Spec sheet · Omron
Programmable Relay ZEN V2 Units
Spec sheet37 pagesPDF 1.8 MB
Catalog datasheet for the Omron ZEN V2 programmable relays, including the ZEN-10C1DR-D-V2 CPU Unit, with ratings and wiring.
Covers · 1 model
The models it covers
Summary
What is in it
Omron's catalog for the ZEN V2 programmable relay units, which provide relay, timer, counter and time switch functions in one compact unit. It covers features, the series configuration of CPU Units (standard LCD, LED, economy and RS-485 communications types), Expansion I/O Units, power supply and accessories, the model number legend and list of models (including the ZEN-10C1DR-D-V2), ratings, characteristics, input and output specifications and connection diagrams.
From the sheet
Key facts from this sheet
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
OMRON catalog for the ZEN V2 programmable relays: CPU Units with 10 or 20 I/O points, including the ZEN-10C1DR-D-V2, plus ZEN-8E1 Expansion I/O Units and the ZEN-PA03024 Power Supply Unit. It gives ratings, input and output specifications, wiring, accessories and precautions for choosing and installing a unit.
- Device
- ZEN-10C1DR-D-V2: Standard LCD-type programmable relay CPU Unit with 6 DC inputs, 4 relay outputs and DC power supply p. 4, 5
- Power supply
- DC-supply models: 12 to 24 VDC (ripple 5% max.), operating range 10.8 to 28.8 VDC p. 7
- Power consumption
- ZEN-10C@DR-D-V2: 3 W max., 4 W max. with three Expansion I/O Units p. 7
- DC inputs
- 10 I/O-point units, I0 to I3: 12 to 24 VDC, 4.5 mA typ. at 24 VDC, ON 8 VDC min., OFF 5 VDC max. p. 9
- Analog inputs
- DC-supply units, I4 and I5 on 10 I/O-point units: 0 to 10 V, 0.1 V resolution, ±1.5% FS accuracy p. 2, 10
- Relay outputs
- 250 VAC/8 A or 24 VDC/5 A resistive, 5 VDC/10 mA min.; 10 I/O-point CPU Units: 20 A max. total p. 11
- Relay life
- Electrical 50,000 operations (resistive or inductive load); mechanical 10 million p. 11
- Programming
- Ladder diagram, 96 lines (3 input conditions and 1 output per line) p. 8
- Expansion
- Up to 3 Expansion I/O Units of 4 inputs and 4 outputs each, 34 I/O points max. with a 10-point CPU Unit; the AC-input ZEN-8E1AR cannot connect to a DC-supply CPU Unit p. 5, 8, 34
- Display and buttons
- LCD types: 12 characters x 4 lines with backlight, 8 operation buttons p. 8
- Programming cable
- ZEN-CIF01 Connecting Cable (2 m RS-232C, 9-pin D-sub); CS1W-CIF31 USB-Serial Conversion Cable for computers without a serial port p. 2, 6
- Options
- Memory Cassette ZEN-ME01, Battery Unit ZEN-BAT01, Support Software ZEN-SOFT01-V4 p. 6, 29
- Memory backup
- Program in internal EEPROM; clock and holding data kept by super capacitor 2 days min. (25°C), or 10 years min. with the optional battery p. 8
- Size and weight
- 70 mm wide x 90 mm high; 10 I/O-point CPU Unit approx. 300 g max. p. 1, 8
What this sheet walks you through
- Decoding the CPU Unit and Expansion I/O Unit model numbers p. 4
- Model list, including the ZEN-STARTER02-V2 kit built on the ZEN-10C1DR-D-V2 p. 5
- Accessories and system configuration p. 6
- Ratings, characteristics and approved standards p. 7, 8, 9
- Input and output specifications of CPU and Expansion I/O Units p. 9, 10, 11
- Wiring inputs on AC-supply and DC-supply units, including analog devices p. 12, 13
- Expansion I/O Unit and Power Supply Unit dimensions p. 27
- Changes from V1 and pre-V1 units when switching p. 29
- Safe use: circuit design, wiring, handling and storage p. 34
Good to know
- On DC-supply units, connect the COM terminal before turning on the power supply. p. 13
- The supply voltage must reach its rated value within 4 s; a slow rise can prevent reset or cause unstable outputs. p. 13
- With positive (+) common (NPN) wiring, I4 and I5 cannot be used as analog inputs. p. 13
- Previous Expansion I/O Units cannot be connected to V2 CPU Units. p. 29
- If self-diagnosis finds an error, operation stops and all outputs turn off. p. 34
Questions this sheet answers
What power supply does the ZEN-10C1DR-D-V2 need?
12 to 24 VDC, with an operating range of 10.8 to 28.8 VDC. It draws 3 W max. without Expansion I/O Units. p. 5, 7
How many I/O points does the ZEN-10C1DR-D-V2 have?
6 inputs and 4 outputs, expandable to 34 I/O points with up to three Expansion I/O Units. p. 4, 5, 8
Can older ZEN expansion units be used with a ZEN V2 CPU Unit?
No. Previous Expansion I/O Units cannot be connected to V2 CPU Units. p. 29
How long does a ZEN keep its clock without power?
The super capacitor holds the clock and holding data for 2 days min. at 25°C; the optional battery lasts 10 years min. p. 8
How do I connect a ZEN to a computer without a serial port?
Connect an OMRON CS1W-CIF31 USB-Serial Conversion Cable to the ZEN-CIF01 Connecting Cable. p. 2
The whole text · 4 parts
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file