The text of a spec sheet · part 2 of 4
Programmable Relay ZEN V2 Units, pages 11 to 20
Pages 11 to 20 of 37
The original document is the PDF (1.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron ZEN-10C1DR-D-V2
Page 11
■ Output Specifications (CPU Units and Expansion I/O Units) Units with Relay Outputs Item
Specifications
Circuit drawing
Maximum switching capacity 250 VAC/8 A (resistive load: cosφ = 1) 24 VDC/5 A (resistive load) Use the following values for the total of all outputs. CPU Units with 10 I/O points: 20 A max. (15 A max. for Communications-type CPU Units) CPU Units with 20 I/O points: 40 A max. Expansion I/O Units: 20 A max.
Q0 to Q3/OUT0 to OUT3 L
Electrical
Resistive load: 50,000 times (cosφ = 1) Inductive load: 50,000 times (cosφ = 0.4)
Mechanical
10 million times
ON response time
15 ms max.
OFF response time
5 ms max.
COM Models with 20 I/O points only L Q5/Q7
The life under the worst conditions, of the output contacts used in ZEN relay outputs is given in the above table. Guidelines for the normal life of the relays are shown in the diagram on the right. Note: The switching capacity, switching durability, and applicable load area when actually using the relay depend on the type of load, environmental conditions, and switching conditions. Therefore, be sure to confirm these conditions for the actual machine before use.
Life-test Curve (Reference Value) Usage: 360 times/hour Life (× 103)
Relay life
Q4/Q6 L
Internal circuit
Minimum switching capacity 5 VDC/10 mA (resistive load)
1,000
250-VAC resistive load 24-VDC resistive load/ 250-VAC inductive load 24-VDC inductive load (t = 7 ms)
500 300
100 50 30
10 0
2
4
6
8
10
Contact current (A)
Units with Transistor Outputs Item
Specifications
Maximum switching capacity 24 VDC +20%, 500 mA
Leakage current
Circuit drawing Each circuit is configured with an independent common circuit 390 Ω
0.1 mA max.
Q0 to Q3/OUT0 to OUT3 28.8 VDC max.
L L
1 kΩ
Residual voltage
1.5 V max. Internal circuit
ON response time
1 ms max.
COM + L
Q4/Q6
OFF response time
28.8 VDC max. Models with 20 I/O points only
1 ms max. L
Q5/Q7
Programmable Relay ZEN V2 Units
11
Page 12
Connections ■ Input Connections Units with AC Power Supply Note: 1. Supply power to both the CPU Unit and Expansion I/O Units from the same power supply and turn them ON and OFF at the same time. 2. The input circuit commons for CPU Units with AC power supply are internally connected to the N terminal of the power supply circuit. Wire the L terminal to the power supply of the input device. 3. The input circuit commons for Expansion I/O Units with AC power supply are internally connected to the N terminal of the power supply circuit. Wire the L terminal to the power supply of the input device.
CPU Units with 10 I/O Points and Expansion I/O Units 100 to 240 VAC, 50/60 Hz L N Circuit protector
Input device
L
N
NC
I0
I1
I2
I3
I4
I5
L
CPU Unit with 10 I/O points
N
IN0 IN1 IN2 IN3
ZEN-8E1AR Expansion I/O Unit (AC input type)
CPU Units with 20 I/O Points and Expansion I/O Units 100 to 240 VAC, 50/60 Hz L
N
Circuit protector
Input device
L
N
NC
I0
I1
I2
I3
I4
I5
NC
I6
I7
I8
I9
Ia
Ib
L
CPU Unit with 20 I/O points
N
IN0 IN1 IN2 IN3
ZEN-8E1AR Expansion I/O Unit (AC input type)
Connecting Expansion I/O Units with DC Inputs 100 to 240 VAC, 50/60 Hz
DC power supply
N
L Circuit protector
Input device
Input device L
N
NC
I0
I1
I2
CPU Unit with 10 I/O points
I3
I4
I5
COM IN0 IN1 IN2 IN3
ZEN-8E1DR Expansion I/O Unit (DC inputs and relay outputs)
COM IN0 IN1 IN2 IN3
ZEN-8E1DT Expansion I/O Unit (DC inputs and transistor outputs)
Note: When connecting Expansion I/O Units with DC inputs to a CPU Unit with an AC power supply, the burst noise immunity will be 1 kV (IEC 61000-4-4).
12
Programmable Relay ZEN V2 Units
Page 13
Units with DC Power Supply Note: 1. Be sure to connect the COM terminal before turning ON the power supply. If the COM terminal is disconnected, or if the wiring is changed after turning ON the power supply, a malfunction may occur. 2. Apply the power supply voltage through a relay or switch in such a way that the voltage reaches the rated value within 4 s. If the voltage is applied gradually, the power may not be reset or unstable output operations may result.
CPU Units with 10 I/O Points For Connections to Negative (−) Common (PNP Connection) 12 to 24 VDC
Input device COM
CPU Unit with 10 I/O points
For Connecting Analog Input Devices to Input Terminals I4 and I5 12 to 24 VDC
COM I 0
I1
I2
I3
I4
I5
CPU Unit with 10 I/O points
Note: When connecting an analog input device, always connect the negative side to the COM terminal.
For Connections to Positive (+) Common (NPN Connection)
12 to 24 VDC
Input device +
−
COM I0
I1
I2
I3
I4
I5
CPU Unit with 10 I/O points
Note: When connected to the positive (+) common, I4 and I5 cannot be used as analog inputs.
Programmable Relay ZEN V2 Units
13
Page 14
CPU Units with 20 I/O Points For Connections to a Negative Common (PNP Connection) 12 to 24 VDC
Input device COM I0
I1
I2
I3
I4
I5
NC I6
I7
I8
I9
Ia
Ib
CPU Unit with 20 I/O points
For Connecting Analog Input Devices to Input Terminals Ia and Ib 12 to 24 VDC
COM I 0
I1
I2
I3
I4 I5
NC
I6 I 7
I8
I9
Ia
Ib
CPU Unit with 20 I/O points
Note: When connecting an analog input device, always connect the negative side to the COM terminal.
For Connections to Positive (+) Common (NPN Connection) 12 to 24 VDC
Input device +
−
COM I0
I1
I2
I3
I4
I5
NC I6
I7
I8
I9
Ia
Ib
CPU Units with 20 I/O points
Note: When connected to the positive (+) common, Ia and Ib cannot be used as analog inputs.
Expansion I/O Units Note: 1. Supply power to both the CPU Unit and Expansion I/O Units from the same power supply and turn them ON and OFF at the same time. 2. ZEN-8E1AR Expansion I/O Units with AC inputs cannot be connected to CPU Units with DC power supply. 3. The input circuit commons for ZEN-8E1DR Expansion I/O Units with relay outputs are each internally connected to one side of the power supply circuit (COM terminal). 4. ZEN-8E1DT Expansion I/O Units with transistor outputs do not need to be connected to a power supply.
For Connections to Negative (−) Common 12 to 24 VDC
Input device
Input device +
−
COM I0
I1
I2
I3
I4
I5
CPU Unit with 10 I/O points
± COM IN0 IN1 IN2 IN3
ZEN-8E1DR Expansion I/O Unit (DC input, relay output)
NC COM IN0 IN1 IN2 IN3
ZEN-8E1DT Expansion I/O Unit (DC input, transistor output)
For Connections to Positive (+) Common 12 to 24 VDC
Input device
Input device +
−
COM I0
I1
I2
CPU Unit with 10 I/O points
14
I3
I4
I5
± COM IN0 IN1 IN2 IN3
ZEN-8E1DR Expansion I/O Unit (DC input, relay output)
NC COM IN0 IN1 IN2 IN3
ZEN-8E1DT Expansion I/O Unit (DC input, transistor output)
Programmable Relay ZEN V2 Units
Page 15
■ Output Connections Units with Relay Outputs All four relay output circuits in both CPU Units with 10 I/O points and Expansion I/O Units have independent contacts. CPU Units with 20 I/O points have 4 independent contacts (Q0 to Q3) and the remaining four (Q4 to Q7) have 2 points/common. There are no restrictions for polarity.
Standard LCD-type CPU Units, LED-type CPU Units, and Economy-type CPU Units
Communications-type CPU Units
Q7
Load
Load
Expansion I/O Unit
OUT OUT 0 1 Load
RS-485
OUT 3
Load
OUT 2
Load
B (+) A (−)
Load
Load
Load
Q2
Load
Q1
Q6
Expansion I/O Units
Communications-type CPU Unit
Q0
Q5
Load
Q4
Load
Q3
Load
Q2
Load
Q1
Load
Q0
Load
Q3
Load
Q2
Load
Q1
Load
Q0
CPU Unit with 20 I/O Points
Load
CPU Unit with 10 I/O Points
Units with Transistor Outputs For CPU Units with 10 I/O points and Expansion I/O Units, all 4 outputs in the transistor output circuits have independent circuits. The terminals of output have polarity given on the terminal block, but no problem will result from reversing the connection positions of the power supply and load. For CPU Units with 20 I/O points, outputs Q0 to Q3 in the transistor output circuits have independent circuits and outputs Q4 to Q7 have 2 points per common. The terminals of output Q0 to Q3 have polarity given on the terminal block, but no problem will result from reversing the connection positions of the power supply and load. Note: Do not exceed a cable length of 10 m when connecting transistor outputs.
Standard LCD-type CPU Units and LED-type CPU Units without Display
Load
− + − Q6 Q7
Load
− + − Q4 Q5
Load
+ − Q3
Load
+ − Q2
Load
Load
+ − Q1
Q0 to Q3 Load
Load
Q0 to Q3
Load
+ − Q0
+ − Q3
Load
Load
+ − Q2
Load
+ − Q1
Load
+ − Q0
CPU Unit with 20 I/O Points
Load
CPU Unit with 10 I/O Points
Expansion I/O Units Expansion I/O Unit − + − + OUT2 OUT3 − OUT1
Load
OUT0 to OUT3 Load
+
Load
Load
Load
+ − OUT0
Programmable Relay ZEN V2 Units
15
Page 16
Nomenclature ■ Standard LCD-type, Economy-type, and Communications-type CPU Units (Except for ZEN-@C2@@-@-V2 Models) CPU Units with 10 I/O Points Left side
Front
Right side
Power supply Input terminals terminals
Operation buttons
Display screen
Output terminals (See note 1.) Battery Unit connector (Remove the seal to connect the Battery Unit.)
Display Screen
Expansion Unit connector cover (See note 2.) Do not remove this cover until connecting an Expansion Unit.
ZEN Support Software connector (also used for Memory Cassette.)
Front Power supply terminals
Right side
Input terminals
I6
I7
I8
I9
Ia
Operation buttons
Q4
Q5
Q6
Meaning
RUN
Display while in RUN mode.
ERR
Indicates an error.
▲
Displayed when there is a higher-level menu or ladder program line than the one currently displayed.
▼
Displayed when there is a lower-level menu or ladder program line than the one currently displayed.
Ib
20C1AR-A-V2
Display screen
Displayed when a password had been set.
Q7
Output terminals Battery Unit connector (Remove the seal to connect the Battery Unit.)
Icon Meanings Icon
CPU Units with 20 I/O Points Left side
RUN ERR
ZEN Support Software connector (also used for Memory Cassette.)
Expansion Unit connector cover (See note 2.) Do not remove this cover until connecting an Expansion Unit.
Note: 1. With Communications-type CPU Units, the Q3 terminal is used as the RS-485 terminal. For details, refer to “Output Connections” on page 15. 2. Economy-type CPU Units are not provided with an Expansion Unit connector. Do not remove the cover.
16
Programmable Relay ZEN V2 Units
Page 17
Operation Buttons DEL Button
ALT Button
Operation Button Names and Operations Button
Function Menus
Cursor Buttons
ESC Button
Writing ladder program
Setting parameters
Button input bit (See page 24.)
DEL
---
Deletes inputs, outputs, connection --lines, and blank lines.
B6 ON
ALT
---
• Switches between normally open --and normally closed conditions. • Changes to connection line write mode. • Inserts a line.
B7 ON
Up
Moves the cursor • Moves the cursor up and down. up and down. • Selects bit types and functions.
• Moves the cursor up B5 ON and down. • Changes numerals and parameters. B2 ON
---
Moves the cursor right B3 ON and left.
OK Button
Down
Left
Moves the cursor right and left.
Right
B4 ON
ESC
Returns to the Cancels the setting and returns to previous screen. the previous operation.
Cancels the setting and returns to the previous operation.
B0 ON
OK
Selects the Confirms the setting. menu item at the cursor position.
Confirms the setting.
B1 ON
Programmable Relay ZEN V2 Units
17
Page 18
■ LED-type CPU Units without Display (ZEN-@C2@@-@-V2) CPU Units with 10 I/O Points Left side
Front Power supply terminals
Right side Input terminals
LED indicators
LED Indicators Output terminals
Battery Unit connector (Remove the seal to connect the Battery Unit.)
ZEN Support Software connector (also used for Memory Cassette.)
Expansion Unit connector cover Do not remove this cover until connecting an Expansion Unit.
Front Power supply terminals
LED
Green Lit
Right side
Input terminals
I6
I7
ERROR I8
I9
Ia
Status
Green Lit Not lit
RUN
CPU Units with 20 I/O Points Left side
Name POWER
Red
Ib
Power is ON. Power is OFF. Operating (RUN)
Not lit
Stopped (STOP)
Lit
Error occurred.
Not lit
Normal
20C2AR-A-V2
Q4
Q5
Q6
Q7
Output terminals Battery Unit connector (Remove the seal to connect the Battery Unit.)
Expansion Unit connector cover Do not remove this cover until connecting an Expansion I/O Unit.
ZEN Support Software connector (also used for Memory Cassette.) LED indicators
■ Expansion I/O Units (ZEN-8E1@@) Left side
Front Power supply terminals
Right side
Input terminals
Output terminals
Expansion I/O Unit connector
Expansion I/O Unit connector cover Do not remove this cover until connecting an Expansion I/O Unit.
Precaution when Using Expansion I/O Units: Up to three Expansion I/O Units can be connected. When removing the Expansion Unit connector cover from the side of the CPU Unit, use a Phillips screwdriver to remove the cover screw, and then insert a flat-blade screw driver in the cover gap to remove the cover, as shown at the right.
18
Programmable Relay ZEN V2 Units
Phillips screwdriver
Flat-blade screwdriver
Page 19
Operation ■ Bits Name
Symbol
Bit addresses
No. of points
Input bits
I
I0 to Ib 12 (See note 2.)
Reflect the ON/OFF status of the input devices connected to the input terminals on the CPU Unit.
Expansion input bits
X
X0 to Xb
Reflect the ON/OFF status of the input devices connected to the input terminals on the Expansion I/O Units.
Output bits
Q
Q0 to Q7 8 (See note 2.)
The ON/OFF status of these output bits is used to control the output devices connected to the output terminals on the CPU Unit.
Expansion output bits
Y
Y0 to Yb
12
The ON/OFF status of these output bits is used to control the output devices connected to the output terminals on the Expansion I/O Units.
Work bits
M
M0 to Mf
16
Work bits can be used only within the ZEN program. I/Os for external devices cannot be made (i.e., all I/O is internal).
Holding bits
H
H0 to Hf
16
Used the same as the work bits. However, if the power to the ZEN is turned OFF, these bits also maintain the previous ON/OFF status.
Timers
T
T0 to Tf
16
12
Operation
X: ON-delay timer
Functions are selected from the screen when parameter settings are made.
■: OFF-delay timer O: One-shot pulse timer
Details (See note 1.)
Time units can be selected from the following: 0.01-s unit: 0.01 to 99.99 s min/s unit: 00 min 01 s to 99 min 59 s h/s unit: 00 h 01 min to 99 h 59 min
F: Flashing pulse timer
---
1
2
W: Twin timer Holding timers
#
#0 to #7
8
Hold the present value being counted even if the trigger input or power supply is turned OFF and continue timing when the trigger input or power is restored.
Counters
C
C0 to Cf
16
Reversible 4-digit counters that can be incremented and decremented.
8-digit counter
F
F0
1
Reversible 8-digit counters that can be incremented and decremented. CPU Units with DC power supply support a high-speed counter up to 150 Hz. For details, refer to “8-digit Counter Operation” on page 21.
Weekly timers (See note 3.)
@
@0 to @f
16
Turn ON and OFF during specified times on specified days.
Calendar timers (See note 3.)
*
*0 to *f
16
Turn ON and OFF between specified dates.
Display bits (See note 3.)
D
D0 to Df
16
Display user-specified messages, times, timer/counter present values, or analog-converted values.
Analog comparator bits A
A0 to A3
4
Used as program input conditions to output analog comparator comparison results. These bits can be used only for CPU Units with DC power supply.
Timer/counter comparator bits
P
P0 to Pf
16
Compare the present values of timers (T), holding timers (#), and counters (C). Comparison can be made between the same two counters or timers, or with constants.
8-digit counter comparator bits
G
G0 to G3
4
Used to compare the present values of 8-digit counters (F) and output the comparison results.
Button input bits (See note 3.)
B
B0 to B7
8
Used as program input conditions and turn ON when operation buttons are pressed in RUN Mode.
3 4 5 6 7 8 9 10 11 12
Note: 1. For details, refer to the indicated item numbers on the following pages. 2. CPU Units with 10 I/O points have 6 input bits (I0 to I5) and 4 output bits (Q0 to Q3). Output bit Q3 of Communications-type CPU Units, however, cannot be output externally. It can be used as a work bit. 3. These input bits are not supported by LED-type CPU Units without display.
1. Additional Bit Output Functions [: Normal
Set/Reset operation S: Set
I0
I1 [Q0
A: Alternate R: Reset
I2 SQ1
I3 RQ1
I0
I1
I2
Q0
Q1
Q1
Q0 will turn ON or OFF depending Q1 will stay ON once the execution Q1 is forced OFF when the on the ON/OFF status of the condition I1 has turned ON once. A execution condition I2 is turned execution condition I0. reset is used to turn Q1 OFF. ON.
AQ2
I3
Q2
Q2 alternates between turning ON and OFF when the execution condition I3 turns ON.
Programmable Relay ZEN V2 Units
19
Page 20
2. Using Timers and Holding Timers X: ON-delay timer Trigger input
Turns ON after set delay after the trigger input turns ON. Basic Operation
Reset input Setting
Trigger input Timing
Present value 0 Timer bit
Output
Main Applications When delayed operation or a time lag is required.
■: OFF-delay timer Trigger input Reset input Setting
Stays ON while the trigger input is ON and turns OFF after a set delay after the trigger input has turned OFF. Basic Operation Trigger input Timing
Present value 0 Timer bit
Output
Main Applications Useful for OFF delay circuits for lights or fans
O: One-shot pulse timer
Trigger input
Turns ON for a set period after the trigger input turns ON and regardless of how long the trigger input remains ON. Basic Operation
Reset input Trigger input Setting Present value 0 Timer bit
Timing Output
Main Applications Useful for set operations where operation is always required during a regular period only.
F: Flashing pulse timer Trigger input Reset input
Repeatedly turns ON and OFF in a set cycle while the trigger input is ON. Basic Operation Trigger input Timing
Setting Present value 0 Timer bit
Timing
Timing
Timing
Output
Main Applications Useful for flashing emergency lights or sounding buzzers as the output for an alarm circuit.
W: Twin timer Trigger input Reset input ON-time OFF-time
Repeatedly turns ON and OFF in a set cycle while the trigger input is ON. Independent ON- and OFF-time settings are possible. Basic Operation Trigger input Timing Timing Timing Timing (OFF-time) (ON-time) (OFF-time) (ON-time)
Present value 0 Timer bit
Output
Main Applications Useful for intermittent (ON/OFF) operation, such as that used for fans.
3. Using Holding Timers X: ON-delay timer Trigger input Reset input Setting Present value 0
Timer bit
20
Programmable Relay ZEN V2 Units
Turns ON after set delay after the trigger input turns ON. The present value is held while the trigger input is OFF. Main Applications To continue operation after momentary power loss or power interruptions. Also can be used when delayed operation or a time lag is required.