For the Optimation OL4054 and Optimation OL4058

Page 19

Optimation OptiLogic Driver Help

19 Requirements None

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.SET

Boolean

N/A

Write Only

16 Digital Output Module Digital outputs are used to turn loads on and off. Loads may be lights, motors, solenoids or any type of On/Off device. Digital outputs in the OptiLogic series come in three types: relay, transistor and solid state relay. Each type has applications it is best suited for. For more information, refer to the module manual. If there is a loss of communication with the host, the output module will enter a fail safe state. There are three types of states: fail safe to all outputs off, fail safe to a pattern and fail safe to last state. The time in which a fail safe state is entered after loss of communication can be delayed up to 25.5 seconds. If certain points need to be treated differently in fail safe mode, a pattern can be used to signify which points are turned on and which ones are turned off in fail safe mode.

Subtypes N/A

Address Types 16 Digital Output Fail Safe Type Fail Safe Pattern Fail Safe Time Fail Safe Set

16 Digital Output Addressing Specifications Syntax

Data Type

Range

Access

S<slot>:DO<point>

Boolean

0-7

Read/Write

S<slot>:DO<offset>*

Byte

0-1

Read/Write

S<slot>:DO<offset>*

Word, Short

0

Read/Write

S<slot>:DO<offset>*

DWord, Long

0

Read/Write

*Multiple points can be referenced through the use of this optional syntax. For more information, refer to Digital I/O Bit Mapping.

Examples Address

Value

Description

S1:DO0

1

Slot 1, point 0 (turn point 0 on).

S1:DO1 (as Byte)

255

Slot 1, byte 1 (turn points 8-15 on).

S1:DO0 (as Word)

0

Slot 1, word 0 (turn points 0-15 off).

S1:DO0 (as DWORD)

65535

Slot 1, DWord 0 (turn points 0-15 on).

Fail Safe Type Addressing There are three types of fail safe states: fail safe to all outputs off, fail safe to a pattern and fail safe to last state. These types may be specified by referencing FS.TYPE.

Values 1 = Fail safe to all outputs off 2 = Fail safe to the pattern contained in FS<point>.PATTERN 3 = Fail safe to last state

Requirements www. kepware.com

Page 20

Optimation OptiLogic Driver Help

20

None Important: The value specified in FS.TYPE is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.TYPE

Byte, Word, Short, DWord, Long*

N/A

Write Only

*The default data type is shown in bold.

Fail Safe Pattern Addressing Using a fail safe pattern, users can specify which points are set and which ones are cleared when in fail safe mode.

Values True = turn point on False = turn point off

Requirements FS.TYPE must be set to 2 for device to fail safe to a pattern. Note: If using Byte, Word, Short, DWord or Long data types, the bit pattern determines which points are turned on and which ones are turned off. Important: The pattern specified in FS.PATTERN is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>FS<point>.PATTERN

Boolean

0-7

Write Only

S<slot>:FS<offset>.PATTERN*

Byte

0-1

Write Only

S<slot>:FS<offset>.PATTERN*

Word, Short

0

Write Only

S<slot>:FS<offset>.PATTERN*

DWord, Long

0

Write Only

*Multiple points can be referenced through the use of this optional syntax. For more information, refer to Digital I/O Bit Mapping.

Examples Address

Value

Description

S1:FS0.PATTERN

1

Slot 1, turn point 0 on in fail safe mode.*

S1:FS1.PATTERN (as Byte)

255

Slot 1, turn points 8-15 on in fail safe mode.*

S1:FS0.PATTERN (as Word)

0

Slot 1, turn points 0-15on in fail safe mode.*

S1:FS0.PATTERN (as DWORD)

65535

Slot 1, turn points 0-15 on in fail safe mode.*

*See Notes and Requirements above.

Fail Safe Time Addressing After communication between the host and the RTU has been lost, a time delay may be introduced before fail safe mode is engaged for the output module. This time delay can be entered by referencing FS.TIME and is specified in tenths of seconds.

Requirements None Important: The value specified in FS.TYPE is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.TIME

Byte, Word, Short, DWord, Long

N/A

Write Only

Examples Address

Value

Description www. kepware.com

Page 21

Optimation OptiLogic Driver Help

21 S1:FS.TIME

255

Slot 1, fail safe time delay = 25.5 seconds.

S1:FS.TIME

0

Slot 1, no delay.

S1:FS.TIME

1

Slot 1, fail safe time delay = .1 seconds.

Fail Safe Set Addressing For any of the fail safe configuration parameters (type, time and pattern) to be sent to the device, FS.SET must be set. Immediately after the parameters are sent, FS.SET will be reset.

Values True = Send fail safe configurations to device False = No action

Requirements None

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.SET

Boolean

N/A

Write Only

24 Digital Output Module Digital outputs are used to turn loads on and off. Loads may be lights, motors, solenoids or any type of On/Off device. Digital outputs in the OptiLogic series come in three types: relay, transistor and solid state relay. Each type has applications it is best suited for. For more information, refer to the module manual. If there is a loss of communication with the host, the output module will enter a fail safe state. There are three types of states: fail safe to all outputs off, fail safe to a pattern and fail safe to last state. The time in which a fail safe state is entered after loss of communication can be delayed up to 25.5 seconds. If certain points need to be treated differently in fail safe mode, a pattern can be used to signify which points are turned on and which ones are turned off in fail safe mode.

Subtypes N/A

Address Types 24 Digital Output Fail Safe Type Fail Safe Pattern Fail Safe Time Fail Safe Set

24 Digital Output Addressing Specifications Syntax

Data Type

Range

Access

S<slot>:DO<point>

Boolean

0-7

Read/Write

S<slot>:DO<offset>*

Byte

0-2

Read/Write

S<slot>:DO<offset>*

Word, Short

0-1

Read/Write

S<slot>:DO<offset>*

DWord, Long

0

Read/Write

*Multiple points can be referenced through the use of this optional syntax. For more information, refer to Digital I/O Bit Mapping.

Examples Address

Value

Description

S1:DO0

1

Slot 1, point 0 (turn point 0 on).

S1:DO2 (as Byte)

255

Slot 1, byte 2 (turn points 16-23 on).

www. kepware.com

Page 22

Optimation OptiLogic Driver Help

22

S1:DO1 (as Word)

1

Slot 1, word 1 (turn point 16 on).

S1:DO0 (as DWORD)

16777216

Slot 1, DWord 0 (turn points 0-23 on).

Fail Safe Type Addressing There are three types of fail safe states: fail safe to all outputs off, fail safe to a pattern and fail safe to last state. These types may be specified by referencing FS.TYPE.

Values 1 = Fail safe to all outputs off 2 = Fail safe to the pattern contained in FS<point>.PATTERN 3 = Fail safe to last state

Requirements None Important: The value specified in FS.TYPE is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.TYPE

Byte, Word, Short, DWord, Long

N/A

Write Only

Fail Safe Pattern Addressing Using a fail safe pattern, users can specify which points are set and which ones are cleared when in fail safe mode.

Values True = turn point on False = turn point off

Requirements FS.TYPE must be set to 2 for device to fail safe to a pattern. Note: If using Byte, Word, Short, DWord or Long data types, the bit pattern determines which points are turned on and which ones are turned off. Important: The pattern specified in FS.PATTERN is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>FS<point>.PATTERN

Boolean

0-7

Write Only

S<slot>:FS<offset>.PATTERN*

Byte

0-2

Write Only

S<slot>:FS<offset>.PATTERN*

Word, Short

0-1

Write Only

S<slot>:FS<offset>.PATTERN*

DWord, Long

0

Write Only

*Multiple points can be referenced through the use of this optional syntax. For more information, refer to Digital I/O Bit Mapping

Examples Address

Value

Description

S1:FS0.PATTERN

1

Slot 1, turn point 0 on in fail safe mode.*

S1:FS2.PATTERN (as Byte)

255

Slot 1, turn points 16-23 on in fail safe mode.*

S1:FS1.PATTERN (as Word)

1

Slot 1, turn point 16 on in fail safe mode.*

S1:FS0.PATTERN (as DWORD)

16777216

Slot 1, turn points 0-23 on in fail safe mode.*

*See Notes and Requirements above.

Fail Safe Time Addressing After communication between the host and the RTU has been lost, a time delay may be introduced before fail safe mode is engaged for the output module. This time delay can be entered by referencing FS.TIME and is specified in tenths of seconds.

Requirements www. kepware.com

Page 23

Optimation OptiLogic Driver Help

23 None

Important: The value specified in FS.TYPE is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.TIME

Byte, Word, Short, DWord, Long

N/A

Write Only

Examples Address

Value

Description

S1:FS.TIME

255

Slot 1, fail safe time delay = 25.5 seconds.

S1:FS.TIME

0

Slot 1, no delay.

S1:FS.TIME

1

Slot 1, fail safe time delay = .1 seconds.

Fail Safe Set Addressing For any of the fail safe configuration parameters (type, time and pattern) to be sent to the device, FS.SET must be set. Immediately after the parameters are sent, FS.SET will be reset.

Values True = Send fail safe configurations to device False = No action

Requirements None

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.SET

Boolean

N/A

Write Only

32 Digital Output Module Digital outputs are used to turn loads on and off. Loads may be lights, motors, solenoids or any type of On/Off device. Digital outputs in the OptiLogic series come in three types: relay, transistor and solid state relay. Each type has applications it is best suited for. For more information, refer to the module manual. If there is a loss of communication with the host, the output module will enter a fail safe state. There are three types of states: fail safe to all outputs off, fail safe to a pattern and fail safe to last state. The time in which a fail safe state is entered after loss of communication can be delayed up to 25.5 seconds. If certain points need to be treated differently in fail safe mode, a pattern can be used to signify which points are turned on and which ones are turned off in fail safe mode.

Subtypes N/A

Address Types 32 Digital Output Fail Safe Type Fail Safe Pattern Fail Safe Time Fail Safe Set

32 Digital Output Addressing Specifications Syntax

Data Type

Range

Access

S<slot>:DO<point>

Boolean

0-7

Read/Write

S<slot>:DO<offset>*

Byte

0-3

Read/Write www. kepware.com

Page 24

Optimation OptiLogic Driver Help

24

S<slot>:DO<offset>*

Word, Short

0-1

Read/Write

S<slot>:DO<offset>*

DWord, Long

0

Read/Write

*Multiple points can be referenced through the use of this optional syntax. For more information, refer to Digital I/O Bit Mapping.

Examples Address

Value

Description

S1:DO0

1

Slot 1, point 0 (turn point 0 on).

S1:DO0 (as Byte)

255

Slot 1, byte 0 (turn points 0-7 on).

S1:DO1 (as Word)

1

Slot 1, word 1 (turn point 16 on).

S1:DO0 (as DWORD)

4294967295

Slot 1, DWord 0 (turn points 0-31 on).

Fail Safe Type Addressing There are three types of fail safe states: fail safe to all outputs off, fail safe to a pattern and fail safe to last state. These types may be specified by referencing FS.TYPE.

Values 1 = Fail safe to all outputs off 2 = Fail safe to the pattern contained in FS<point>.PATTERN 3 = Fail safe to last state

Requirements None Important: The value specified in FS.TYPE is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.TYPE

Byte, Word, Short, DWord, Long

N/A

Write Only

Fail Safe Pattern Addressing Using a fail safe pattern, users can specify which points are set and which ones are cleared when in fail safe mode.

Values True = turn point on False = turn point off

Requirements FS.TYPE must be set to 2 for device to fail safe to a pattern. Note: If using Byte, Word, Short, DWord or Long data types, the bit pattern determines which points are turned on and which ones are turned off. Important: The pattern specified in FS.PATTERN is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>FS<point>.PATTERN

Boolean

0-7

Write Only

S<slot>:FS<offset>.PATTERN*

Byte

0-3

Write Only

S<slot>:FS<offset>.PATTERN*

Word, Short

0-1

Write Only

S<slot>:FS<offset>.PATTERN*

DWord, Long

0

Write Only

*Multiple points can be referenced through the use of this optional syntax. For more information, refer to Digital I/O Bit Mapping.

Examples Address

Value

Description

S1:FS0.PATTERN

1

Slot 1, turn point 0 on in fail safe mode.*

S1:FS0.PATTERN (as Byte)

255

Slot 1, turn points 0-7 on in fail safe mode.* www. kepware.com

Page 25

Optimation OptiLogic Driver Help

25 S1:FS1.PATTERN (as Word)

1

Slot 1, turn point 16 on in fail safe mode.*

S1:FS0.PATTERN (as DWORD)

4294967295

Slot 1, turn points 0-31 on in fail safe mode.*

*See Notes and Requirements above

Fail Safe Time Addressing After communication between the host and the RTU has been lost, a time delay may be introduced before fail safe mode is engaged for the output module. This time delay can be entered by referencing FS.TIME and is specified in tenths of seconds.

Requirements None Important: The value specified in FS.TYPE is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.TIME

Byte, Word, Short, DWord, Long

N/A

Write Only

Examples Address

Value

Description

S1:FS.TIME

255

Slot 1, fail safe time delay = 25.5 seconds.

S1:FS.TIME

0

Slot 1, no delay.

S1:FS.TIME

1

Slot 1, fail safe time delay = .1 seconds.

Fail Safe Set Addressing For any of the fail safe configuration parameters (type, time and pattern) to be sent to the device, FS.SET must be set. Immediately after the parameters are sent, FS.SET will be reset.

Values True = Send fail safe configurations to device False = No action

Requirements None

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.SET

Boolean

N/A

Write Only

2 Channel Analog Input Module

Analog inputs are used to monitor the value of continuously variable field measurements. Typical analog inputs are measurements of temperature, pressure, weight, liquid level, pH, flow rate and many other "real world" parameters. Each channel of an analog input module takes an analog signal as input and uses a 12-bit A/D converter to put that analog value in digital form.

Subtypes N/A

2 Channel Analog Input Addressing Specifications www. kepware.com

Page 26

Optimation OptiLogic Driver Help

26

Syntax

Data Type

Range

Access

S<slot>:AI<channel>

Word, Short, DWord, Long

1-2

Read Only

Examples Address

Value

Description

S1:AI1

*

Slot 1, channel 1.

S1:AI2

*

Slot 1, channel 2.

*Value depends on input level, voltage/current ranges, accuracy and so forth.

4 Channel Analog Input Module

Analog inputs are used to monitor the value of continuously variable field measurements. Typical analog inputs are measurements of temperature, pressure, weight, liquid level, pH, flow rate and many other "real world" parameters. Each channel of an analog input module takes an analog signal as input and uses a 12 bit A/D converter to put that analog value in digital form.

Subtypes N/A

4 Channel Analog Input Addressing Specifications Syntax

Data Type

Range

Access

S<slot>:AI<channel>

Word, Short, DWord, Long

1-4

Read Only

Examples Address

Value

Description

S1:AI2

*

Slot 1, channel 2.

S1:AI4

*

Slot 1, channel 4.

*Value depends on input level, voltage/current ranges, accuracy and so forth.

8 Channel Analog Input Module

Analog inputs are used to monitor the value of continuously variable field measurements. Typical analog inputs are measurements of temperature, pressure, weight, liquid level, pH, flow rate and many other "real world" parameters. Each channel of an analog input module takes an analog signal as input and uses a 12-bit A/D converter to put that analog value in digital form.

Subtypes OL2408, OL2418

8 Channel Analog Input Addressing Specifications www. kepware.com

Page 27

Optimation OptiLogic Driver Help

27 Syntax

Data Type

Range

Access

S<slot>:AI<channel>

Word, Short, DWord, Long

1-8

Read Only

Examples Address

Value

Description

S1:AI2

*

Slot 1, channel 2.

S1:AI8

*

Slot 1, channel 8.

*Values depend on input level, voltage/current ranges, accuracy and so forth.

16 Channel Analog Input Module

Analog inputs are used to monitor the value of continuously variable field measurements. Typical analog inputs are measurements of temperature, pressure, weight, liquid level, pH, flow rate and many other "real world" parameters. Each channel of an analog input module takes an analog signal as input and uses a 12-bit A/D converter to put that analog value in digital form.

Subtypes N/A

16 Channel Analog Input Addressing Specifications Syntax

Data Type

Range

Access

S<slot>:AI<channel>

Word, Short, DWord, Long

1-16

Read Only

Examples Address

Value

Description

S1:AI2

*

Slot 1, channel 2.

S1:AI16

*

Slot 1, channel 16.

*Values depend on input level, voltage/current ranges, accuracy and so forth.

2 Channel Analog Output Module

Each channel of an analog input module uses a 12 bit D/A converter to produce an analog output signal.

Subtypes N/A

2 Channel Analog Output Addressing Specifications www. kepware.com

Page 28

Optimation OptiLogic Driver Help

28

Syntax

Data Type

Range

Access

S<slot>:AO<channel>

Word, Short, DWord, Long

1-2

Write Only

Examples Address

Value

Description

S1:AO1

1024 *

Slot 1, channel 1.

S1:AO2

0*

Slot 1, channel 2.

*The exact analog output value depends on voltage range, accuracy and so forth.

4 Channel Analog Output Module

Each channel of an analog input module uses a 12 bit D/A converter to produce an analog output signal.

Subtypes OL2304

Address Types 4 Channel Analog Output 4 Channel Analog Output Range

4 Channel Analog Output Addressing Requirements As a precaution, the analog output range should be set prior to writing to an analog output channel.

Specifications Syntax

Data Type

Range

Access

S<slot>:AO<channel>

Word, Short, DWord, Long

1-4

Write Only

Examples Address

Value

Description

S1:AO2

1024 *

Slot 1, channel 2.

S1:AO4

0*

Slot 1, channel 4.

*The exact analog output value depends on voltage range, accuracy and so forth.

4 Channel Analog Output Range Addressing Each channel must be configured for a specific analog output range. This is done by setting AO<channel>.RANGE.

Values 0 = 0-5 V 1 = 0-10 V 2 = +/- 5 V 3 = +/- 10 V

Requirements None.

Specifications www. kepware.com