for devices such as timers and counters.
The LCD screen comes with 8 operation buttons on the front panel to enable programming in ladder view format. The LCD screen also has a backlight, making it easier to see when the ZEN is used in dark locations. Note: Not supported for ZEN-@C2@@-@-V2 models.
90 mm
70 mm
Programmable Relay ZEN V2 Units
1
Page 2
Flexible Expansion Enables Up to 44 I/O Points Up to three Expansion I/O Units can be connected if there are not enough I/O points. Expansion I/O Units are only 35 mm wide.
Support Software with Simulation Function • Programs can be easily written, saved, and monitored by personal computer. • Programs can be simulated on the personal computer without connecting to the ZEN.
Note: CPU Units with 10 I/O points can be expanded to 34 I/O points. Expansion I/O Units cannot be connected to Economy-type CPU Units.
Note: For notebook computers that do not have an RS-232C serial port, connect the computer to the ZEN by connecting an OMRON CS1W-CIF31 USB-Serial Conversion Cable to the ZEN-CIF01 Connecting Cable.
Other Versatile Functions • Use of a Memory Cassette makes it easy to copy and save programs. • Equipped with two analog input channels (CPU Units with DC power supply only). • Password function ensures security. (See note.) • Multi-language display in six languages (English, Japanese, German, French, Spanish, Italian). (See note.) • Display user-set messages or analog-converted values. (See note.) Note: Not supported for ZEN-@C2@@-@-V2 models.
■ Enhanced Features of V2 CPU Units Improved Weekly Timer and Calendar Timer Functions
RS-485 Communications Model Added to Series
Note: Not supported for ZEN-@C2@@-@-V2 models. • The time precision has been increased. Conventional model: 2-min difference/month ↓ -V2 models: ±15-s difference/month (at 25°C) • Multiple-day operation and pulse-output operation are now possible. • These improved functions are convenient for time-controlled applications such as lighting and air conditioning control.
Production line conditions can be remotely monitored by monitoring the ZEN control status.
Production line Office
More Precise Analog Input
Lighting control
Air conditioning control
Economy-type Added to the Series • Economy-type CPU Units with a more affordable price have been added to the series, although Expansion I/O Units cannot be added.
Conventional model: ± 10% FS → -V2 models: ± 1.5% FS DC power supply models are equipped with two analog inputs (0 to 10 V). There are four analog comparators. The increased precision makes it even easier to use the Unit in simple control applications with voltage, current, temperature, and other analog values.
8-digit Counter, 150-Hz Counter • An 8-digit counter and 8-digit comparator have been added. • The maximum count for DC power supply models is 150 Hz.
12 to 24 VDC Line Voltage Operation
Twin-timer Operation Added
Operation is now possible with 12 VDC.
Twin-timer operation allows you to set ON and OFF times separately, greatly simplifying intermittent operation.
Expansion I/O Units have been reduced to half-size (35 mm wide).
2
Programmable Relay ZEN V2 Units
Page 3
■ Series Configuration CPU Units Power supply voltage: 100 to 240 VAC, 12 to 24 VDC, Output: Relay, transistor output
With LCD display, operation buttons, and calendar/clock function
10 I/O points
20 I/O points
LED type
10 I/O points
20 I/O points
ZEN-10C2@
ZEN-20C2@ This CPU Unit has no LCD, operation buttons, or calendar/clock function.
Standard LCD type
Economy type
Communications type
Standard LCD type
Economy type
ZEN-10C1@
ZEN-10C3@
ZEN-10C4@
ZEN-20C1@
ZEN-20C3@
Expansion I/O Units cannot be connected.
RS-485 communications type.
(10 I/O points)
Expansion I/O Units cannot be connected.
Expansion I/O Units
Power Supply Unit
Support Software
Only 35-mm wide. 4 input, 4 output points
Same shape and design as ZEN. 24 VDC, 30 W
Allows easy programming and operation simulation.
Programmable Relay ZEN V2 Units
3
Page 4
Model Number Structure ■ Model Number Legend Note: This model number legend includes combinations that are not available. Please check “List of Models” for availability.
CPU Units ZEN-@C@@@-@-V2 1
2 3 4 5
1. Number of I/O points 10: 6 inputs and 4 outputs (See note.) 20: 12 inputs and 8 outputs 2. Type classifier 1: Standard LCD type with display 2: LED type without display 3: Economy type with display (Expansion I/O Units cannot be connected.) 4: Communications type with display
3. Input type A: AC input D: DC input 4. Output type R: Relay T: Transistor 5. Supply voltage A: AC power supply D: DC power supply
Note: The Communications-type CPU Unit has 6 inputs and 3 outputs.
Expansion I/O Units ZEN-8E1@@ 1 2 3 4 1. Number of I/O points 8: 4 inputs and 4 outputs 2. Unit version classifier E1: Can connect to V2 CPU Units (See note.)
3. Input type A: AC input D: DC input 4. Output type R: Relay T: Transistor
Note: Use a ZEN-8E@@/-4E@ to connect to pre-V1 and V1 CPU Units.
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. ZEN Operation Manual (Cat. No. Z211) ZEN Communications Manual (Cat. No. Z212) ZEN Support Software Operation Manual (Cat. No. Z184-E1-03) The PDF versions of these manuals can be downloaded from the following website. ZEN Website http://www.zen.omron.co.jp/eng/index.html
4
Programmable Relay ZEN V2 Units
Page 5
Ordering Information ■ List of Models CPU Units and Expansion I/O Units Unit
Name
CPU Units
Standard LCD type
No. of I/O points
LCD display
10
Yes
Power supply voltage 100 to 240 VAC
Inputs
6
12 to 24 VDC
Outputs
100 to 240 VAC
4
Relays
Buttons, calendar, and clock Yes
12 to 24 VDC
Analog input No
ZEN-10C1AR-A-V2
Yes
ZEN-10C1DR-D-V2
Transistors 20
100 to 240 VAC
12
12 to 24 VDC
100 to 240 VAC
8
ZEN-10C1DT-D-V2
Relays
No
12 to 24 VDC
Yes Transistors
LED type 10 without display (See note 1.)
No
100 to 240 VAC
6
12 to 24 VDC
100 to 240 VAC
4
Relays
No
12 to 24 VDC
100 to 240 VAC
12
12 to 24 VDC
No Yes
100 to 240V AC
8
10
Yes
Relays
12 to 24 VDC
Expansion I/O Units
6
12 to 24 VDC 20
100 to 240 VAC
100 to 240 VAC
4
Relays
12
100 to 240 VAC
8
Relays
12 to 24 VDC
100 to 240 VAC
6
12 to 24 VDC
100 to 240 VAC
3
ZEN-10C2AR-A-V2 ZEN-10C2DR-D-V2
No
ZEN-20C2AR-A-V2
Yes
ZEN-20C2DR-D-V2 ZEN-20C2DT-D-V2
Yes
12 to 24 VDC
12 to 24 VDC
Communica- 9 tions type ZEN Kit
100 to 240 VAC
ZEN-20C1DR-D-V2
ZEN-10C2DT-D-V2
Transistors Economy type (Expansion I/O Units cannot be connected)
ZEN-20C1AR-A-V2 ZEN-20C1DT-D-V2
Transistors
20
Model
Relays
12 to 24 VDC
No
ZEN-10C3AR-A-V2
Yes
ZEN-10C3DR-D-V2
No
ZEN-20C3AR-A-V2
Yes
ZEN-20C3DR-D-V2
No
ZEN-10C4AR-A-V2
Yes
ZEN-10C4DR-D-V2
Set containing CPU Unit (ZEN-10C1AR-A-V2), Connecting Cable, ZEN Support Software, and manual.
ZEN-STARTER01-V2
Set containing CPU Unit (ZEN-10C1DR-D-V2), Connecting Cable, ZEN Support Software, and manual.
ZEN-STARTER02-V2
8
ZEN-8E1AR (See notes 2, 3.)
---
100 to 240 VAC 12 to 24 VDC
4
100 to 240 VAC
4
Relays
---
12 to 24 VDC
ZEN-8E1DR (See note 2.)
---
Transistors
ZEN-8E1DT (See note 2.)
Note: 1. Programming is not possible using only the CPU in the LED-type CPU Unit. ZEN Support Software or a Memory Cassette is required. 2. Cannot be connected to pre-V1 and V1 CPU Units. 3. The ZEN-8E1AR cannot be connected to a CPU Unit with DC power supply.
Power Supply Unit Power ratings 30 W
Input voltage 100 to 240 VAC
Output voltage 24 VDC
Output current 1.3 A
Model ZEN-PA03024
Note: Refer to the ZEN-PA03024 Datasheet (Cat. No. L103) for detailed specifications.
Programmable Relay ZEN V2 Units
5
Page 6
Accessories (Order Separately) Name
Specifications
Memory Cassette EEPROM (for data security and copying)
Remarks
Model
Enables programs and parameter settings to be saved or copied to another ZEN. (See note 1.)
ZEN-ME01
LCD-type CPU Unit with LED-type CPU Unit without display (See note 2.) display (See note 3.)
Connecting Cable 2 m RS-232C (9-pin Dsub connector)
Transfer from ZEN to Memory
Supported
Not supported
Transfer from Memory Cassette to ZEN
Supported
Automatic transfer when power turned ON
Memory Cassette initialization
Supported
Not supported
---
ZEN-CIF01
Battery Unit
10 years min. Battery life Ladder programs and parameter settings are saved to the CPU Unit EEP-ROM ZEN-BAT01 but calendar, clock, and holding timer bits and holding timer/counter present (at 25°C) values are held by the capacitor. Therefore, if the power supply is interrupted for 2 days or more (at 25°C), this data will be reset. Use a Battery Unit for systems where the power supply may be interrupted for long periods.
ZEN Support Software
Runs on Windows 95, 98, Specifically designed for the ZEN (CD-ROM). 2000, ME, XP, or NT 4.0.
ZEN-SOFT01-V4
Note: 1. Memory Cassettes created using a CPU Unit can be read to other CPU Units, regardless of which model is used. Restrictions, apply, however, to the functions that can be used, depending on the CPU Unit version combination. For details, refer to “Memory Cassette and CPU Unit Combinations” on page 33. 2. Standard LCD-type, Economy-type, and Communications-type CPU Units (i.e., excluding ZEN-@C2@@-@-V2 models). 3. LED-type CPU Unit without display (i.e., ZEN-@C2@@-@-V2 models).
Mounting Accessories (Order Separately) Name
Specifications
Mounting Track
Model
50 cm (l) × 7.3 mm (t)
PFP-50N
1 m (l) × 7.3 mm (t)
PFP-100N
1 m (l) × 16 mm (t)
PFP-100N2
End Plate
PFP-M
Spacer
PFP-S
System Configuration Power Supply Unit
Expansion I/O Units
CPU Unit Battery Unit
Connecting Cable
Memory Cassette
Support Software
Note: 1. Up to 3 Expansion I/O Units can be connected to any type of CPU Unit except for Economy-type CPU Units. Expansion I/O Units with AC Inputs, however, cannot be connected to CPU Units with DC Power Supplies. 2. The Connecting Cable and Memory Cassette cannot be connected to the ZEN at the same time. 3. Programs cannot be written to LED-type CPU Units (i.e., ZEN-@C2@@-@-V2 models) without the ZEN Support Software or a Memory Cassette.
6
Programmable Relay ZEN V2 Units
Page 7
Specifications ■ Ratings Item
Specification ZEN-@C@AR-A-V2/ZEN-8E1AR
ZEN-@C@D@-D-V2/ZEN-8E1D@
Rated supply voltage
100 to 240 VAC, 50/60 Hz
12 to 24 VDC (DC ripple rate: 5% max.)
Operating voltage range
85 to 264 VAC
10.8 to 28.8 VDC
Power consumption
CPU Units without Expansion I/O Units • ZEN-10C1AR-A-V2/ZEN-10C2AR-A-V2/ ZEN-10C3AR-A-V2 100 V AC: 5 VA max. 240 V AC: 7 VA max. • ZEN-10C4AR-A-V2 100 V AC: 6 VA max. 240 V AC: 8 VA max. • ZEN-20C@AR-A-V2 100 V AC: 7 VA max. 240 V AC: 10 VA max.
CPU Units without Expansion I/O Units • ZEN-10C@DR-D-V2 12/24 V DC: 3 W max. (ZEN-10C3DR-D-V2: 2.8 W max.) • ZEN-10C@DT-D-V2 12/24 V DC: 2 W max. • ZEN-20C@DR-D-V2 12/24 V DC: 4 W max. • ZEN-20C@DT-D-V2 12/24 V DC: 2 W max. CPU Units with three Expansion I/O Units • ZEN-10C@DR-D-V2 12/24 V DC: 4 W max. • ZEN-10C@DT-D-V2 12/24 V DC: 3 W max. • ZEN-20C@DR-D-V2 12/24 V DC: 5 W max. • ZEN-20C@DT-D-V2 12/24 V DC: 3 W max.
CPU Units with three Expansion I/O Units • ZEN-10C1AR-A-V2/ZEN-10C2AR-A-V2 100 V AC: 6 VA max. 240 V AC: 8 VA max. • ZEN-10C4AR-A-V2 100 V AC: 7 VA max. 240 V AC: 9 VA max. • ZEN-20C@AR-A-V2 100 V AC: 8 VA max. 240 V AC: 11 VA max.
Expansion I/O Units • ZEN-8E1DR 12/24 V DC: 2 W max.
Expansion I/O Units • ZEN-8E1AR 100 V AC: 3 VA max. 240 V AC: 4 VA max.
ZEN-10C@D@-D-V2: 30 A max. ZEN-20C@D@-D-V2: 30 A max. ZEN-8E1DR: 15 A max.
Inrush current
ZEN-10C@AR-A-V2: 4.5 A max. ZEN-20C@AR-A-V2: 4.5 A max. ZEN-8E1AR: 4 A max.
Ambient temperature
0 to 55°C (−25 to 55°C for ZEN-@C2@@-@-V2 models)
Ambient storage temperature −20 to 75°C (−40 to 75°C for ZEN-@C2@@-@-V2 models) Ambient humidity
10% to 90% (with no condensation)
Ambient conditions
No corrosive gases
Mounting method
Surface mounting, DIN track mounting (standard (vertical) installation and horizontal installation) (See notes 1 and 2.)
Terminal block
Solid-line terminal block (use solid wire or fine-stranded wire)
Terminal screw tightening torque
0.565 to 0.6 N·m (5 to 5.3 in-lb)
Degree of protection
IP20 (Mounted inside a control panel)
Note: 1. Can be mounted to 35-mm DIN Track. 2. Standard (Vertical) installation Horizontal installation
Programmable Relay ZEN V2 Units
7
Page 8
■ Characteristics Item
Specification
Control method
Stored program control
I/O control method
Cyclic scan
Programming language
Ladder diagram
Program capacity
96 lines (3 input conditions and 1 output per line)
Max. No. of control I/O points
44 points (See note 1.) CPU Units with 20 I/O points: 12 inputs and 8 outputs Expansion I/O Units: 4 inputs and 4 outputs each, up to 3 Units.
LCD display (See note 2.)
12 characters × 4 lines, with backlight
Operation buttons (See note 2.) 8 (4 cursor buttons and 4 operation buttons) User program backup
Internal EEPROM, Memory Cassette (optional)
Power interruption hold
Internal holding bit status, holding timer/counter present values, calendar and clock (year, month, day of month, day of week, time) • Super capacitor backup time: 2 days min. (25°C) • Life of optional battery: 10 years min. (25°C)
Calendar and clock function (See note 2.)
Accuracy: ±15 s/month (at 25°C)
Timer accuracy
0.01 s unit: −0.05% −10 ms max. (rate for set value) min/s unit: −0.05% −1 s max. (rate for set value) h/min unit: −0.05% −1 min max. (rate for set value)
Maximum counting speed
150 Hz: 8-Digit counter (F) set to high-speed operations (CPU Units with DC power supplies only) (The counting speed may be less than 150 Hz depending on the cycle time of the program. See page 21.)
Insulation resistance
20 MΩ (at 500 VDC) min.: Between power supply terminals and all output terminals. Between terminals of different output circuits. Between all terminals of CPU Unit and all terminals of Expansion I/O Unit.
Insulation
• Reinforced insulation Between power supply or input terminals and output terminals. Between terminals of different output circuits. Between all terminals of CPU Unit and all terminals of Expansion I/O Unit. • No separation Between power supply and input terminals of the same unit. Between power supply terminals of CPU Unit and computer connector, Battery Unit connector, or all Expansion Unit connectors (all interfaces are live parts).
Dielectric strength
2,300 VAC, 50/60 Hz for 1 min (leakage current 1 mA max.): Between power supply terminals and all output terminals. Between terminals of different output circuit. Between all terminals of CPU Unit and all terminals of Expansion I/O Unit.
Vibration resistance
Conforms to IEC60068-2-6, 5 to 9 Hz with 3.5-mm single amplitude, 9 to 150 Hz acceleration 9.8 m/s2, 10 sweeps each in X, Y, and Z directions (1 octave/min)
Shock resistance
Conforms to IEC60068-2-27, 147 m/s2, 3 times each in X, Y, and Z directions.
Weight
CPU Unit with 10 I/O points: Approx. 300 g max. CPU Unit with 20 I/O points: Approx. 350 g max. Expansion I/O Unit: Approx. 120 g max.
Note: 1. Up to 34 points for CPU Units with 10 I/O points. With Communications-type CPU Units, however, the CPU Unit has 6 inputs and 3 outputs, for a maximum of 33 I/O points. 2. Not provided for LED-type CPU Unit without display (i.e., ZEN-@C2@@-@-V2 models).
■ Communications Specifications (Communications-type CPU Units) Item
ZEN-10C4@R-@-V2
Communications
RS-485 (two-wire, half duplex)
Synchronization method
Start-stop synchronization
Baud rate
4800, 9600, or 19200 bps
Transmission code
ASCII
Data bit length
7 or 8 bits
Stop bit length
1 or 2 bits
Error detection
Vertical parity (none, even, odd), Block check character (BCC)
Flow control
None
Interface
RS-485
Retry function
None
Node number
0 to 99 (default: 1), XX (broadcasting)
8
Programmable Relay ZEN V2 Units
Page 9
■ Approved Standards Item
Specification
Safety standards cULus: UL508/CSA C22.2 No.142 Class I Div2 Conforms to EN/IEC 61131-2 clause 11, excluding 11.7.2.2 (Overvoltage category 2 and Pollution degree II conforms to IEC 60664-1)
EMC (See note.)
Radiation Field Emission Noise Terminal Voltage Emission
CISPR11 CISPR11
Electrostatic Discharge Immunity Electromagnetic Field Immunity Electrical Fast Transient/Burst Immunity
IEC61000-4-2 IEC61000-4-3 IEC61000-4-4
Class A, Group 1 Class A, Group 1
In air: 8 kV, In contact: 6 kV 10 V/m Power line AC I/O: 2 kV DC I/O: 1 kV Surge Immunity IEC61000-4-5 Normal Noise AC power supply, AC I/O: 1 kV DC power supply, DC I/O: 0.5 kV Common Noise AC power supply, AC I/O: 2 kV DC power supply: 1 kV DC I/O: 0.5 kV Immunity to Conducted Disturbances Induced by Radio-frequency Fields IEC61000-4-6 3V Momentary Power Interruption Immunity IEC61131-2 CPU Units with AC Power Supplies: 10 ms max. CPU Units with DC Power Supplies: 2 ms max. (level: PS1) Note: EMC conforms to EN 61131-2 clause 8 except in the following cases. • When Expansion I/O Units with DC inputs are connected to a CPU Unit with an AC power supply, the burst immunity between power supplies will be 1 kv. • When the signal wire for transistor outputs exceeds 10 m, the surge immunity of DC output signal lines will not conform.
■ Input Specifications CPU Units AC Inputs (Not Isolated) Item Input voltage
Specifications
Input impedance
680 kΩ
Input current
0.15 mA/100 VAC, 0.35 mA/240 VAC
ON voltage
80 VAC min.
OFF voltage
25 VAC max.
ON response time
50 ms or 70 ms at 100 VAC (See note.) 100 ms or 120 ms at 240 VAC (See note.)
OFF response time
Circuit drawing
100 to 240 VAC +10%, −15%, 50/60 Hz IN 330 kΩ 300 kΩ IN 51 kΩ
Internal circuit
100 to 240 VAC N L
Note: Can be selected using the filter settings.
DC Inputs: I0 to I3 for Units with 10 I/O points, I0 to I9 for Units with 20 I/O Points (Not Isolated) Item Input voltage
Specifications
Circuit drawing
12 to 24 VDC +20%, −10%
Input impedance
5.3 kΩ
Input current
4.5 mA (typ.)/24 VDC
ON voltage
8 VDC min.
OFF voltage
5 VDC max.
ON response time
15 ms or 50 ms (See note.)
IN 5.1 kΩ 1.8 kΩ 12 to 24 VDC
IN Internal circuit COM
OFF response time Note: Can be selected using the input filter settings, except when I0 is being used for an 8-digit counter with a high-speed input.
Programmable Relay ZEN V2 Units
9
Page 10
DC Inputs: I4 and I5 for Units with 10 I/O points, Ia and Ib for Units with 20 I/O Points (Not Isolated) Item
Specifications
Input current
PNP: NPN:
4.3 mA (typ.)/24 VDC 4.6 mA (typ.)/24 VDC
ON voltage
8 VDC min.
OFF voltage
3 VDC max.
ON response time
15 ms or 50 ms (See note.)
OFF response time Input range
0 to 10 V
External input impedance
100 kΩ min.
150 kΩ IN
27 kΩ
+
47 kΩ 220 kΩ
−
COM 47 kΩ
12 to 24 VDC
Resolution
0.1 V (1/100 FS)
Accuracy
±1.5% FS (at ambient operating temperature within rated range)
6.2 kΩ
Internal circuit
NPN:
5.5 kΩ/14 VDC min. 100 kΩ/14 VDC max. 5.2 kΩ
PNP:
Analog voltage output device
Input impedance
Analog Inputs
Circuit drawing
12 to 24 VDC +20%, −10%
DC Inputs Input voltage
5.6 kΩ
AD conversion data 0 to 10.5 V (in increments of 0.1 V) Note: Can be selected using the input filter settings.
Expansion I/O Units AC Inputs (Not Isolated) Specifications
Circuit drawing
100 to 240 VAC +10%, −15%, 50/60 Hz
Input impedance
680 kΩ
Input current
0.15 mA/100 VAC, 0.35 mA/240 VAC
IN
ON voltage
80 VAC min.
IN
OFF voltage
25 VAC max.
ON response time
50 ms or 70 ms at 100 VAC (See note.) 100 ms or 120 ms at 240 VAC (See note.)
Off response time
Internal circuit
Item Input voltage
330 kΩ 300 kΩ 51 kΩ
100 to 240 VAC N L
Note: Can be selected using the input filter settings.
DC Inputs (ZEN-8E1DR: Not Isolated, ZEN-8E1DT: Photocoupler Isolated) Item
Specifications
Circuit drawing
Input voltage
12 to 24 VDC +20%, −10%
Input impedance
6.5 kΩ
IN
Input current
3.7 mA (typ.)/24 VDC
IN
ON voltage
8 VDC min.
OFF voltage
5 VDC max.
ON response time
15 ms or 50 ms (See note 1.)
OFF response time Note: 1. Can be selected using the input filter settings. 2. The ZEN-8E1DT has no +/- terminals. There is no need to supply power.
10
Programmable Relay ZEN V2 Units
± 12 to 24 VDC
COM
6.2 kΩ (See note 2.)
1.8 kΩ Internal circuit