For the Omron ZEN-10C1DR-D-V2

Page 1

Programmable Relay ZEN V2 Units Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Refer to “Warranty and Application Considerations” on page 36, and “Precautions for Safe Use” on page 34.

Even Broader Applications with Increased Functionality and Higher Precision • Increased functionality in a compact body (70 mm wide × 90 mm high). • Easy programming is available using the LCD and operation buttons. (See note 1.) • This single Unit easily provides relay, timer, counter, and time switch functions. • Expansion is easy with Expansion I/O Units, allowing up to 44 I/O points. (See note 2.) • Economy-type and Communications-type CPU Units have been added to series. • Improved Weekly Timers (See note 1.) Increased timing accuracy with a monthly deviation of ±15 s max. Multiple-day operation and pulse output operation have been added. • Select from two power supply options: 100 to 240 VAC or 12 to 24 VDC.

The information in this document applies to V2 Units. Refer to page 28 for details on differences with previous products.

Note: 1. Not supported for ZEN-@C2@@-@-V2 models. 2. When using CPU Units with 20 I/O points.

Features ■ Easy and Simple Programming for Automatic Small-scale Control Saves Space, Wiring, and Installation Steps

Easy Programming

• Versatile functionality in a compact body (70 mm wide × 90 mm high). • This single Unit easily provides relay, timer, counter, and time switch functions. Wiring work is greatly reduced because separate wiring is not required for devices such as timers and counters.

The LCD screen comes with 8 operation buttons on the front panel to enable programming in ladder view format. The LCD screen also has a backlight, making it easier to see when the ZEN is used in dark locations. Note: Not supported for ZEN-@C2@@-@-V2 models.

90 mm

70 mm

Programmable Relay ZEN V2 Units

1

Page 2

Flexible Expansion Enables Up to 44 I/O Points Up to three Expansion I/O Units can be connected if there are not enough I/O points. Expansion I/O Units are only 35 mm wide.

Support Software with Simulation Function • Programs can be easily written, saved, and monitored by personal computer. • Programs can be simulated on the personal computer without connecting to the ZEN.

Note: CPU Units with 10 I/O points can be expanded to 34 I/O points. Expansion I/O Units cannot be connected to Economy-type CPU Units.

Note: For notebook computers that do not have an RS-232C serial port, connect the computer to the ZEN by connecting an OMRON CS1W-CIF31 USB-Serial Conversion Cable to the ZEN-CIF01 Connecting Cable.

Other Versatile Functions • Use of a Memory Cassette makes it easy to copy and save programs. • Equipped with two analog input channels (CPU Units with DC power supply only). • Password function ensures security. (See note.) • Multi-language display in six languages (English, Japanese, German, French, Spanish, Italian). (See note.) • Display user-set messages or analog-converted values. (See note.) Note: Not supported for ZEN-@C2@@-@-V2 models.

■ Enhanced Features of V2 CPU Units Improved Weekly Timer and Calendar Timer Functions

RS-485 Communications Model Added to Series

Note: Not supported for ZEN-@C2@@-@-V2 models. • The time precision has been increased. Conventional model: 2-min difference/month ↓ -V2 models: ±15-s difference/month (at 25°C) • Multiple-day operation and pulse-output operation are now possible. • These improved functions are convenient for time-controlled applications such as lighting and air conditioning control.

Production line conditions can be remotely monitored by monitoring the ZEN control status.

Production line Office

More Precise Analog Input

Lighting control

Air conditioning control

Economy-type Added to the Series • Economy-type CPU Units with a more affordable price have been added to the series, although Expansion I/O Units cannot be added.

Conventional model: ± 10% FS → -V2 models: ± 1.5% FS DC power supply models are equipped with two analog inputs (0 to 10 V). There are four analog comparators. The increased precision makes it even easier to use the Unit in simple control applications with voltage, current, temperature, and other analog values.

8-digit Counter, 150-Hz Counter • An 8-digit counter and 8-digit comparator have been added. • The maximum count for DC power supply models is 150 Hz.

12 to 24 VDC Line Voltage Operation

Twin-timer Operation Added

Operation is now possible with 12 VDC.

Twin-timer operation allows you to set ON and OFF times separately, greatly simplifying intermittent operation.

Expansion I/O Units have been reduced to half-size (35 mm wide).

2

Programmable Relay ZEN V2 Units

Page 3

■ Series Configuration CPU Units Power supply voltage: 100 to 240 VAC, 12 to 24 VDC, Output: Relay, transistor output

With LCD display, operation buttons, and calendar/clock function

10 I/O points

20 I/O points

LED type

10 I/O points

20 I/O points

ZEN-10C2@

ZEN-20C2@ This CPU Unit has no LCD, operation buttons, or calendar/clock function.

Standard LCD type

Economy type

Communications type

Standard LCD type

Economy type

ZEN-10C1@

ZEN-10C3@

ZEN-10C4@

ZEN-20C1@

ZEN-20C3@

Expansion I/O Units cannot be connected.

RS-485 communications type.

(10 I/O points)

Expansion I/O Units cannot be connected.

Expansion I/O Units

Power Supply Unit

Support Software

Only 35-mm wide. 4 input, 4 output points

Same shape and design as ZEN. 24 VDC, 30 W

Allows easy programming and operation simulation.

Programmable Relay ZEN V2 Units

3

Page 4

Model Number Structure ■ Model Number Legend Note: This model number legend includes combinations that are not available. Please check “List of Models” for availability.

CPU Units ZEN-@C@@@-@-V2 1

2 3 4 5

1. Number of I/O points 10: 6 inputs and 4 outputs (See note.) 20: 12 inputs and 8 outputs 2. Type classifier 1: Standard LCD type with display 2: LED type without display 3: Economy type with display (Expansion I/O Units cannot be connected.) 4: Communications type with display

3. Input type A: AC input D: DC input 4. Output type R: Relay T: Transistor 5. Supply voltage A: AC power supply D: DC power supply

Note: The Communications-type CPU Unit has 6 inputs and 3 outputs.

Expansion I/O Units ZEN-8E1@@ 1 2 3 4 1. Number of I/O points 8: 4 inputs and 4 outputs 2. Unit version classifier E1: Can connect to V2 CPU Units (See note.)

3. Input type A: AC input D: DC input 4. Output type R: Relay T: Transistor

Note: Use a ZEN-8E@@/-4E@ to connect to pre-V1 and V1 CPU Units.

This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. ZEN Operation Manual (Cat. No. Z211) ZEN Communications Manual (Cat. No. Z212) ZEN Support Software Operation Manual (Cat. No. Z184-E1-03) The PDF versions of these manuals can be downloaded from the following website. ZEN Website http://www.zen.omron.co.jp/eng/index.html

4

Programmable Relay ZEN V2 Units

Page 5

Ordering Information ■ List of Models CPU Units and Expansion I/O Units Unit

Name

CPU Units

Standard LCD type

No. of I/O points

LCD display

10

Yes

Power supply voltage 100 to 240 VAC

Inputs

6

12 to 24 VDC

Outputs

100 to 240 VAC

4

Relays

Buttons, calendar, and clock Yes

12 to 24 VDC

Analog input No

ZEN-10C1AR-A-V2

Yes

ZEN-10C1DR-D-V2

Transistors 20

100 to 240 VAC

12

12 to 24 VDC

100 to 240 VAC

8

ZEN-10C1DT-D-V2

Relays

No

12 to 24 VDC

Yes Transistors

LED type 10 without display (See note 1.)

No

100 to 240 VAC

6

12 to 24 VDC

100 to 240 VAC

4

Relays

No

12 to 24 VDC

100 to 240 VAC

12

12 to 24 VDC

No Yes

100 to 240V AC

8

10

Yes

Relays

12 to 24 VDC

Expansion I/O Units

6

12 to 24 VDC 20

100 to 240 VAC

100 to 240 VAC

4

Relays

12

100 to 240 VAC

8

Relays

12 to 24 VDC

100 to 240 VAC

6

12 to 24 VDC

100 to 240 VAC

3

ZEN-10C2AR-A-V2 ZEN-10C2DR-D-V2

No

ZEN-20C2AR-A-V2

Yes

ZEN-20C2DR-D-V2 ZEN-20C2DT-D-V2

Yes

12 to 24 VDC

12 to 24 VDC

Communica- 9 tions type ZEN Kit

100 to 240 VAC

ZEN-20C1DR-D-V2

ZEN-10C2DT-D-V2

Transistors Economy type (Expansion I/O Units cannot be connected)

ZEN-20C1AR-A-V2 ZEN-20C1DT-D-V2

Transistors

20

Model

Relays

12 to 24 VDC

No

ZEN-10C3AR-A-V2

Yes

ZEN-10C3DR-D-V2

No

ZEN-20C3AR-A-V2

Yes

ZEN-20C3DR-D-V2

No

ZEN-10C4AR-A-V2

Yes

ZEN-10C4DR-D-V2

Set containing CPU Unit (ZEN-10C1AR-A-V2), Connecting Cable, ZEN Support Software, and manual.

ZEN-STARTER01-V2

Set containing CPU Unit (ZEN-10C1DR-D-V2), Connecting Cable, ZEN Support Software, and manual.

ZEN-STARTER02-V2

8

ZEN-8E1AR (See notes 2, 3.)

---

100 to 240 VAC 12 to 24 VDC

4

100 to 240 VAC

4

Relays

---

12 to 24 VDC

ZEN-8E1DR (See note 2.)

---

Transistors

ZEN-8E1DT (See note 2.)

Note: 1. Programming is not possible using only the CPU in the LED-type CPU Unit. ZEN Support Software or a Memory Cassette is required. 2. Cannot be connected to pre-V1 and V1 CPU Units. 3. The ZEN-8E1AR cannot be connected to a CPU Unit with DC power supply.

Power Supply Unit Power ratings 30 W

Input voltage 100 to 240 VAC

Output voltage 24 VDC

Output current 1.3 A

Model ZEN-PA03024

Note: Refer to the ZEN-PA03024 Datasheet (Cat. No. L103) for detailed specifications.

Programmable Relay ZEN V2 Units

5

Page 6

Accessories (Order Separately) Name

Specifications

Memory Cassette EEPROM (for data security and copying)

Remarks

Model

Enables programs and parameter settings to be saved or copied to another ZEN. (See note 1.)

ZEN-ME01

LCD-type CPU Unit with LED-type CPU Unit without display (See note 2.) display (See note 3.)

Connecting Cable 2 m RS-232C (9-pin Dsub connector)

Transfer from ZEN to Memory

Supported

Not supported

Transfer from Memory Cassette to ZEN

Supported

Automatic transfer when power turned ON

Memory Cassette initialization

Supported

Not supported

---

ZEN-CIF01

Battery Unit

10 years min. Battery life Ladder programs and parameter settings are saved to the CPU Unit EEP-ROM ZEN-BAT01 but calendar, clock, and holding timer bits and holding timer/counter present (at 25°C) values are held by the capacitor. Therefore, if the power supply is interrupted for 2 days or more (at 25°C), this data will be reset. Use a Battery Unit for systems where the power supply may be interrupted for long periods.

ZEN Support Software

Runs on Windows 95, 98, Specifically designed for the ZEN (CD-ROM). 2000, ME, XP, or NT 4.0.

ZEN-SOFT01-V4

Note: 1. Memory Cassettes created using a CPU Unit can be read to other CPU Units, regardless of which model is used. Restrictions, apply, however, to the functions that can be used, depending on the CPU Unit version combination. For details, refer to “Memory Cassette and CPU Unit Combinations” on page 33. 2. Standard LCD-type, Economy-type, and Communications-type CPU Units (i.e., excluding ZEN-@C2@@-@-V2 models). 3. LED-type CPU Unit without display (i.e., ZEN-@C2@@-@-V2 models).

Mounting Accessories (Order Separately) Name

Specifications

Mounting Track

Model

50 cm (l) × 7.3 mm (t)

PFP-50N

1 m (l) × 7.3 mm (t)

PFP-100N

1 m (l) × 16 mm (t)

PFP-100N2

End Plate

PFP-M

Spacer

PFP-S

System Configuration Power Supply Unit

Expansion I/O Units

CPU Unit Battery Unit

Connecting Cable

Memory Cassette

Support Software

Note: 1. Up to 3 Expansion I/O Units can be connected to any type of CPU Unit except for Economy-type CPU Units. Expansion I/O Units with AC Inputs, however, cannot be connected to CPU Units with DC Power Supplies. 2. The Connecting Cable and Memory Cassette cannot be connected to the ZEN at the same time. 3. Programs cannot be written to LED-type CPU Units (i.e., ZEN-@C2@@-@-V2 models) without the ZEN Support Software or a Memory Cassette.

6

Programmable Relay ZEN V2 Units

Page 7

Specifications ■ Ratings Item

Specification ZEN-@C@AR-A-V2/ZEN-8E1AR

ZEN-@C@D@-D-V2/ZEN-8E1D@

Rated supply voltage

100 to 240 VAC, 50/60 Hz

12 to 24 VDC (DC ripple rate: 5% max.)

Operating voltage range

85 to 264 VAC

10.8 to 28.8 VDC

Power consumption

CPU Units without Expansion I/O Units • ZEN-10C1AR-A-V2/ZEN-10C2AR-A-V2/ ZEN-10C3AR-A-V2 100 V AC: 5 VA max. 240 V AC: 7 VA max. • ZEN-10C4AR-A-V2 100 V AC: 6 VA max. 240 V AC: 8 VA max. • ZEN-20C@AR-A-V2 100 V AC: 7 VA max. 240 V AC: 10 VA max.

CPU Units without Expansion I/O Units • ZEN-10C@DR-D-V2 12/24 V DC: 3 W max. (ZEN-10C3DR-D-V2: 2.8 W max.) • ZEN-10C@DT-D-V2 12/24 V DC: 2 W max. • ZEN-20C@DR-D-V2 12/24 V DC: 4 W max. • ZEN-20C@DT-D-V2 12/24 V DC: 2 W max. CPU Units with three Expansion I/O Units • ZEN-10C@DR-D-V2 12/24 V DC: 4 W max. • ZEN-10C@DT-D-V2 12/24 V DC: 3 W max. • ZEN-20C@DR-D-V2 12/24 V DC: 5 W max. • ZEN-20C@DT-D-V2 12/24 V DC: 3 W max.

CPU Units with three Expansion I/O Units • ZEN-10C1AR-A-V2/ZEN-10C2AR-A-V2 100 V AC: 6 VA max. 240 V AC: 8 VA max. • ZEN-10C4AR-A-V2 100 V AC: 7 VA max. 240 V AC: 9 VA max. • ZEN-20C@AR-A-V2 100 V AC: 8 VA max. 240 V AC: 11 VA max.

Expansion I/O Units • ZEN-8E1DR 12/24 V DC: 2 W max.

Expansion I/O Units • ZEN-8E1AR 100 V AC: 3 VA max. 240 V AC: 4 VA max.

ZEN-10C@D@-D-V2: 30 A max. ZEN-20C@D@-D-V2: 30 A max. ZEN-8E1DR: 15 A max.

Inrush current

ZEN-10C@AR-A-V2: 4.5 A max. ZEN-20C@AR-A-V2: 4.5 A max. ZEN-8E1AR: 4 A max.

Ambient temperature

0 to 55°C (−25 to 55°C for ZEN-@C2@@-@-V2 models)

Ambient storage temperature −20 to 75°C (−40 to 75°C for ZEN-@C2@@-@-V2 models) Ambient humidity

10% to 90% (with no condensation)

Ambient conditions

No corrosive gases

Mounting method

Surface mounting, DIN track mounting (standard (vertical) installation and horizontal installation) (See notes 1 and 2.)

Terminal block

Solid-line terminal block (use solid wire or fine-stranded wire)

Terminal screw tightening torque

0.565 to 0.6 N·m (5 to 5.3 in-lb)

Degree of protection

IP20 (Mounted inside a control panel)

Note: 1. Can be mounted to 35-mm DIN Track. 2. Standard (Vertical) installation Horizontal installation

Programmable Relay ZEN V2 Units

7

Page 8

■ Characteristics Item

Specification

Control method

Stored program control

I/O control method

Cyclic scan

Programming language

Ladder diagram

Program capacity

96 lines (3 input conditions and 1 output per line)

Max. No. of control I/O points

44 points (See note 1.) CPU Units with 20 I/O points: 12 inputs and 8 outputs Expansion I/O Units: 4 inputs and 4 outputs each, up to 3 Units.

LCD display (See note 2.)

12 characters × 4 lines, with backlight

Operation buttons (See note 2.) 8 (4 cursor buttons and 4 operation buttons) User program backup

Internal EEPROM, Memory Cassette (optional)

Power interruption hold

Internal holding bit status, holding timer/counter present values, calendar and clock (year, month, day of month, day of week, time) • Super capacitor backup time: 2 days min. (25°C) • Life of optional battery: 10 years min. (25°C)

Calendar and clock function (See note 2.)

Accuracy: ±15 s/month (at 25°C)

Timer accuracy

0.01 s unit: −0.05% −10 ms max. (rate for set value) min/s unit: −0.05% −1 s max. (rate for set value) h/min unit: −0.05% −1 min max. (rate for set value)

Maximum counting speed

150 Hz: 8-Digit counter (F) set to high-speed operations (CPU Units with DC power supplies only) (The counting speed may be less than 150 Hz depending on the cycle time of the program. See page 21.)

Insulation resistance

20 MΩ (at 500 VDC) min.: Between power supply terminals and all output terminals. Between terminals of different output circuits. Between all terminals of CPU Unit and all terminals of Expansion I/O Unit.

Insulation

• Reinforced insulation Between power supply or input terminals and output terminals. Between terminals of different output circuits. Between all terminals of CPU Unit and all terminals of Expansion I/O Unit. • No separation Between power supply and input terminals of the same unit. Between power supply terminals of CPU Unit and computer connector, Battery Unit connector, or all Expansion Unit connectors (all interfaces are live parts).

Dielectric strength

2,300 VAC, 50/60 Hz for 1 min (leakage current 1 mA max.): Between power supply terminals and all output terminals. Between terminals of different output circuit. Between all terminals of CPU Unit and all terminals of Expansion I/O Unit.

Vibration resistance

Conforms to IEC60068-2-6, 5 to 9 Hz with 3.5-mm single amplitude, 9 to 150 Hz acceleration 9.8 m/s2, 10 sweeps each in X, Y, and Z directions (1 octave/min)

Shock resistance

Conforms to IEC60068-2-27, 147 m/s2, 3 times each in X, Y, and Z directions.

Weight

CPU Unit with 10 I/O points: Approx. 300 g max. CPU Unit with 20 I/O points: Approx. 350 g max. Expansion I/O Unit: Approx. 120 g max.

Note: 1. Up to 34 points for CPU Units with 10 I/O points. With Communications-type CPU Units, however, the CPU Unit has 6 inputs and 3 outputs, for a maximum of 33 I/O points. 2. Not provided for LED-type CPU Unit without display (i.e., ZEN-@C2@@-@-V2 models).

■ Communications Specifications (Communications-type CPU Units) Item

ZEN-10C4@R-@-V2

Communications

RS-485 (two-wire, half duplex)

Synchronization method

Start-stop synchronization

Baud rate

4800, 9600, or 19200 bps

Transmission code

ASCII

Data bit length

7 or 8 bits

Stop bit length

1 or 2 bits

Error detection

Vertical parity (none, even, odd), Block check character (BCC)

Flow control

None

Interface

RS-485

Retry function

None

Node number

0 to 99 (default: 1), XX (broadcasting)

8

Programmable Relay ZEN V2 Units

Page 9

■ Approved Standards Item

Specification

Safety standards cULus: UL508/CSA C22.2 No.142 Class I Div2 Conforms to EN/IEC 61131-2 clause 11, excluding 11.7.2.2 (Overvoltage category 2 and Pollution degree II conforms to IEC 60664-1)

EMC (See note.)

Radiation Field Emission Noise Terminal Voltage Emission

CISPR11 CISPR11

Electrostatic Discharge Immunity Electromagnetic Field Immunity Electrical Fast Transient/Burst Immunity

IEC61000-4-2 IEC61000-4-3 IEC61000-4-4

Class A, Group 1 Class A, Group 1

In air: 8 kV, In contact: 6 kV 10 V/m Power line AC I/O: 2 kV DC I/O: 1 kV Surge Immunity IEC61000-4-5 Normal Noise AC power supply, AC I/O: 1 kV DC power supply, DC I/O: 0.5 kV Common Noise AC power supply, AC I/O: 2 kV DC power supply: 1 kV DC I/O: 0.5 kV Immunity to Conducted Disturbances Induced by Radio-frequency Fields IEC61000-4-6 3V Momentary Power Interruption Immunity IEC61131-2 CPU Units with AC Power Supplies: 10 ms max. CPU Units with DC Power Supplies: 2 ms max. (level: PS1) Note: EMC conforms to EN 61131-2 clause 8 except in the following cases. • When Expansion I/O Units with DC inputs are connected to a CPU Unit with an AC power supply, the burst immunity between power supplies will be 1 kv. • When the signal wire for transistor outputs exceeds 10 m, the surge immunity of DC output signal lines will not conform.

■ Input Specifications CPU Units AC Inputs (Not Isolated) Item Input voltage

Specifications

Input impedance

680 kΩ

Input current

0.15 mA/100 VAC, 0.35 mA/240 VAC

ON voltage

80 VAC min.

OFF voltage

25 VAC max.

ON response time

50 ms or 70 ms at 100 VAC (See note.) 100 ms or 120 ms at 240 VAC (See note.)

OFF response time

Circuit drawing

100 to 240 VAC +10%, −15%, 50/60 Hz IN 330 kΩ 300 kΩ IN 51 kΩ

Internal circuit

100 to 240 VAC N L

Note: Can be selected using the filter settings.

DC Inputs: I0 to I3 for Units with 10 I/O points, I0 to I9 for Units with 20 I/O Points (Not Isolated) Item Input voltage

Specifications

Circuit drawing

12 to 24 VDC +20%, −10%

Input impedance

5.3 kΩ

Input current

4.5 mA (typ.)/24 VDC

ON voltage

8 VDC min.

OFF voltage

5 VDC max.

ON response time

15 ms or 50 ms (See note.)

IN 5.1 kΩ 1.8 kΩ 12 to 24 VDC

IN Internal circuit COM

OFF response time Note: Can be selected using the input filter settings, except when I0 is being used for an 8-digit counter with a high-speed input.

Programmable Relay ZEN V2 Units

9

Page 10

DC Inputs: I4 and I5 for Units with 10 I/O points, Ia and Ib for Units with 20 I/O Points (Not Isolated) Item

Specifications

Input current

PNP: NPN:

4.3 mA (typ.)/24 VDC 4.6 mA (typ.)/24 VDC

ON voltage

8 VDC min.

OFF voltage

3 VDC max.

ON response time

15 ms or 50 ms (See note.)

OFF response time Input range

0 to 10 V

External input impedance

100 kΩ min.

150 kΩ IN

27 kΩ

+

47 kΩ 220 kΩ

−

COM 47 kΩ

12 to 24 VDC

Resolution

0.1 V (1/100 FS)

Accuracy

±1.5% FS (at ambient operating temperature within rated range)

6.2 kΩ

Internal circuit

NPN:

5.5 kΩ/14 VDC min. 100 kΩ/14 VDC max. 5.2 kΩ

PNP:

Analog voltage output device

Input impedance

Analog Inputs

Circuit drawing

12 to 24 VDC +20%, −10%

DC Inputs Input voltage

5.6 kΩ

AD conversion data 0 to 10.5 V (in increments of 0.1 V) Note: Can be selected using the input filter settings.

Expansion I/O Units AC Inputs (Not Isolated) Specifications

Circuit drawing

100 to 240 VAC +10%, −15%, 50/60 Hz

Input impedance

680 kΩ

Input current

0.15 mA/100 VAC, 0.35 mA/240 VAC

IN

ON voltage

80 VAC min.

IN

OFF voltage

25 VAC max.

ON response time

50 ms or 70 ms at 100 VAC (See note.) 100 ms or 120 ms at 240 VAC (See note.)

Off response time

Internal circuit

Item Input voltage

330 kΩ 300 kΩ 51 kΩ

100 to 240 VAC N L

Note: Can be selected using the input filter settings.

DC Inputs (ZEN-8E1DR: Not Isolated, ZEN-8E1DT: Photocoupler Isolated) Item

Specifications

Circuit drawing

Input voltage

12 to 24 VDC +20%, −10%

Input impedance

6.5 kΩ

IN

Input current

3.7 mA (typ.)/24 VDC

IN

ON voltage

8 VDC min.

OFF voltage

5 VDC max.

ON response time

15 ms or 50 ms (See note 1.)

OFF response time Note: 1. Can be selected using the input filter settings. 2. The ZEN-8E1DT has no +/- terminals. There is no need to supply power.

10

Programmable Relay ZEN V2 Units

± 12 to 24 VDC

COM

6.2 kΩ (See note 2.)

1.8 kΩ Internal circuit