The text of a manual · part 2 of 2
ZEN Programmable Relays (New Product News), page 8
Page 8 of 8
The original document is the PDF (4.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron ZEN-10C1AR-A-V1 /AC100
Page 8
Models
Precautions when Selecting ZEN Programmable Relays Differences between V1 and Pre-V1 CPU Units Data Area Comparisons
Password Function (LCD-type CPU Units Only) V1 CPU Units
CPU Unit
ZEN-10C
-
Pre-V1 CPU Units
-V1 ZEN-20C
-
-V1
ZEN-10C
-
CPU Unit input bits
I0 to I5 (6 points)
I0 to Ib (12 points)
I0 to 5b (6 points)
CPU Unit output bits
Q0 to Q3 (4 points)
Q0 to Q7 (8 points)
Q0 to Q3 (4 points)
No. of I/O points
Power supply
ZEN-10C1AR-A-V1
10
AC
6
AC
ZEN-10C2AR-A-V1
10
AC
6
AC
ZEN-10C1DR-D-V1
10
DC
6
ZEN-10C2DR-D-V1
10
DC
ZEN-10C1DT-D-V1
10
DC
10 20
Model
In addition to the password-protected items in existing models, password protection is also provided for the Program All Clear operation in the V1 CPU Units.
ZEN-10C2DT-D-V1 ZEN-20C1AR-A-V1
Items Protected by Password (0000 to 9999)
Unit name
CPU Unit
Outputs
LCD
Calendar/ clock
4
Relay
Yes
Yes
4
Relay
No
No
DC
4
Relay
Yes
Yes
6
DC
4
Relay
No
No
6
DC
4
Transistor
Yes
Yes
DC AC
6 12
DC AC
4 8
Transistor Relay
No Yes
No Yes
Inputs
Timers
T0 to Tf (16 points)
T0 to T7 (8 points)
ZEN-20C2AR-A-V1
20
AC
12
AC
8
Relay
No
No
Holding timers
#0 to #7 (8 points)
#0 to #3 (4 points)
ZEN-20C1DR-D-V1
20
DC
12
DC
8
Relay
Yes
Yes
Counters
C0 to Cf (16 points)
C0 to C7 (8 points)
ZEN-20C2DR-D-V1
20
DC
12
DC
8
Relay
No
No
Weekly timers
@0 to @f (16 points)
@0 to @7 (8 points)
ZEN-20C1DT-D-V1
20
DC
12
DC
8
Transistor
Yes
Yes
DC
Transistor
No
No
Calendar timers
0 to
Display bits
D0 to Df (16 points)
V1 Units
Pre-V1 Units
Editing ladder program
Editing ladder program f (8 points)
Program all clear
Ladder monitoring
ZEN-20C2DT-D-V1
20
D0 to D7 (8 points)
Ladder monitoring
Changing/clearing password
ZEN-8EAR
8
12 4
DC AC
8 4
Relay
Changing/clearing password
Changing backlight OFF time
ZEN-8EDR
8
4
DC
4
Relay
Setting input filter
ZEN-8EDT
8
4
DC
4
Transistor
Setting node number
ZEN-4EA
4
4
AC
4
DC 4
Relay f (16 points)
0 to
Work bits
M0 to Mf (16 points)
Holding bits
H0 to Hf (16 points)
Expansion I/O Unit input bits
X0 to Xb (12 points)
Expansion I/O Unit output bits
Y0 to Yb (12 points)
ZEN-4ED
4
Analog comparator bits
A0 to A3 (4 points)
ZEN-4ER
4
Comparator bits
P0 to Pf (16 points)
ZEN-ME01
Memory Cassette
ZEN-CIF01
Connecting Cable
ZEN-BAT01
Battery Unit
ZEN-SOFT01-V3
ZEN Support Software (CD-ROM)
ZEN-KIT01-EV3
Set containing CPU Unit (ZEN-10C1AR-A-V1), Support Software Connecting Cable, ZEN Support Software, and manual.
ZEN-KIT02-EV3
Set containing CPU Unit (ZEN-10C1DR-D-V1), Support Software Connecting Cable, ZEN Support Software, and manual.
Changing backlight OFF time Setting input filter Setting node number
Input Wiring (DC-type CPU Units Only) V1 CPU Units
Pre-V1 CPU Units
With Pre-V1 CPU Units, the input circuit common terminal is connected internally to the negative (–) side of the power supply circuit.
With V1 CPU Units, you can wire to either the negative (–) common or positive (+) common terminal. • Negative (–) COM Wiring
• Positive (+) COM Wiring
24 VDC, 6.5 W
24 VDC, 6.5 W COM wiring required.
Expansion I/O Unit
24 VDC, 6.5 W COM wiring required.
Analog inputs possible.
Analog inputs possible.
Input devices
Input devices
COM
Input devices
COM
CPU Unit with 10 I/O points
NC
CPU Unit with 10 I/O points
CPU Unit with 10 I/O points
Note: I4 and I5 cannot be used as analog input terminals.
Support Software and CPU Unit Combinations Support Software Version
CPU Unit
ZEN-SOFT01 Ver. 1.00
ZEN-SOFT01-V3 Ver. 3.00
Can be used.
Can be used.
Can be used.
10 I/O points
Can be used, with restrictions (See note.)
Can be used, with restrictions (See note.)
Can be used.
20 I/O points
Cannot be used.
Cannot be used.
Can be used.
Pre-V1 Units V1 Units
ZEN-SOFT01-V2 Ver. 2.00
Note: Only half of each of the timer, holding timer, counter, weekly timer, calendar timer, and display function areas can be used (i.e., the Pre-V1 bit range).
Difference between ZEN Programmable Relays and PLC Ladder Program Execution ZEN Programmable Relays I0
I1
ZEN executes the entire ladder program (up to 96 lines) from the first to last line at one time. Each row is executed in order from left to right starting from the left bus bar.
I2
0
[ Q0
Q0 1 I3 2
[ Q1
I4 3
TT0
T0 4
[ Q2
Bus bar
OMRON SYSMAC PLCs
Executed sequentially from the bus bar.
I0
I1
PLCs execute ladder programs one rung (circuit) at a time, starting with the top rung and executing it in order from the left. When the END instruction is reached, the program is executed again from the first rung.
I2
0
[ Q0
Q0 1 I3 2
[ Q1
I4 3
TT0
T0 4
[ Q2
END
The ON/OFF status produced by an output contact will not be used as the input contact status in the same cycle, but it can be used in the next cycle. I0
I0 0
M0 M0
1
Q0
I0 0
M0
M0 M0
1
Q0 1 cycle
14
When the following instructions are executed, Q0 turns ON/OFF at the same time as the other bits.
1 cycle
Q0
I0 M0 Q0
15