Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of EMD-FL-C-10 Current Monitoring Relay Data Sheet

Manual · Phoenix Contact

EMD-FL-C-10 Current Monitoring Relay Data Sheet

Manual9 pagesPDF 157 KB

Data sheet for the Phoenix Contact EMD-FL-C-10 current monitoring relay: functions, technical data, wiring and function modes.

Download the PDF157 KB

Covers · 1 model

The models it covers

Summary

What is in it

Phoenix Contact's data sheet for the EMD-FL-C-10 current monitoring relay, which monitors direct and alternating current in 1-phase networks with settable thresholds, starting override, response delay and fault memory. It lists the structure and controls, technical data for supply, measuring input, accuracy, contacts, climate, housing and terminals, ordering data, installation, circuit diagram and connection examples, and describes the OVER, UNDER and WIN functions with and without latch.

Its parts

  1. Functions
  2. Structure
  3. Technical Data
  4. Ordering Data
  5. Installation
  6. Circuit Diagram
  7. Connection Examples
  8. Functional Description

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Phoenix Contact data sheet (08/2004) for the EMD-FL-C-10 current monitoring relay. It covers the front panel, technical data, ordering data, connection examples for each measuring range, and how the overcurrent, undercurrent and window functions switch the output relay.

Device
Current monitoring relay for direct and alternating current in 1-phase networks p. 1
Measuring ranges
100 mA (I1), 1 A (I2), 10 A (I3) p. 5, 6
Supply voltage
24 V AC/DC to 240 V AC/DC, wide range p. 5
Functions
OVER, UNDER and WIN (between MIN and MAX), each with or without fault memory (LATCH) p. 1, 6
Front controls
START (starting override), MAX, MIN and DELAY potentiometers; rotary function switch p. 1
Rotary switch
O, U, W, WL, UL, OL p. 6
Indicators
Green supply LED, yellow output relay LED, red threshold LEDs p. 3
Mounting
Snaps onto 35 mm DIN rails per EN 60715-35 p. 5
Order number
28 66 02 2 p. 4
Fault reset
A latched fault clears by interrupting the supply voltage p. 7

What this manual walks you through

  • Front panel LEDs, potentiometers and rotary switch p. 1
  • Mounting and supply connection p. 5
  • Wiring for the 100 mA, 1 A and 10 A measuring ranges p. 5, 6
  • Choosing the function with the rotary switch p. 6
  • How the starting override works at power-up p. 6
  • Overcurrent monitoring, OVER and OVER + LATCH p. 7
  • Undercurrent monitoring, UNDER and UNDER + LATCH p. 7
  • Window function, WIN and WIN + LATCH p. 8

Good to know

  • Never work on live parts. p. 5
  • During the starting override, changes in the measured current do not affect the output relay. p. 6
  • LEDs MIN and MAX flash alternately if the MIN value is set higher than the MAX value. p. 6

Questions this manual answers

What current ranges does the EMD-FL-C-10 measure?

Three measuring ranges: 100 mA on input I1, 1 A on I2 and 10 A on I3, for AC or DC. p. 1, 5, 6

What supply voltage does the EMD-FL-C-10 need?

Its wide range power supply accepts 24 V AC/DC to 240 V AC/DC. p. 5

How do I reset a latched fault on the EMD-FL-C-10?

Interrupt the supply voltage; the output relay picks up when power returns and monitoring restarts after the starting override. p. 7

Why are the MIN and MAX LEDs flashing alternately?

The minimum value set for the measured current is greater than the maximum value. p. 6

What is the Phoenix Contact order number for the EMD-FL-C-10?

Order No. 28 66 02 2. p. 4

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Functions1
  2. Structure1
  3. Technical Data2
    1. Power Supply2
    2. Measuring Input2
    3. Accuracy2
    4. Contact Side (Output)3
    5. Climatic Data3
    6. General Data3
    7. Indicators3
    8. Housing4
    9. Connection Terminal Blocks4
  4. Ordering Data4
  5. Installation5
  6. Circuit Diagram5
  7. Connection Examples5
  8. Functional Description6
    1. Overcurrent Monitoring – OVER, OVER + LATCH7
    2. Undercurrent Monitoring – UNDER, UNDER + LATCH7
    3. Window Function – WIN, WIN + LATCH8

From the PDF’s own bookmarks.

The whole text · 1 part

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 91-9

The file

Revision and size

Revision102057_00_en, 08/2004
PublisherPhoenix Contact
Pages9
PDF157 KB
TextText from the PDF itself.

The first pages · 3 of 9

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 9
Page 2
Page 2of 9
Page 3
Page 3of 9

More documents · 1

For the same models