For the Omron ZEN-10C1DR-D-V2

Page 11

■ Output Specifications (CPU Units and Expansion I/O Units) Units with Relay Outputs Item

Specifications

Circuit drawing

Maximum switching capacity 250 VAC/8 A (resistive load: cosφ = 1) 24 VDC/5 A (resistive load) Use the following values for the total of all outputs. CPU Units with 10 I/O points: 20 A max. (15 A max. for Communications-type CPU Units) CPU Units with 20 I/O points: 40 A max. Expansion I/O Units: 20 A max.

Q0 to Q3/OUT0 to OUT3 L

Electrical

Resistive load: 50,000 times (cosφ = 1) Inductive load: 50,000 times (cosφ = 0.4)

Mechanical

10 million times

ON response time

15 ms max.

OFF response time

5 ms max.

COM Models with 20 I/O points only L Q5/Q7

The life under the worst conditions, of the output contacts used in ZEN relay outputs is given in the above table. Guidelines for the normal life of the relays are shown in the diagram on the right. Note: The switching capacity, switching durability, and applicable load area when actually using the relay depend on the type of load, environmental conditions, and switching conditions. Therefore, be sure to confirm these conditions for the actual machine before use.

Life-test Curve (Reference Value) Usage: 360 times/hour Life (× 103)

Relay life

Q4/Q6 L

Internal circuit

Minimum switching capacity 5 VDC/10 mA (resistive load)

1,000

250-VAC resistive load 24-VDC resistive load/ 250-VAC inductive load 24-VDC inductive load (t = 7 ms)

500 300

100 50 30

10 0

2

4

6

8

10

Contact current (A)

Units with Transistor Outputs Item

Specifications

Maximum switching capacity 24 VDC +20%, 500 mA

Leakage current

Circuit drawing Each circuit is configured with an independent common circuit 390 Ω

0.1 mA max.

Q0 to Q3/OUT0 to OUT3 28.8 VDC max.

L L

1 kΩ

Residual voltage

1.5 V max. Internal circuit

ON response time

1 ms max.

COM + L

Q4/Q6

OFF response time

28.8 VDC max. Models with 20 I/O points only

1 ms max. L

Q5/Q7

Programmable Relay ZEN V2 Units

11

Page 12

Connections ■ Input Connections Units with AC Power Supply Note: 1. Supply power to both the CPU Unit and Expansion I/O Units from the same power supply and turn them ON and OFF at the same time. 2. The input circuit commons for CPU Units with AC power supply are internally connected to the N terminal of the power supply circuit. Wire the L terminal to the power supply of the input device. 3. The input circuit commons for Expansion I/O Units with AC power supply are internally connected to the N terminal of the power supply circuit. Wire the L terminal to the power supply of the input device.

CPU Units with 10 I/O Points and Expansion I/O Units 100 to 240 VAC, 50/60 Hz L N Circuit protector

Input device

L

N

NC

I0

I1

I2

I3

I4

I5

L

CPU Unit with 10 I/O points

N

IN0 IN1 IN2 IN3

ZEN-8E1AR Expansion I/O Unit (AC input type)

CPU Units with 20 I/O Points and Expansion I/O Units 100 to 240 VAC, 50/60 Hz L

N

Circuit protector

Input device

L

N

NC

I0

I1

I2

I3

I4

I5

NC

I6

I7

I8

I9

Ia

Ib

L

CPU Unit with 20 I/O points

N

IN0 IN1 IN2 IN3

ZEN-8E1AR Expansion I/O Unit (AC input type)

Connecting Expansion I/O Units with DC Inputs 100 to 240 VAC, 50/60 Hz

DC power supply

N

L Circuit protector

Input device

Input device L

N

NC

I0

I1

I2

CPU Unit with 10 I/O points

I3

I4

I5

COM IN0 IN1 IN2 IN3

ZEN-8E1DR Expansion I/O Unit (DC inputs and relay outputs)

COM IN0 IN1 IN2 IN3

ZEN-8E1DT Expansion I/O Unit (DC inputs and transistor outputs)

Note: When connecting Expansion I/O Units with DC inputs to a CPU Unit with an AC power supply, the burst noise immunity will be 1 kV (IEC 61000-4-4).

12

Programmable Relay ZEN V2 Units

Page 13

Units with DC Power Supply Note: 1. Be sure to connect the COM terminal before turning ON the power supply. If the COM terminal is disconnected, or if the wiring is changed after turning ON the power supply, a malfunction may occur. 2. Apply the power supply voltage through a relay or switch in such a way that the voltage reaches the rated value within 4 s. If the voltage is applied gradually, the power may not be reset or unstable output operations may result.

CPU Units with 10 I/O Points For Connections to Negative (−) Common (PNP Connection) 12 to 24 VDC

Input device COM

CPU Unit with 10 I/O points

For Connecting Analog Input Devices to Input Terminals I4 and I5 12 to 24 VDC

COM I 0

I1

I2

I3

I4

I5

CPU Unit with 10 I/O points

Note: When connecting an analog input device, always connect the negative side to the COM terminal.

For Connections to Positive (+) Common (NPN Connection)

12 to 24 VDC

Input device +

−

COM I0

I1

I2

I3

I4

I5

CPU Unit with 10 I/O points

Note: When connected to the positive (+) common, I4 and I5 cannot be used as analog inputs.

Programmable Relay ZEN V2 Units

13

Page 14

CPU Units with 20 I/O Points For Connections to a Negative Common (PNP Connection) 12 to 24 VDC

Input device COM I0

I1

I2

I3

I4

I5

NC I6

I7

I8

I9

Ia

Ib

CPU Unit with 20 I/O points

For Connecting Analog Input Devices to Input Terminals Ia and Ib 12 to 24 VDC

COM I 0

I1

I2

I3

I4 I5

NC

I6 I 7

I8

I9

Ia

Ib

CPU Unit with 20 I/O points

Note: When connecting an analog input device, always connect the negative side to the COM terminal.

For Connections to Positive (+) Common (NPN Connection) 12 to 24 VDC

Input device +

−

COM I0

I1

I2

I3

I4

I5

NC I6

I7

I8

I9

Ia

Ib

CPU Units with 20 I/O points

Note: When connected to the positive (+) common, Ia and Ib cannot be used as analog inputs.

Expansion I/O Units Note: 1. Supply power to both the CPU Unit and Expansion I/O Units from the same power supply and turn them ON and OFF at the same time. 2. ZEN-8E1AR Expansion I/O Units with AC inputs cannot be connected to CPU Units with DC power supply. 3. The input circuit commons for ZEN-8E1DR Expansion I/O Units with relay outputs are each internally connected to one side of the power supply circuit (COM terminal). 4. ZEN-8E1DT Expansion I/O Units with transistor outputs do not need to be connected to a power supply.

For Connections to Negative (−) Common 12 to 24 VDC

Input device

Input device +

−

COM I0

I1

I2

I3

I4

I5

CPU Unit with 10 I/O points

± COM IN0 IN1 IN2 IN3

ZEN-8E1DR Expansion I/O Unit (DC input, relay output)

NC COM IN0 IN1 IN2 IN3

ZEN-8E1DT Expansion I/O Unit (DC input, transistor output)

For Connections to Positive (+) Common 12 to 24 VDC

Input device

Input device +

−

COM I0

I1

I2

CPU Unit with 10 I/O points

14

I3

I4

I5

± COM IN0 IN1 IN2 IN3

ZEN-8E1DR Expansion I/O Unit (DC input, relay output)

NC COM IN0 IN1 IN2 IN3

ZEN-8E1DT Expansion I/O Unit (DC input, transistor output)

Programmable Relay ZEN V2 Units

Page 15

■ Output Connections Units with Relay Outputs All four relay output circuits in both CPU Units with 10 I/O points and Expansion I/O Units have independent contacts. CPU Units with 20 I/O points have 4 independent contacts (Q0 to Q3) and the remaining four (Q4 to Q7) have 2 points/common. There are no restrictions for polarity.

Standard LCD-type CPU Units, LED-type CPU Units, and Economy-type CPU Units

Communications-type CPU Units

Q7

Load

Load

Expansion I/O Unit

OUT OUT 0 1 Load

RS-485

OUT 3

Load

OUT 2

Load

B (+) A (−)

Load

Load

Load

Q2

Load

Q1

Q6

Expansion I/O Units

Communications-type CPU Unit

Q0

Q5

Load

Q4

Load

Q3

Load

Q2

Load

Q1

Load

Q0

Load

Q3

Load

Q2

Load

Q1

Load

Q0

CPU Unit with 20 I/O Points

Load

CPU Unit with 10 I/O Points

Units with Transistor Outputs For CPU Units with 10 I/O points and Expansion I/O Units, all 4 outputs in the transistor output circuits have independent circuits. The terminals of output have polarity given on the terminal block, but no problem will result from reversing the connection positions of the power supply and load. For CPU Units with 20 I/O points, outputs Q0 to Q3 in the transistor output circuits have independent circuits and outputs Q4 to Q7 have 2 points per common. The terminals of output Q0 to Q3 have polarity given on the terminal block, but no problem will result from reversing the connection positions of the power supply and load. Note: Do not exceed a cable length of 10 m when connecting transistor outputs.

Standard LCD-type CPU Units and LED-type CPU Units without Display

Load

− + − Q6 Q7

Load

− + − Q4 Q5

Load

+ − Q3

Load

+ − Q2

Load

Load

+ − Q1

Q0 to Q3 Load

Load

Q0 to Q3

Load

+ − Q0

+ − Q3

Load

Load

+ − Q2

Load

+ − Q1

Load

+ − Q0

CPU Unit with 20 I/O Points

Load

CPU Unit with 10 I/O Points

Expansion I/O Units Expansion I/O Unit − + − + OUT2 OUT3 − OUT1

Load

OUT0 to OUT3 Load

+

Load

Load

Load

+ − OUT0

Programmable Relay ZEN V2 Units

15

Page 16

Nomenclature ■ Standard LCD-type, Economy-type, and Communications-type CPU Units (Except for ZEN-@C2@@-@-V2 Models) CPU Units with 10 I/O Points Left side

Front

Right side

Power supply Input terminals terminals

Operation buttons

Display screen

Output terminals (See note 1.) Battery Unit connector (Remove the seal to connect the Battery Unit.)

Display Screen

Expansion Unit connector cover (See note 2.) Do not remove this cover until connecting an Expansion Unit.

ZEN Support Software connector (also used for Memory Cassette.)

Front Power supply terminals

Right side

Input terminals

I6

I7

I8

I9

Ia

Operation buttons

Q4

Q5

Q6

Meaning

RUN

Display while in RUN mode.

ERR

Indicates an error.

▲

Displayed when there is a higher-level menu or ladder program line than the one currently displayed.

▼

Displayed when there is a lower-level menu or ladder program line than the one currently displayed.

Ib

20C1AR-A-V2

Display screen

Displayed when a password had been set.

Q7

Output terminals Battery Unit connector (Remove the seal to connect the Battery Unit.)

Icon Meanings Icon

CPU Units with 20 I/O Points Left side

RUN ERR

ZEN Support Software connector (also used for Memory Cassette.)

Expansion Unit connector cover (See note 2.) Do not remove this cover until connecting an Expansion Unit.

Note: 1. With Communications-type CPU Units, the Q3 terminal is used as the RS-485 terminal. For details, refer to “Output Connections” on page 15. 2. Economy-type CPU Units are not provided with an Expansion Unit connector. Do not remove the cover.

16

Programmable Relay ZEN V2 Units

Page 17

Operation Buttons DEL Button

ALT Button

Operation Button Names and Operations Button

Function Menus

Cursor Buttons

ESC Button

Writing ladder program

Setting parameters

Button input bit (See page 24.)

DEL

---

Deletes inputs, outputs, connection --lines, and blank lines.

B6 ON

ALT

---

• Switches between normally open --and normally closed conditions. • Changes to connection line write mode. • Inserts a line.

B7 ON

Up

Moves the cursor • Moves the cursor up and down. up and down. • Selects bit types and functions.

• Moves the cursor up B5 ON and down. • Changes numerals and parameters. B2 ON

---

Moves the cursor right B3 ON and left.

OK Button

Down

Left

Moves the cursor right and left.

Right

B4 ON

ESC

Returns to the Cancels the setting and returns to previous screen. the previous operation.

Cancels the setting and returns to the previous operation.

B0 ON

OK

Selects the Confirms the setting. menu item at the cursor position.

Confirms the setting.

B1 ON

Programmable Relay ZEN V2 Units

17

Page 18

■ LED-type CPU Units without Display (ZEN-@C2@@-@-V2) CPU Units with 10 I/O Points Left side

Front Power supply terminals

Right side Input terminals

LED indicators

LED Indicators Output terminals

Battery Unit connector (Remove the seal to connect the Battery Unit.)

ZEN Support Software connector (also used for Memory Cassette.)

Expansion Unit connector cover Do not remove this cover until connecting an Expansion Unit.

Front Power supply terminals

LED

Green Lit

Right side

Input terminals

I6

I7

ERROR I8

I9

Ia

Status

Green Lit Not lit

RUN

CPU Units with 20 I/O Points Left side

Name POWER

Red

Ib

Power is ON. Power is OFF. Operating (RUN)

Not lit

Stopped (STOP)

Lit

Error occurred.

Not lit

Normal

20C2AR-A-V2

Q4

Q5

Q6

Q7

Output terminals Battery Unit connector (Remove the seal to connect the Battery Unit.)

Expansion Unit connector cover Do not remove this cover until connecting an Expansion I/O Unit.

ZEN Support Software connector (also used for Memory Cassette.) LED indicators

■ Expansion I/O Units (ZEN-8E1@@) Left side

Front Power supply terminals

Right side

Input terminals

Output terminals

Expansion I/O Unit connector

Expansion I/O Unit connector cover Do not remove this cover until connecting an Expansion I/O Unit.

Precaution when Using Expansion I/O Units: Up to three Expansion I/O Units can be connected. When removing the Expansion Unit connector cover from the side of the CPU Unit, use a Phillips screwdriver to remove the cover screw, and then insert a flat-blade screw driver in the cover gap to remove the cover, as shown at the right.

18

Programmable Relay ZEN V2 Units

Phillips screwdriver

Flat-blade screwdriver

Page 19

Operation ■ Bits Name

Symbol

Bit addresses

No. of points

Input bits

I

I0 to Ib 12 (See note 2.)

Reflect the ON/OFF status of the input devices connected to the input terminals on the CPU Unit.

Expansion input bits

X

X0 to Xb

Reflect the ON/OFF status of the input devices connected to the input terminals on the Expansion I/O Units.

Output bits

Q

Q0 to Q7 8 (See note 2.)

The ON/OFF status of these output bits is used to control the output devices connected to the output terminals on the CPU Unit.

Expansion output bits

Y

Y0 to Yb

12

The ON/OFF status of these output bits is used to control the output devices connected to the output terminals on the Expansion I/O Units.

Work bits

M

M0 to Mf

16

Work bits can be used only within the ZEN program. I/Os for external devices cannot be made (i.e., all I/O is internal).

Holding bits

H

H0 to Hf

16

Used the same as the work bits. However, if the power to the ZEN is turned OFF, these bits also maintain the previous ON/OFF status.

Timers

T

T0 to Tf

16

12

Operation

X: ON-delay timer

Functions are selected from the screen when parameter settings are made.

■: OFF-delay timer O: One-shot pulse timer

Details (See note 1.)

Time units can be selected from the following: 0.01-s unit: 0.01 to 99.99 s min/s unit: 00 min 01 s to 99 min 59 s h/s unit: 00 h 01 min to 99 h 59 min

F: Flashing pulse timer

---

1

2

W: Twin timer Holding timers

#

#0 to #7

8

Hold the present value being counted even if the trigger input or power supply is turned OFF and continue timing when the trigger input or power is restored.

Counters

C

C0 to Cf

16

Reversible 4-digit counters that can be incremented and decremented.

8-digit counter

F

F0

1

Reversible 8-digit counters that can be incremented and decremented. CPU Units with DC power supply support a high-speed counter up to 150 Hz. For details, refer to “8-digit Counter Operation” on page 21.

Weekly timers (See note 3.)

@

@0 to @f

16

Turn ON and OFF during specified times on specified days.

Calendar timers (See note 3.)

*

*0 to *f

16

Turn ON and OFF between specified dates.

Display bits (See note 3.)

D

D0 to Df

16

Display user-specified messages, times, timer/counter present values, or analog-converted values.

Analog comparator bits A

A0 to A3

4

Used as program input conditions to output analog comparator comparison results. These bits can be used only for CPU Units with DC power supply.

Timer/counter comparator bits

P

P0 to Pf

16

Compare the present values of timers (T), holding timers (#), and counters (C). Comparison can be made between the same two counters or timers, or with constants.

8-digit counter comparator bits

G

G0 to G3

4

Used to compare the present values of 8-digit counters (F) and output the comparison results.

Button input bits (See note 3.)

B

B0 to B7

8

Used as program input conditions and turn ON when operation buttons are pressed in RUN Mode.

3 4 5 6 7 8 9 10 11 12

Note: 1. For details, refer to the indicated item numbers on the following pages. 2. CPU Units with 10 I/O points have 6 input bits (I0 to I5) and 4 output bits (Q0 to Q3). Output bit Q3 of Communications-type CPU Units, however, cannot be output externally. It can be used as a work bit. 3. These input bits are not supported by LED-type CPU Units without display.

1. Additional Bit Output Functions [: Normal

Set/Reset operation S: Set

I0

I1 [Q0

A: Alternate R: Reset

I2 SQ1

I3 RQ1

I0

I1

I2

Q0

Q1

Q1

Q0 will turn ON or OFF depending Q1 will stay ON once the execution Q1 is forced OFF when the on the ON/OFF status of the condition I1 has turned ON once. A execution condition I2 is turned execution condition I0. reset is used to turn Q1 OFF. ON.

AQ2

I3

Q2

Q2 alternates between turning ON and OFF when the execution condition I3 turns ON.

Programmable Relay ZEN V2 Units

19

Page 20

2. Using Timers and Holding Timers X: ON-delay timer Trigger input

Turns ON after set delay after the trigger input turns ON. Basic Operation

Reset input Setting

Trigger input Timing

Present value 0 Timer bit

Output

Main Applications When delayed operation or a time lag is required.

■: OFF-delay timer Trigger input Reset input Setting

Stays ON while the trigger input is ON and turns OFF after a set delay after the trigger input has turned OFF. Basic Operation Trigger input Timing

Present value 0 Timer bit

Output

Main Applications Useful for OFF delay circuits for lights or fans

O: One-shot pulse timer

Trigger input

Turns ON for a set period after the trigger input turns ON and regardless of how long the trigger input remains ON. Basic Operation

Reset input Trigger input Setting Present value 0 Timer bit

Timing Output

Main Applications Useful for set operations where operation is always required during a regular period only.

F: Flashing pulse timer Trigger input Reset input

Repeatedly turns ON and OFF in a set cycle while the trigger input is ON. Basic Operation Trigger input Timing

Setting Present value 0 Timer bit

Timing

Timing

Timing

Output

Main Applications Useful for flashing emergency lights or sounding buzzers as the output for an alarm circuit.

W: Twin timer Trigger input Reset input ON-time OFF-time

Repeatedly turns ON and OFF in a set cycle while the trigger input is ON. Independent ON- and OFF-time settings are possible. Basic Operation Trigger input Timing Timing Timing Timing (OFF-time) (ON-time) (OFF-time) (ON-time)

Present value 0 Timer bit

Output

Main Applications Useful for intermittent (ON/OFF) operation, such as that used for fans.

3. Using Holding Timers X: ON-delay timer Trigger input Reset input Setting Present value 0

Timer bit

20

Programmable Relay ZEN V2 Units

Turns ON after set delay after the trigger input turns ON. The present value is held while the trigger input is OFF. Main Applications To continue operation after momentary power loss or power interruptions. Also can be used when delayed operation or a time lag is required.