The text of a spec sheet · part 3 of 4
Programmable Relay ZEN V2 Units, pages 21 to 30
Pages 21 to 30 of 37
The original document is the PDF (1.8 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron ZEN-10C1DR-D-V2
Page 21
4. Counter Operation The counter bit turns ON when the counter value (present value) reaches the set value (present value ≥ set value). The counter returns to 0 and the counter bit turns OFF when the reset input turns ON. Count inputs are not accepted while the reset input is turned ON. The counter present value and counter bit (ON/OFF) are held even if the operating mode is changed or the power supply is interrupted.
Counter direction specification input Counter input Reset input Set value Present value 0000 Counter bit
5. 8-digit Counter Operation Count speed H
High speed
Operation The counter bit turns ON when the counter value (present value) reaches the set value (present value ≥ set value). The counter returns to 0 and the counter bit turns OFF when the reset input turns ON. Count inputs are not accepted while the reset input is turned ON. The counter present value and counter bit (ON/OFF) are held even if the operating mode is changed or the power supply is interrupted. High-speed Operation For CPU Units with DC power supply, high-speed operation is possible for input I0 only. (Maximum counting speed: 150 Hz)
Counter direction specification input Counter input Reset input
L
Low speed
Set value Present value 00000000 Counter bit
Counting Speed of the 8-digit Counter The maximum counting speed of the 8-digit counter is 150 Hz. When the ladder program volume is large, however, this speed will be less than 150 Hz. Calculate the cycle time and confirm the maximum counting speed using the following formula. The calculation serves as a guide only, so allow a suitable margin in the actual machine. Maximum counting speed = 1,000,000 Hz/ Cycle time (µs) × 2.2 Hz Note: Even if the calculated maximum counting speed exceeds 150 Hz using this formula, the maximum counting speed will be 150 Hz. Cycle Time Calculation Method Cycle time (µs)
=
Common processing time
+
Processing time taken when Expansion I/O Units are connected
+
Ladder program execution time
+
Communications processing time (only for CPU Units with communications)
Refer to the following table for ZEN execution times. The execution times are provided as a guide. External factors, button operations, execution of ZEN Support Software operations, and timing of the processing affects the actual processing times. Common Processing Time
Ladder Program Execution Time
Unit type
Common processing time
Standard LCD-type CPU Units, Economy-type CPU Units, and Communications-type CPU Units
850 µs
LED-type CPU Units
200 µs
Expansion I/O Unit Processing Time Unit type Expansion I/O Units
Expansion I/O Unit processing time 160 µs per Unit
Communications Processing Time (only for CPU Units with Communications) Reading information
170 µs
Writing set values
Twin timer: 11,000 µs Others: 6,000 µs
Writing time information
820 µs
30 µs: Line containing program 7 µs: Empty lines
Per line
Per output CPU Unit output bits (Q) 4 µs
*1 *2
Expansion I/O Unit output bits (Y) Work bits (M) Holding bits (H) Timers (T)/Holding timers (#)
15 µs
Counters (C)/8-Digit Counters (F)
13 µs
Display bits (D)
Hour and minute (CLK)/Year and month (DAT)/Month and day (DAT1): 21 µs Timers (T)/Holding timers (#)/Counters (C)/Analog comparators: 28 µs Characters (CHR)/8-Digit Counters (F): 38 µs
Weekly timers (@)
4 µs
Calendar timers (*)
1 µs
Analog comparators (A)
3 µs
Comparators (P)
7 µs
8-Digit Comparators (G)
4 µs
Programmable Relay ZEN V2 Units
*3
*4
*5
21
Page 22
Example Calculation of Ladder Program Execution Time
00 01 02 03 04
I0
I1
I2
Ladder program execution time = (30 × 5) + (4 × 3) + 15 + 4 + 7 = 188 (µs)
[Q0
Q0
*5: P0
I3
*4: @0
[Q1
I4
*3: T0 (output)
TT0
@0
P0
T0
*2: Q (outputs) for 3 points
[Q2
*1: For 5 lines
6. Weekly Timer Operation (Only for Standard LCD-type, Economy-type, and Communicationstype CPU Units) Weekly timer mode N
Normal operation
Operation Typical Timer Operation
Between Tuesday and Friday every week, the weekly timer bit turns ON from 08:15 until 17:30.
Date setting
Time setting
24:00 Stop time
17:30
Start time
8:15 0:00
Mon
Tues
Wed
Thurs
Fri
Sat
Sun
Weekly timer bit
Timer Operation Extending Past Midnight
Between Tuesday and Friday every week, the weekly timer bit turns ON from 23:00 until 05:00 the following day.
Time setting
Date setting
Start time
Stop time
24:00 23:00
Mon
Tues
Wed
Thurs
Fri
Sat
Sun
5:00 0:00
Weekly timer bit
Multipleday operation
The weekly timer bit turns ON from Tuesday 08:15 until Friday 17:30 every week.
Date setting 24:00 Time setting
D
Stop time
17:30
Start time
8:15 0:00
Mon
Tues
Wed
Thurs
Fri
Sat
Sun
Weekly timer bit
Pulseoutput operation
Date setting 24:00 Time setting
P
Start time
Mon
Tues
Wed
Thurs
Fri
Sat
Sun
Every week, from Tuesday through Friday, the weekly timer bit turns ON for 15 minutes and thirty seconds from 08:15.
8:15 0:00
Weekly timer bit Operation time setting: 15 minutes, 30 seconds
7. Calendar Timer Operation (Only for Standard LCD-type, Economy-type, and Communications-type CPU Units) Dec 31 End date Sep 1 Start date Apr 1 Jan 1 Calendar timer bit The calendar timer bit is ON between 1 April and 31 August.
22
Programmable Relay ZEN V2 Units
Page 23
8. Display Settings (Only for Standard LCD-type, Economy-type, and Communications-type CPU Units) Backlight/display L0: No backlight; No switching to display function screen (See note 1.) function screen L1: Backlight; No switching to display function screen (See note 1.) switching L2: No backlight; Switching to display function screen (See note 2.) L3: Backlight; Switching to display function screen (See note 2.) Display start position
X (digit): 00 to 11 Y (line): 0 to 3
Display object
CHR
Monitoring
X00
X11
Y0 to Y3
Characters (Up to 12 characters - English, numerals, symbols)
DAT
Month/day (5 digits @@/@@)
CLK hour/minute (5 digits @@:@@)
I4 to I5
Analog-converted value (4 digits @@:@)
T0 to Tf
Timer present value (5 digits @@.@@)
#0 to #7
Holding timer present value (5 digits @@.@@)
C0 to Cf
Counter present value (4 digits @@@@)
F0
8-digit counter present value(8 digits @@@@@@@@)
A: Can read settings during operation. D: Cannot read settings during operation.
Note: 1. When L0 or L1 are selected to disable the display function screen, the display function screen will not be displayed automatically. Use operation buttons to move to the display function screen. 2. When L2 or L3 are selected, the ZEN switches to the display function screen if the display function is enabled and the specified data is displayed. The Main Screen will no longer be displayed. To display the Main Screen, change the CPU Unit to STOP mode.
9. Analog Comparator Operation • Example 1 (When comparison shows analog input 1 ≥ 5.2 V)
• Example 2 (When comparison shows analog input 1 is ≤ analog input 2)
Setting 10.5 10.0
Converted value 10.0 Analog input 1
5.2 Analog input 2
00.0 0.0
10.5 V
00.0
10.0 V Input voltage
Analog comparator bit
Analog comparator bit
10. Timer/Counter Comparator Operation • Example 1 (When comparison setting is holding timer #0 ≥ 12 min 34 s) Setting
• Example 2 (When comparison setting is counter 1 (C1) ≤ counter 2 (C2)) C1 present value
#0 present value
12 min 34 s C2 present value 0 Comparator bit
Comparator bit
11. 8-digit Counter Comparator Operation • When comparison setting is 8-digit counter F0 ≥ 12000000
F0 present value
12000000
0 8-digit counter comparator bit
Programmable Relay ZEN V2 Units
23
Page 24
12. Specifications for Button Input Bits (Only for Standard LCD-type, Economy-type, and Communications-type CPU Units) The operation buttons are used to perform operations for input bits. They are useful when checking program operations or forcefully resetting holding timers or counters.
ALT Button input 7 (B7)
DEL Button input 6 (B6)
Button input 5 (B5) Button input 4 (B4) Button input 3 (B3) Button input 2 (B2)
OK Button input 1 (B1)
ESC Button input 0 (B0)
■ Password Function (Only for Standard LCD-type, Economy-type, and Communications-type CPU Units) The ZEN has a password function to prevent incorrect manipulation of ladder programs or settings data by other operators. When the password (0000 to 9999) is set, the following operations will not be possible unless the password is input correctly. • Editing ladder program • Program all clear • Monitoring ladder programs • Changing/clearing password • Changing backlight OFF time • Setting input filter • Setting RS-485 communications
24
Programmable Relay ZEN V2 Units
Page 25
■ ZEN Support Software Functions Note: Always use ZEN-SOFT01-V4 as the Support Software for the V2 CPU Unit.
Creating Ladder Programs
Simulating Ladder Programs
ZEN ladder programs can be created with ease.
The simulation function makes it possible to check whether correct operation is performed without connecting to the ZEN.
Note: The Edit Input Dialog Box is displayed when an input bit is inserted. Timer, counter, and other parameter settings are also set in the Edit Input Dialog Box. They cannot be set in the Edit Output Dialog Box.
Monitoring Ladder Programs
Printing Ladder Programs
The operating status can be monitored from the Support Software by connecting to the ZEN using a Connecting Cable (ZEN-CIF01).
Ladder programs and I/O comments, as well as timer, counter and other parameter settings can be printed.
Note: Both RS-485 communications and the ZEN monitoring function cannot be used at the same time with Communications-type CPU Units.
The Support Software can also be used to save files and edit comments. Refer to the ZEN Support Software Operation Manual (Cat. No. Z184-E1-03) for details.
Programmable Relay ZEN V2 Units
25
Page 26
Dimensions Note: All units are in millimeters unless otherwise indicated.
■ CPU Units CPU Units with 10 I/O Points ZEN-10C@@@-@-V2
Unit Mounting Holes
56 44
70 60
4.5 5.5
90
80
Note: Use M4 screws for mounting.
45
Mounting Hole Dimensions Two, M4
4.7 (Sliding: 13 max.)
CPU Units with 20 I/O Points ZEN-20C@@@-@-V2
80 56 44
122.5 112.5 I6
I7
I8
I9
Ia
Ib
60 (112.5) * * The dimensions in parentheses refer to models with 20 I/O points.
20C1AR-A-V2
90
80
45
Q4
Q5
Q6
Q7
4.7 (Sliding: 13 max.)
Dimensions with Battery Unit CPU Units with 10 I/O Points
CPU Units with 20 I/O Points 140
87.5 17.5
44
122.5
17.5
70
I6
I8
ZEN-BAT01
20C1AR-A-V2
45
45
Q4
26
I7
Programmable Relay ZEN V2 Units
Q5
Q6
Q7
I9
Ia
Ib
Page 27
■ Expansion I/O Units DIN Track Hook (Using Slide)
ZEN-8E1@@
Mounting Hole Dimensions 7.6 2
54
Two, 3.5 dia.
90
97
Two, M3
17.5
44
35
90
45
97
2 7.6
■ Power Supply Unit ZEN-PA03024
70 60
90
56 44
45
80
Mounting Hole Dimensions Two, M4
80
60 4.7 (Sliding: 13 max.)
■ Accessories (Order Separately) Battery Unit
Memory Cassette
Connecting Cable
ZEN-BAT01
ZEN-ME01
ZEN-CIF01 Cable length: 2m
Programmable Relay ZEN V2 Units
27
Page 28
■ Track Mounting Accessories (Order Separately) Mounting Track PFP-100N PFP-50N
PFP-100N2
16
7.3±0.15 4.5
4.5 35±0.3
15
25
10
25
25 1,000 (500) *
10
25
15 (5) *
27±0.15
1
35±0.3 27
15
25
10
* The numbers in parentheses () are dimensions for the PFP-50N.
End Plate M4 × 8 pan-head screw
1,000
10
25
15
16 12
5 1.8
1.5
1
Spacer
10 6.2
PFP-M
25
25
29.2
24
PFP-S
1
50
35.5 35.3 1.8
34.8 44.3
11.5 10
M4 spring washer
1.3 4.8
16.5
Precautions when Selecting ZEN Programmable Relays ■ Changes in Comparison with Previous Models • The power supply and transistor output voltage ranges for CPU Units and Expansion I/O Units with DC power supply has been expanded to 10.8 to 28.8 VDC. • The width of Expansion I/O Units has been reduced by half and only 8-point models are available. • The connection method between the CPU Unit and Expansion I/O Units has changed. • Twin timer operation has been added to timers. • Multiple-day operation and pulse-output operation has been added to weekly timers. • An 8-digit counter and 8-digit comparators have been added. • The accuracy of analog inputs has been increased to ±1.5% FS. • The timing accuracy of weekly timers and calendar timers has been increased to ±15 s or less per month (at 25°C). • Australia and New Zealand Daylight Saving Time (DST) settings have been added. • CPU Units with RS-485 communications and economic CPU Units have been added. • The heat slits in the cases of CPU Units and Expansion I/O Units have been removed to prevent foreign matter from entering.
Model numbers have been changed to reflect the improved functionality. Previous Model Numbers ZEN-@C@@@-@ ZEN-@C@@@-@-V1 ZEN-@E@@
(Pre-V1 CPU Units) (V1 CPU Units) (4E/8E-type Expansion I/O Units)
New Model Numbers ZEN-@C@@@-@-V2 ZEN-8E1@@
(V2 CPU Units) (8E1-type Expansion I/O Unit)
Memory Cassettes, Connecting Cables, and Battery Units have not been changed and can be used as they are with the new models.
28
Programmable Relay ZEN V2 Units
Page 29
Precautions when Switching from Previous Units • Previous models of Expansion I/O Units cannot be connected to V2 CPU Units. • ZEN-8E1@R Expansion I/O Units with relay outputs need to be connected to a power supply. • A ZEN-@C@D@-D-V2 CPU Unit with DC power supply cannot be connected to an Expansion I/O Unit with AC inputs. • When connecting Expansion I/O Units with DC inputs to a CPU Unit with an AC power supply, the burst noise immunity will be 1 kV (IEC 610004-4). • There is no change to the 8 A per contact for relay output, but the total output for all contacts must be as follows: Units with 10 I/O Points: 20 A max. (15 A max. for Communications-type CPU Units) Units with 20 I/O Points: 40 A max. Expansion I/O Units: 20 A max. • Always use the ZEN-SOFT01-V4 Support Software for V2 CPU Units. • Input wiring for CPU Units with DC power supplies differs from that for Pre-V1 CPU Units. Refer to the following diagrams. V2 and V1 CPU Units
Pre-V1 CPU Units
COM wiring depends on whether a negative common or positive common is being used. Positive (+) COM Wiring
Negative (−) COM Wiring
The input circuit common terminal is connected internally to the negative (−) side of the power supply circuit.
24 VDC
24 VDC
COM wiring required.
COM wiring required.
24 VDC
Analog inputs possible. Input devices +
−
COM
Analog inputs possible.
Input devices + −
Input devices
COM
+ −
NC
CPU Unit with 10 I/O Points
CPU Unit with 10 I/O Points
CPU Unit with 10 I/O Points
Note: I4 and I5 (Ia and Ib for CPU Units with 20 I/O points) cannot be used as analog input terminals.
■ Changes Ratings and Specifications CPU Units Item
V2 Units
V1 Units
Pre-V1 Units
Rated power Models with DC supply voltage power supply
10.8 to 28.8 VDC
20.4 to 26.4 VDC
Power consumption
See Ratings on page 7.
30 VA max. (with 3 Expansion I/O Units connected)
Models with AC power supply Models with DC power supply
6.5 W max. (with 3 Expansion I/O Units connected)
Inrush current Models with AC power supply
Models with 10 I/O points: 4.5 A max. Models with 20 I/O points: 4.5 A max.
40 A max.
Models with DC power supply
Models with 10 I/O points: 30 A max. Models with 20 I/O points: 30 A max.
20 A max.
DC inputs I0 to I3 (See note 1.)
Input impedance
5.3 kΩ
5 kΩ
ON voltage
8 VDC min.
16 VDC min.
Input common
Independent common terminal
4.8 kΩ Internally connected to power supply terminal
Programmable Relay ZEN V2 Units
29
Page 30
Item DC inputs I4 to I5 (See note 2.)
V2 Units
V1 Units
Input impedance
5.2 to 5.5 kΩ
ON voltage
8 VDC min.
16 VDC min.
OFF voltage
3 VDC max.
5 VDC max.
Pre-V1 Units
5 kΩ
Analog inputs Input impedance I4 to I5 Accuracy (See note 2.)
100 kΩ min.
150 kΩ min.
±1.5% FS (at ambient operating temperature within rated range)
±10% FS (at ambient operating temperature within rated range)
Control outputs
8 A per output Total for all outputs must be as follows: Units with 10 I/O Points: 20 A max. (15 A max. for Communications-type CPU Units) Units with 20 I/O Points: 40 A max.
8 A per output
Relay outputs
Transistor outputs 28.8 V max.
26.4 V max.
Timing accuracy of weekly and calendar timers
±15 s or less per month (at 25°C)
±2 min per month
Mounting direction
Standard (vertical) installation and horizontal installation Standard (vertical) installation
Terminal block tightening torque
0.565 to 0.6 N·m (5 to 5.3 in-lb)
Connectable Expansion I/O Units
ZEN-8E1@ (See note 3.)
ZEN-4E@ and ZEN-8E@
Case structure
No heat slits
Heat slits
0.5 to 0.6 N·m
Note: 1. Units with 20 I/O Points: I0 to I9 2. Units with 20 I/O Points: Ia to Ib 3. Refer to page 32 for details on compatible combinations of CPU Units and Expansion I/O Units.
Expansion I/O Units Item Model
8E1 type Unit with 8 I/O Points
AC inputs
DC inputs
4E/8E type Units with 4 input, 4 output, or 8 I/O points
Input impedance
680 kΩ
83 kΩ
Isolation
No isolation
Photocoupler
Input common
Internally connected to power supply terminal
Independent common terminal
Input voltage
10.8 to 28.8 VDC
20.4 to 26.4 VDC
Input impedance
6.5 kΩ
4.7 kΩ
Isolation
ZEN-8E1DR: No isolation ZEN-8E1DT: Photocoupler
Photocoupler
ON voltage
8 VDC min.
16 VDC min.
Input common
ZEN-8E1DR: Internally connected to power supply Independent common terminal terminal ZEN-8E1DT: Independent common terminal
Control output Relay outputs
Transistor outputs
8 A per output Total for all outputs must be as follows: Units with 10 I/O Points: 20 A max. Units with 20 I/O Points: 40 A max.
8 A per output
28.8 V max.
26.4 V max.
Mounting screws
M3 (mounting holes on DIN Track hooks)
M4 (mounting holes on Unit)
Connectable CPU Unit
V2 CPU Units (See note.)
V1 or Pre-V1 CPU Units
Dimensions (H × W × D)
90 × 35 × 56 mm
90 × 70 × 56 mm
Case structure
No heat slits
Heat slits
Note: Refer to page 32 for details on compatible combinations of CPU Units and Expansion I/O Units.
30