EMD-FL-C-10 Current Monitoring Relay
Data Sheet
08/2004
Functions
Structure
Current monitoring of direct and alternating current in 1-phase networks with settable threshold values, starting override and response delay that can be set separately, fault memory and the following functions that can be selected with the rotary switch: – OVER overcurrent monitoring – UNDER undercurrent monitoring – WIN monitoring of the range between the thresholds MIN and MAX
Figure 1 1 2 3 4 5 6 7 8 9 10
102057_00_en
Structure
LED: Supply U LED: Threshold value MAX LED: Threshold value MIN LED: Output relay R Potentiometer START – starting override Potentiometer MAX Potentiometer MIN Potentiometer DELAY – response delay Rotary switch function Snap-on foot
1
Page 2
EMD-FL-C-10
Technical Data Power Supply Supply voltage Connection terminal blocks (electrically isolated) Tolerance Nominal frequency
24 V … 240 V AC/DC A1 - A2 -15% ... +10% AC / -20% ... +25% DC 48 Hz ... 400 Hz on request Nominal operational power
16.6 Hz 4.5 VA (1.5 W)
Measuring Input Time setting range for starting override Time setting range for response delay Measured value Measuring input Connection terminal blocks Overload capacity Input resistance Switching threshold
0 s … 10 s 0.1 s … 10 s DC, AC sinus (16.6 Hz … 400 Hz) 100 mA AC/DC 1 A AC/DC GND - I1(+) GND - I2(+) 800 mA 3A 470 mΩ 47 mΩ
– max. (relative to IN)
10% … 100%
– min. (relative to IN)
5% ... 95%
Accuracy Basic accuracy of scale end value Setting accuracy of scale end value Repeat accuracy Temperature influence
2
10 A AC/DC GND - I3(+) 12 A 5 mΩ
±5% ≤ 5% ≤ 2% ≤ 0.1%/K
102057_00_en
Page 3
EMD-FL-C-10
Contact Side (Output) Contact type Rated voltage in accordance with IEC 60664-1 Switching capacity
Floating PDT (2x) 250 V AC
– device mounted in row (spacing < 5 mm)
750 VA (3 A/250 V AC)
– device not mounted in row (spacing > 5 mm) Fusing Mechanical service life Electrical service life (ohmic load 1000 VA) Switching rate in accordance with IEC 60947-5-1
1250 VA (5 A/250 V AC) 5 A fast 20 x 106 cycles 2 x 105 cycles
– max. (with ohmic load 100 VA)
60/min.
– max. (with ohmic load 1000 VA)
6/min.
Climatic Data Ambient temperature – operation (IEC 60068-1/UL 508) – storage Relative humidity Climatic class in accordance with IEC 60721-3-3 Contamination class in accordance with IEC 60664-1 General Data Duty cycle Recovery time Surge voltage category in accordance with IEC 60664-1 Rated surge voltage Indicators Supply voltage applied: green LED Starting override: green LED Position of output relay: yellow LED Error in corresponding threshold: red LED Response delay in corresponding threshold: red LED
102057_00_en
-25°C … +55°C / -25°C … +40°C (-13°F ... 131°F / -13°F ... 104°F) -25°C … +70°C (-13°F ... 158°F) 15% … 85% 3K3 3
100% 500 ms III 4 kV
ON Flashes ON / OFF ON / OFF Flashes
3
Page 4
EMD-FL-C-10
Housing Material Degree of protection Mounting Installation position Dimensions (W x H x D) Weight Connection Terminal Blocks Touch-proof Degree of protection Torque, max. Conductor cross section
Polyamide PA 6.6, self-extinguishing IP40 On 35 mm DIN rails in accordance with EN 60715-35 As desired 22.5 mm x 90 mm x 113 mm (0.886 in. x 3.543 in. x 4.449 in.) approx. 160 g
Yes IP20 1 Nm
– with/without ferrule
1 x 0.5 … 2.5 mm2 (AWG 20 ... 14)
– without ferrule
1 x 4 mm2 (AWG 12)
– with/without ferrule
2 x 0.5 mm … 1.5 mm2 (AWG 20 ... 16)
– flexible without ferrule
2 x 2.5 mm2 (AWG 14)
Ordering Data Description Current monitoring relay
4
Order Designation EMD-FL-C-10
Order No. 28 66 02 2
102057_00_en
Page 5
EMD-FL-C-10
Installation
Connection Examples
Danger of fatal injury! Never carry out work on live parts! The monitoring module can be snapped onto all 35 mm DIN rails in accordance with EN 60715-35. An integrated wide range power supply unit allows voltage in the range of 24 V AC/DC to 240 V AC/DC to be connected.
Circuit Diagram
Figure 2
102057_00_en
Figure 3
Measuring range 100 mA (I1)
Figure 4
Measuring range 1 A (I2)
Circuit diagram
5
Page 6
EMD-FL-C-10
Functional Description When supply voltage U is applied, output relay R picks up (yellow LED REL lights up) and the start override (START) begins its count down (green LED U flashes). During start override, changes in the measured current have no effect on the position of the output relay. Once the start override duration has expired, the green LED U remains permanently lit. LEDs MIN and MAX flash alternately for all functions if the minimum value selected for the measured current is greater than the maximum value.
Figure 5
Measuring range 10 A (I3)
The desired function is set with the rotary switch (Figure 6): O= Overcurrent monitoring OVER U= Undercurrent monitoring UNDER W = Window function WIN / monitoring of the range between the thresholds MIN and MAX WL = WIN + LATCH / monitoring of the range between the thresholds MIN and MAX with fault memory UL = UNDER + LATCH / undercurrent monitoring with fault memory OL = OVER + LATCH / overcurrent monitoring with fault memory
Figure 6
6
Rotary switch
102057_00_en
Page 7
EMD-FL-C-10
Overcurrent Monitoring – OVER, OVER + LATCH
Figure 7
Overcurrent monitoring – OVER, OVER + LATCH
When the measured current exceeds the value set on the MAX regulator, the response delay (DELAY) starts to elapse (red LED MAX flashes). When the response delay has elapsed (red LED MAX lights up), output relay R drops out (yellow LED REL does not light up). If the measured current falls below the value set on the MIN regulator (red LED MAX does not light up), the output relay R picks up again (yellow LED REL lights up). If the fault memory is activated (OVER + LATCH) and the measured current has exceeded the value set on the MAX regulator by longer than the response delay set, output relay R does not pick up if the current sinks below the value set on the MIN regulator. After clearing the error (interrupting the supply voltage), output relay R picks up when the supply voltage is reconnected and the measuring cycle begins again after the start override duration has expired (START).
102057_00_en
Undercurrent Monitoring – UNDER, UNDER + LATCH
Figure 8
Undercurrent monitoring – UNDER, UNDER + LATCH
When the measured current falls below the value set on the MIN regulator, the response delay (DELAY) starts to elapse (red LED MIN flashes). When the response delay has elapsed (red LED MIN lights up), output relay R drops out (yellow LED REL does not light up). If the measured current falls below the value set on the MAX regulator, the output relay R picks up again (yellow LED REL lights up). If the fault memory is activated (UNDER + LATCH) and the measured current has dropped below the value set on the MIN regulator for longer than the response delay set, output relay R does not pick up if the current exceeds the value set on the MAX regulator. After clearing the error (interrupting the supply voltage), output relay R picks up when the supply voltage is reconnected and the measuring cycle begins again after the start override duration has expired (START).
7
Page 8
EMD-FL-C-10
Window Function – WIN, WIN + LATCH
Figure 9
If the fault memory is activated (WIN + LATCH) and the measured current has dropped below the value set on the MIN regulator for longer than the response delay set, output relay R does not pick up if the minimum value is exceeded. If the measured current has exceeded the value set on the MAX regulator by longer than the response delay set, output relay R also does not pick up if the current sinks below the maximum value. After clearing the error (interrupting the supply voltage), output relay R picks up when the supply voltage is reconnected and the measuring cycle begins again after the start override duration has expired (START).
Window function – WIN, WIN + LATCH
The output relay R picks up (yellow LED REL lights up) if the measured current exceeds the value set on the MIN regulator. When the measured current exceeds the value set on the MAX regulator, the response delay (DELAY) starts to elapse (red LED MAX flashes). When the response delay has elapsed (red LED MAX lights up), output relay R drops out (yellow LED REL does not light up). The output relay R picks up again (yellow LED REL lights up) when the measured current drops below the maximum value again (red LED MAX does not light up). If the measured current falls below the value set on the MIN regulator, the response delay (DELAY) starts to elapse (red LED MIN flashes). When the response delay has elapsed (red LED MIN lights up), output relay R drops out (yellow LED REL does not light up).
8
102057_00_en
Page 9
EMD-FL-C-10
© Phoenix Contact 08/2004 Technical modifications reserved
Make sure you always use the latest documentation. It can be downloaded at www.phoenixcontact.com.
Phoenix Contact Inc. P.O. Box 4100 Harrisburg, PA 17111-0100 USA 717-944-1300 717-944-1625 info@phoenixcon.com www.phoenixcon.com
9
102057_00_en