For the Optimation OL4054 and Optimation OL4058

Page 59

Optimation OptiLogic Driver Help

59 True = new data has been entered False = all data has been read from driver, no new data Syntax

Data Type

Range

Access

P:KDATAREADY

Boolean

N/A

Read Only

Keypad Arrow Max Addressing Panel keypad data entered via the arrows, can be upper bounded by referencing ARROW.MAX. Any keypad data entered above this max will automatically get set to this max value. Note: Initially, before ARROW.MAX is set, the upper limit internally to the device is 9999999999. When the limit is set, keypad data cannot exceed the size of ARROW.MAX which is 32 bits (DWord).

Specifications Syntax

Data Type

Range

Access

P:ARROW.MAX

DWord

N/A

Write Only

Keypad Arrow Min Addressing Panel keypad data entered via the arrows, can be lower bounded by referencing ARROW.MIN. Any keypad data entered below this min will automatically get set to this min value. Note: Initially, before ARROW.MIN is set, the lower limit internally to the device is 0.

Specifications Syntax

Data Type

Range

Access

P:ARROW.MIN

DWord

N/A

Write Only

4 Digital Output Module Digital outputs are used to turn loads on and off. Loads may be lights, motors, solenoids or any type of On/Off device. Digital outputs in the OptiLogic series come in three types: relay, transistor and solid state relay. Each type has applications it is best suited for. For more information, refer to the module manual. If there is a loss of communication with the host, the output module will enter a fail safe state. There are three types of states: fail safe to all outputs off, fail safe to a pattern and fail safe to last state. The time in which a fail safe state is entered after loss of communication can be delayed up to 25.5 seconds. If certain points need to be treated differently in fail safe mode, a pattern can be used to signify which points are turned on and which ones are turned off in fail safe mode.

Subtypes OL2104

Address Types 4 Digital Output Fail Safe Type Fail Safe Pattern Fail Safe Time Fail Safe Set

4 Digital Output Addressing Specifications Syntax

Data Type

Range

Access

S<slot>:DO<point>

Boolean

0-3

Read/Write

S<slot>:DO<offset>*

Byte**

0

Read/Write

S<slot>:DO<offset>*

Word, Short**

0

Read/Write

S<slot>:DO<offset>*

DWord, Long**

0

Read/Write www. kepware.com

Page 60

Optimation OptiLogic Driver Help

60

*Multiple points can be referenced through the use of this optional syntax. For more information, refer to Digital I/O Bit Mapping. **Since only the lower nibble of the least significant byte is being used, any value entered above 15 will be cropped.

Examples Address

Value

Description

S1:DO0

1

Slot 1, point 0 (turn point 0 on).

S1:DO0 (as Byte)

15

Slot 1, byte 0 (turn points 0-3 on).

S1:DO0 (as Word)

0

Slot 1, word 0 (turn all points off).

S1:DO0 (as DWORD)

15

Slot 1, DWord 0 (turn points 0-3 on).

Fail Safe Type Addressing There are three types of fail safe states: fail safe to all outputs off, fail safe to a pattern and fail safe to last state. These types may be specified by referencing FS.TYPE.

Values 1 = Fail safe to all outputs off 2 = Fail safe to the pattern contained in FS<point>.PATTERN 3 = Fail safe to last state

Requirements None Important: The value specified in FS.TYPE is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.TYPE

Byte, Word, Short, DWord, Long

N/A

Write Only

Fail Safe Pattern Addressing Using a fail safe pattern, users can specify which points are set and which ones are cleared when in fail safe mode.

Values True = turn point on False = turn point off

Requirements FS.TYPE must be set to 2 for device to fail safe to a pattern. Note: If using Byte, Word, Short, DWord or Long data types, the bit pattern determines which points are turned on and which ones are turned off. Important: The pattern specified in FS.PATTERN is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>FS<point>.PATTERN

Boolean

0-3

Write Only

S<slot>:FS<offset>.PATTERN*

Byte**

0

Write Only

S<slot>:FS<offset>.PATTERN*

Word, Short**

0

Write Only

S<slot>:FS<offset>.PATTERN*

DWord, Long**

0

Write Only

*Multiple points can be referenced through the use of this optional syntax. For more information, refer to Digital I/O Bit Mapping. **Since only the lower nibble of the least significant byte is being used, any value entered above 15 will be cropped.

Examples Address

Value

Description

S1:FS0.PATTERN

1

Slot 1, turn point 0 on in fail safe mode.*

S1:FS0.PATTERN (as Byte)

15

Slot 1, turn points 0-3 on in fail safe mode.* www. kepware.com

Page 61

Optimation OptiLogic Driver Help

61 S1:FS0.PATTERN (as Word)

0

Slot 1, turn points 0-3 off in fail safe mode.*

S1:FS0.PATTERN (as DWORD)

15

Slot 1, turn points 0-3 on in fail safe mode.*

*See Notes and Requirements above.

Fail Safe Time Addressing After communication between the host and the RTU has been lost, a time delay may be introduced before fail safe mode is engaged for the output module. This time delay can be entered by referencing FS.TIME and is specified in tenths of seconds.

Requirements None Important: The value specified in FS.TYPE is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.TIME

Byte, Word, Short, DWord, Long

N/A

Write Only

Examples Address

Value

Description

S1:FS.TIME

255

Slot 1, fail safe time delay = 25.5 seconds.

S1:FS.TIME

0

Slot 1, no delay.

S1:FS.TIME

1

Slot 1, fail safe time delay = .1 seconds.

Fail Safe Set Addressing For any of the fail safe configuration parameters (type, time and pattern) to be sent to the device, FS.SET must be set. Immediately after the parameters are sent, FS.SET will be reset.

Values True = Send fail safe configurations to device False = No action

Requirements None

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.SET

Boolean

N/A

Write Only

8 Digital Output Module Digital outputs are used to turn loads on and off. Loads may be lights, motors, solenoids or any type of On/Off device. Digital outputs in the OptiLogic series come in three types: relay, transistor and solid state relay. Each type has applications it is best suited for. For more information, refer to the module manual. If there is a loss of communication with the host, the output module will enter a fail safe state. There are three types of states: fail safe to all outputs off, fail safe to a pattern and fail safe to last state. The time in which a fail safe state is entered after loss of communication can be delayed up to 25.5 seconds. If certain points need to be treated differently in fail safe mode, a pattern can be used to signify which points are turned on and which ones are turned off in fail safe mode.

Subtypes OL2108, OL2109, OL2111

Address Types 8 Digital Output www. kepware.com

Page 62

Optimation OptiLogic Driver Help

62

Fail Safe Type Fail Safe Pattern Fail Safe Time Fail Safe Set

8 Digital Output Addressing Specifications Syntax

Data Type

Range

Access

S<slot>:DO<point>

Boolean

0-7

Read/Write

S<slot>:DO<offset>*

Byte

0

Read/Write

S<slot>:DO<offset>*

Word, Short

0

Read/Write

S<slot>:DO<offset>*

DWord, Long

0

Read/Write

*Multiple points can be referenced through the use of this optional syntax. For more information, refer to Digital I/O Bit Mapping.

Examples Address

Value

Description

S1:DO0

1

Slot 1, point 0 (turn point 0 on).

S1:DO0 (as Byte)

255

Slot 1, byte 0 (turn points 0-7 on).

S1:DO0 (as Word)

0

Slot 1, word 0 (turn points 0-7 off).

S1:DO0 (as DWORD)

255

Slot 1, DWord 0 (turn points 0-7 on).

Fail Safe Type Addressing There are three types of fail safe states: fail safe to all outputs off, fail safe to a pattern and fail safe to last state. These types may be specified by referencing FS.TYPE.

Values 1 = Fail safe to all outputs off 2 = Fail safe to the pattern contained in FS<point>.PATTERN 3 = Fail safe to last state

Requirements None Important: The value specified in FS.TYPE is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.TYPE

Byte, Word, Short, DWord, Long

N/A

Write Only

Fail Safe Pattern Addressing Using a fail safe pattern, users can specify which points are set and which ones are cleared when in fail safe mode.

Values True = turn point on False = turn point off

Requirements FS.TYPE must be set to 2 for device to fail safe to a pattern. Note: If using Byte, Word, Short, DWord or Long data types, the bit pattern determines which points are turned on and which ones are turned off. Important: The pattern specified in FS.PATTERN is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>FS<point>.PATTERN

Boolean

0-7

Write Only

S<slot>:FS<offset>.PATTERN*

Byte

0

Write Only

S<slot>:FS<offset>.PATTERN*

Word, Short

0

Write Only

S<slot>:FS<offset>.PATTERN*

DWord, Long

0

Write Only www. kepware.com

Page 63

Optimation OptiLogic Driver Help

63

*Multiple points can be referenced through the use of this optional syntax. For more information, refer to Digital I/O Bit Mapping.

Examples Address

Value

Description

S1:FS0.PATTERN

1

Slot 1, turn point 0 on in fail safe mode.*

S1:FS0.PATTERN (as Byte)

255

Slot 1, turn points 0-7 on in fail safe mode.*

S1:FS0.PATTERN (as Word)

0

Slot 1, turn point 0-7 off in fail safe mode.*

S1:FS0.PATTERN (as DWORD)

255

Slot 1, turn points 0-7 on in fail safe mode.*

*See Notes and Requirements above.

Fail Safe Time Addressing After communication between the host and the RTU has been lost, a time delay may be introduced before fail safe mode is engaged for the output module. This time delay can be entered by referencing FS.TIME and is specified in tenths of seconds.

Requirements None Important: The value specified in FS.TYPE is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.TIME

Byte, Word, Short, DWord, Long

N/A

Write Only

Examples Address

Value

Description

S1:FS.TIME

255

Slot 1, fail safe time delay = 25.5 seconds.

S1:FS.TIME

0

Slot 1, no delay.

S1:FS.TIME

1

Slot 1, fail safe time delay = .1 seconds.

Fail Safe Set Addressing For any of the fail safe configuration parameters (type, time and pattern) to be sent to the device, FS.SET must be set. Immediately after the parameters are sent, FS.SET will be reset.

Values True = Send fail safe configurations to device False = No action

Requirements None

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.SET

Boolean

N/A

Write Only

8 Digital Output Module www. kepware.com

Page 64

Optimation OptiLogic Driver Help

64 Digital outputs are used to turn loads on and off. Loads may be lights, motors, solenoids or any type of On/Off device. Digital outputs in the OptiLogic series come in three types: relay, transistor and solid state relay. Each type has applications it is best suited for. For more information, refer to the module manual. If there is a loss of communication with the host, the output module will enter a fail safe state. There are three types of states: fail safe to all outputs off, fail safe to a pattern and fail safe to last state. The time in which a fail safe state is entered after loss of communication can be delayed up to 25.5 seconds. If certain points need to be treated differently in fail safe mode, a pattern can be used to signify which points are turned on and which ones are turned off in fail safe mode.

Subtypes OL2108, OL2109, OL2111

Address Types 8 Digital Output Fail Safe Type Fail Safe Pattern Fail Safe Time Fail Safe Set

8 Digital Output Addressing Specifications Syntax

Data Type

Range

Access

S<slot>:DO<point>

Boolean

0-7

Read/Write

S<slot>:DO<offset>*

Byte

0

Read/Write

S<slot>:DO<offset>*

Word, Short

0

Read/Write

S<slot>:DO<offset>*

DWord, Long

0

Read/Write

*Multiple points can be referenced through the use of this optional syntax. For more information, refer to Digital I/O Bit Mapping.

Examples Address

Value

Description

S1:DO0

1

Slot 1, point 0 (turn point 0 on).

S1:DO0 (as Byte)

255

Slot 1, byte 0 (turn points 0-7 on).

S1:DO0 (as Word)

0

Slot 1, word 0 (turn points 0-7 off).

S1:DO0 (as DWORD)

255

Slot 1, DWord 0 (turn points 0-7 on).

Fail Safe Type Addressing There are three types of fail safe states: fail safe to all outputs off, fail safe to a pattern and fail safe to last state. These types may be specified by referencing FS.TYPE.

Values 1 = Fail safe to all outputs off 2 = Fail safe to the pattern contained in FS<point>.PATTERN 3 = Fail safe to last state

Requirements None Important: The value specified in FS.TYPE is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.TYPE

Byte, Word, Short, DWord, Long

N/A

Write Only

Fail Safe Pattern Addressing www. kepware.com

Page 65

Optimation OptiLogic Driver Help

65

Using a fail safe pattern, users can specify which points are set and which ones are cleared when in fail safe mode.

Values True = turn point on False = turn point off

Requirements FS.TYPE must be set to 2 for device to fail safe to a pattern. Note: If using Byte, Word, Short, DWord or Long data types, the bit pattern determines which points are turned on and which ones are turned off. Important: The pattern specified in FS.PATTERN is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>FS<point>.PATTERN

Boolean

0-7

Write Only

S<slot>:FS<offset>.PATTERN*

Byte

0

Write Only

S<slot>:FS<offset>.PATTERN*

Word, Short

0

Write Only

S<slot>:FS<offset>.PATTERN*

DWord, Long

0

Write Only

*Multiple points can be referenced through the use of this optional syntax. For more information, refer to Digital I/O Bit Mapping.

Examples Address

Value

Description

S1:FS0.PATTERN

1

Slot 1, turn point 0 on in fail safe mode.*

S1:FS0.PATTERN (as Byte)

255

Slot 1, turn points 0-7 on in fail safe mode.*

S1:FS0.PATTERN (as Word)

0

Slot 1, turn point 0-7 off in fail safe mode.*

S1:FS0.PATTERN (as DWORD)

255

Slot 1, turn points 0-7 on in fail safe mode.*

*See Notes and Requirements above.

Fail Safe Time Addressing After communication between the host and the RTU has been lost, a time delay may be introduced before fail safe mode is engaged for the output module. This time delay can be entered by referencing FS.TIME and is specified in tenths of seconds.

Requirements None Important: The value specified in FS.TYPE is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.TIME

Byte, Word, Short, DWord, Long

N/A

Write Only

Examples Address

Value

Description

S1:FS.TIME

255

Slot 1, fail safe time delay = 25.5 seconds.

S1:FS.TIME

0

Slot 1, no delay.

S1:FS.TIME

1

Slot 1, fail safe time delay = .1 seconds.

Fail Safe Set Addressing For any of the fail safe configuration parameters (type, time and pattern) to be sent to the device, FS.SET must be set. Immediately after the parameters are sent, FS.SET will be reset.

Values True = Send fail safe configurations to device False = No action www. kepware.com

Page 66

Optimation OptiLogic Driver Help

66

Requirements None

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.SET

Boolean

N/A

Write Only

8 Digital Output Module Digital outputs are used to turn loads on and off. Loads may be lights, motors, solenoids or any type of On/Off device. Digital outputs in the OptiLogic series come in three types: relay, transistor and solid state relay. Each type has applications it is best suited for. For more information, refer to the module manual. If there is a loss of communication with the host, the output module will enter a fail safe state. There are three types of states: fail safe to all outputs off, fail safe to a pattern and fail safe to last state. The time in which a fail safe state is entered after loss of communication can be delayed up to 25.5 seconds. If certain points need to be treated differently in fail safe mode, a pattern can be used to signify which points are turned on and which ones are turned off in fail safe mode.

Subtypes OL2108, OL2109, OL2111

Address Types 8 Digital Output Fail Safe Type Fail Safe Pattern Fail Safe Time Fail Safe Set

8 Digital Output Addressing Specifications Syntax

Data Type

Range

Access

S<slot>:DO<point>

Boolean

0-7

Read/Write

S<slot>:DO<offset>*

Byte

0

Read/Write

S<slot>:DO<offset>*

Word, Short

0

Read/Write

S<slot>:DO<offset>*

DWord, Long

0

Read/Write

*Multiple points can be referenced through the use of this optional syntax. For more information, refer to Digital I/O Bit Mapping.

Examples Address

Value

Description

S1:DO0

1

Slot 1, point 0 (turn point 0 on).

S1:DO0 (as Byte)

255

Slot 1, byte 0 (turn points 0-7 on).

S1:DO0 (as Word)

0

Slot 1, word 0 (turn points 0-7 off).

S1:DO0 (as DWORD)

255

Slot 1, DWord 0 (turn points 0-7 on).

Fail Safe Type Addressing There are three types of fail safe states: fail safe to all outputs off, fail safe to a pattern and fail safe to last state. These types may be specified by referencing FS.TYPE.

Values 1 = Fail safe to all outputs off 2 = Fail safe to the pattern contained in FS<point>.PATTERN 3 = Fail safe to last state

Requirements None www. kepware.com

Page 67

Optimation OptiLogic Driver Help

67

Important: The value specified in FS.TYPE is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.TYPE

Byte, Word, Short, DWord, Long

N/A

Write Only

Fail Safe Pattern Addressing Using a fail safe pattern, users can specify which points are set and which ones are cleared when in fail safe mode.

Values True = turn point on False = turn point off

Requirements FS.TYPE must be set to 2 for device to fail safe to a pattern. Note: If using Byte, Word, Short, DWord or Long data types, the bit pattern determines which points are turned on and which ones are turned off. Important: The pattern specified in FS.PATTERN is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>FS<point>.PATTERN

Boolean

0-7

Write Only

S<slot>:FS<offset>.PATTERN*

Byte

0

Write Only

S<slot>:FS<offset>.PATTERN*

Word, Short

0

Write Only

S<slot>:FS<offset>.PATTERN*

DWord, Long

0

Write Only

*Multiple points can be referenced through the use of this optional syntax. For more information, refer to Digital I/O Bit Mapping.

Examples Address

Value

Description

S1:FS0.PATTERN

1

Slot 1, turn point 0 on in fail safe mode.*

S1:FS0.PATTERN (as Byte)

255

Slot 1, turn points 0-7 on in fail safe mode.*

S1:FS0.PATTERN (as Word)

0

Slot 1, turn point 0-7 off in fail safe mode.*

S1:FS0.PATTERN (as DWORD)

255

Slot 1, turn points 0-7 on in fail safe mode.*

*See Notes and Requirements above.

Fail Safe Time Addressing After communication between the host and the RTU has been lost, a time delay may be introduced before fail safe mode is engaged for the output module. This time delay can be entered by referencing FS.TIME and is specified in tenths of seconds.

Requirements None Important: The value specified in FS.TYPE is not sent to the device until FS.SET is set.

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.TIME

Byte, Word, Short, DWord, Long

N/A

Write Only

Examples Address

Value

Description

S1:FS.TIME

255

Slot 1, fail safe time delay = 25.5 seconds.

S1:FS.TIME

0

Slot 1, no delay.

S1:FS.TIME

1

Slot 1, fail safe time delay = .1 seconds.

www. kepware.com

Page 68

Optimation OptiLogic Driver Help

68

Fail Safe Set Addressing For any of the fail safe configuration parameters (type, time and pattern) to be sent to the device, FS.SET must be set. Immediately after the parameters are sent, FS.SET will be reset.

Values True = Send fail safe configurations to device False = No action

Requirements None

Specifications Syntax

Data Type

Range

Access

S<slot>:FS.SET

Boolean

N/A

Write Only

8 Digital Input Module

Digital input modules are used to monitor the state of discrete field devices. Typical digital inputs are connected to switches, buttons, digital outputs from other equipment, discrete level sensors, thermostats and other On/Off sensing devices. Digital status is sensed by a controller such as an OptiLogic system, by passing current through an input sensor. When the current is on, the input state is active. When there is no current, the state is inactive.

Subtypes OL2208, OL2211, OL2201

8 Digital Input Addressing Specifications Syntax

Data Type

Range

Access

S<slot>:DI<point>

Boolean

0-7

Read Only

S<slot>:DI<offset>*

Byte

0

Read Only

S<slot>:DI<offset>*

Word, Short

0

Read Only

S<slot>:DI<offset>*

DWord, Long

0

Read Only

*Multiple points can be referenced through the use of this optional syntax. For more information, refer to Digital I/O Bit Mapping.

Examples Address

Value

Description

S1:DI0

1

Slot 1, point 0 is on.

S1:DI0 (as Byte)

255

Slot 1, byte 0 (points 0-7 are on).

S1:DI0 (as Word)

0

Slot 1, word 0 (points 0-7 are off).

S1:DI0 (as DWORD)

255

Slot 1, DWord 0 (points 0-7 are on).

4 Digital Input Module www. kepware.com