Page 1 of Phoenix Contact EMD-FL-C-10 Manual

Manual · Phoenix Contact

Phoenix Contact EMD-FL-C-10 Manual

Manual2 pagesPDF 230 KB

Both pages are below, each with its text.

Download the PDF230 KB

Covers · 1 model

The models it covers

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

A two-page installation sheet, in German, English, French and Spanish, for the Phoenix Contact EMD-FL-C-10 current monitoring relay. It gives the technical data, connection examples for the three measuring ranges, and how each monitoring function and its fault memory behaves.

Device
Current monitoring relay for direct and alternating current in 1-phase networks p. 1
Order number
28 66 02 2 p. 2
Supply voltage
24 to 240 V AC/DC, integrated wide range power supply p. 2
Measuring ranges
100 mA (input I1), 1 A (input I2), 10 A (input I3) p. 2
Functions
OVER (overcurrent), UNDER (undercurrent), WIN (range between MIN and MAX), each also with LATCH fault memory p. 2
Function selection
Rotary switch on the front p. 2
Adjustments
Potentiometers for START (start override), MAX, MIN and DELAY (response delay) p. 2
Output contact
Floating PDT p. 1
Mounting
Snaps onto 35 mm DIN rails per EN 60 715, any installation position p. 1, 2
Housing
Plastic, self-extinguishing p. 1
Indicators
Green LED for supply, yellow LED for output relay position, red LEDs for threshold error and response delay p. 1

What this manual walks you through

  • Identifying the LEDs, potentiometers and rotary switch p. 2
  • Mounting on a DIN rail and connecting the supply p. 2
  • Wiring for the 100 mA, 1 A and 10 A measuring ranges p. 2
  • Choosing the monitoring function with the rotary switch p. 2
  • Overcurrent monitoring, with and without fault memory p. 2
  • Undercurrent monitoring, with and without fault memory p. 2
  • Window monitoring between MIN and MAX p. 2
  • Clearing a latched fault p. 2

Good to know

  • Never work on the module while voltage is applied. p. 2
  • During the start override time, changes in the measured current do not move the output relay. p. 2
  • If the MIN setting is higher than the MAX setting, the MIN and MAX LEDs flash alternately. p. 2

Questions this manual answers

What supply voltage does the EMD-FL-C-10 need?

It has a wide range power supply that accepts 24 to 240 V AC/DC. p. 2

What current ranges can the EMD-FL-C-10 measure?

100 mA on input I1, 1 A on input I2 and 10 A on input I3. p. 2

How do I reset a latched fault on the EMD-FL-C-10?

Interrupt the supply voltage. When it is reconnected the output relay picks up and the measuring cycle restarts after the start override time. p. 2

Why are the MIN and MAX LEDs flashing alternately?

The minimum value has been set higher than the maximum value. p. 2

What is the order number of the EMD-FL-C-10?

28 66 02 2. p. 2

The file

Size and text

Pages2
PDF230 KB
TextText from the PDF itself.

Every page · 2

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Phoenix Contact EMD-FL-C-10 Manual

The text of page 1, from the PDF itself

DEUTSCH

vom Skalenendwert vom Skalenendwert

Lado de contacto (salida) 2 Tipo de contacto contacto conmutado sin potencial Tensión de dimensionamiento según IEC 664-1 Potencia de conmutación módulo alineado (separación < 5 mm) módulo no alineado (separación > 5 mm)

Côté contact (output) 2 Type de contacts inverseur sans potentiel Tension de dimensionnement selon CEI 664-1 Puissance de commutation appareil juxtaposé (distance < 5 mm) appareil non juxtaposé (distance > 5 mm)

Contact side (output) 2 Contact type floating PDT Rated voltage in acc. with IEC 664-1 Switching capacity device mounted in row (spacing < 5 mm) device not mounted in row (spacing > 5 mm)

Kontaktseite (Output) 2 Kontaktausführung potentialfreier Wechsler Bemessungsspannung nach IEC 664-1 Schaltleistung Gerät angereiht (Abstand < 5 mm) Gerät nicht angereiht (Abstand > 5 mm)

Protección por fusible Vida útil mecánica Vida útil eléctrica Número de maniobras

Fusibles Durée de vie mécanique Durée de vie électrique Fréquence de commutation

Fusing Mechanical service life Electrical service life Switching rate

Absicherung Mechanische Lebensdauer Elektrische Lebensdauer Schalthäufigkeit

operaciones operaciones (carga resistiva) según IEC 947-5-1 máx. (con carga resistiva) máx. (con carga resistiva) Categoría de sobretensiones según IEC 664-1 Tensión transitoria de dimensionamiento Datos climáticos Temperatura ambiente servicio (IEC 68-1/UL 508) almacenamiento Humedad relativa del aire Clase de clima según IEC 721-3-3 Grado de suciedad según IEC 664-1 Datos generales Duración de conexión Tiempo de recuperación Categoría de sobretensiones según IEC 664-1 Tensión transitoria de dimensionamiento Indicaciones Tensión de alimentación presente: LED verde Puenteo de arranque: LED verde Posición del relé de salida: LED amarillo Error del umbral correspondiente: LED rojo Retardo de reacción del umbral correspondiente: LED rojo Carcasa plástico, autoextinguible Grado de protección Montaje sobre carril de 35 mm según EN 60 715 Posición para el montaje discrecional Dimensiones (A x A x P) Peso aprox. Bornes de conexión protegidos contra contactos casuales Grado de protección Par de apriete máx. Sección de conductor con/sin puntera sin puntera con/sin puntera flexible sin puntera

Catégorie de surtension Tension de choc assignée Caractéristiques climatiques Température ambiante

(cycles) (cycles - charge ohmique) selon CEI 947-5-1 max. (charge ohmique) max. (charge ohmique) selon CEI 664-1

service (CEI 68-1/UL 508) stockage Humidité relative de l'air Classe d'atmosphère selon CEI 721-3-3 Degré de pollution selon CEI 664-1 Caractéristiques générales Durée enclenchement Temps de réarmement Catégorie de surtension selon CEI 664-1 Tension de choc assignée Signalisation Tension d'alimentation OK : LED verte Inhibition de démarrage : LED verte clignotante Relais de sortie activé : LED jaune Défaut du seuil concerné : LED rouge Temporisation de déclenchement du seuil concerné : LED rouge Boîtier plastique, auto-extinguible Indice de protection Montage sur profilé de 35 mm, selon EN 60 715 Emplacement du montage indifférent Dimensions (L x H x P) Poids env. Bornes protégées contre les contacts Indice de protection Couple de serrage max. Section du conducteur avec/sans embout sans embout avec/sans embout souple sans embout

Surge voltage category Rated surge voltage Climatic data Ambient temperature Relative humidity Climatic class Contamination class General data Duty cycle Recovery time Surge voltage category Rated surge voltage Displays

cycles cycles (ohmic load) in acc. with IEC 947-5-1 max. (with ohmic load) max. (with ohmic load) in acc. with IEC 664-1

operation (IEC 68-1/UL 508) storage in acc. with IEC 721-3-3 in acc. with IEC 664-1

in acc. with IEC 664-1

supply voltage applied: green LED starting override: green LED position of output relay: yellow LED error in corresponding threshold: red LED response delay in corresponding threshold: red LED Housing plastic, self-extinguishing Degree of protection Mounting on 35 mm DIN rails in acc. with EN 60 715 Installation position as desired Dimensions (W x H x D) Weight approx. Connecting terminal blocks touch-proof Degree of protection Torque max. Conductor cross section with/without ferrule without ferrule with/without ferrule flexible without ferrule

Überspannungskategorie Bemessungsstoßspannung Klimatische Daten Umgebungstemperatur

Schaltspiele Schaltspiele (ohmsche Last) nach IEC 947-5-1 max. (bei ohmscher Last) max. (bei ohmscher Last) nach IEC 664-1

Betrieb (IEC 68-1/UL 508) Lagerung Relative Luftfeuchtigkeit Klimaklasse nach IEC 721-3-3 Verschmutzungsgrad nach IEC 664-1 Allgemeine Daten Einschaltdauer Wiederbereitschaftszeit Überspannungskategorie nach IEC 664-1 Bemessungsstoßspannung Anzeigen Versorgungsspannung liegt an: grüne LED Anlaufüberbrückung: grüne LED Stellung des Ausgangsrelais: gelbe LED Fehler der entsprechenden Schwelle: rote LED Auslöseverzögerung der entsprechenden Schwelle: rote LED Gehäuse Kunststoff, selbstverlöschend Schutzart Montage auf 35 mm-Tragschiene nach EN 60 715 Einbaulage beliebig Abmessungen (B x H x T) Gewicht ca. Anschlussklemmen berührungssicher Schutzart Anzugdrehmoment max. Leiterquerschnitt mit/ohne Aderendhülse ohne Aderendhülse mit/ohne Aderendhülse flexibel ohne Aderendhülse

±5% ≤5% ≤2% ≤ 0,1 %/KOrdIN:W raE

Instrucción de montaje para el ingeniero eléctrico

710MA X 4010(% 0 )60MIN 395(% ) 70

DEL AY 10 W (s U W ) L UL

OFU NC OL TION 2526 18N&ge an

ng ch hu ER wac r r OV er ito (fo üb on R m m DE ro t St rren : UN Cu ramm ag

DiDMIU UDE LA YD I2 15 I33516

U U D LE X MAN D LE D MI LE R D LE X MA N MI

X)MAGN0ST AR 10 50 T (s 70 )AYA1 I1EL

Instruction d’installation pour l’électricien

<D

Installation notes for electrical personnel

FLA YGBmmagDiDE

Genauigkeit Grundgenauigkeit Einstellgenauigkeit Wiederholgenauigkeit Temperatureinfluss

of scale end value of scale end value

0 -1 -C02 2 L66 D-F . 28 EM . No

Einbauanleitung für den Elektroinstallateur

LE

X MAN D LE D MI LE R D LE X MA N MI

EL AY DE LA Y

Accuracy Basic accuracy Setting accuracy Repeat accuracy Temperature influence

de la déviation maximale de la déviation maximale

D

Art.-Nr.: 28 66 02 2

) I(N) % 95 I(N 0s 5 ...100% 0...1..10s ... it 0,2.Limit 10 e m / / Time elle / Lim it Ze / Ti w le ff Zeit ltschwel ha ch Schalts Sc <D

Précision Précision de base Précision de réglage Répétabilité Action de la température

0 … 10 s 0,1 … 10 s DC, AC Sinus / sine / seno (16,6…400 Hz) 100 mA AC/DC 1 A AC/DC 10 A AC/DC GND - I1(+) GND - I2(+) GND - I3(+) 800 mA 3A 12 A 470 mΩ 47 mΩ 5 mΩ 10 … 100 % 5 … 95 % III 4 kV

EMD-FL-C-10

LA Y

Precisión Precisión básica Precisión de ajuste Precisión de repetición Influencia de temperatura

24 … 240 V AC A1 - A2 -15 %...+10 % AC / -20 %...+25 % DC 48...400 Hz (16,6 Hz) 4,5 VA (1,5 W)

DE

Versorgung Versorgungsspannung Anschlussklemmen (galvanisch getrennt) Toleranz Nennfrequenz (auf Anfrage) Nennbetriebsleistung Messeingang 1 Anlaufüberbrückung Zeit-Einstellbereich Auslöseverzögerung Zeit-Einstellbereich Messgröße Messeingang Anschlussklemmen Überlastbarkeit Eingangswiderstand Schaltschwelle max. (bezogen auf IN) min. (bezogen auf IN) Überspannungskategorie nach IEC 60 664-1 Bemessungsstoßspannung

U

Power supply Supply voltage Connecting terminal blocks (electrically isolated) Tolerance Nominal frequency (on request) Nominal operational power Measuring input 1 Starting override time setting range Response delay time setting range Measured value Measuring input Connecting terminal blocks Overload capacity Input resistance Switching threshold max. (relative to IN) min. (relative to IN) Surge voltage category in acc. with IEC 60 664-1 Rated surge voltage

MAX

Alimentation Tension d'alimentation Bornes (avec isolation galvanique) Tolérance Fréquence nominale (sur demande) Puissance en régime nominal Entrée de mesure 1 Inhibition de démarrage plage de réglage du temps Temporisation de déclenchement plage de réglage du temps Grandeur mesurée Entrée mesure Bornes Surcharge admissible Impédance d'entrée Seuil de commutation max. (par rapport à IN) min. (par rapport à IN) Catégorie de surtension selon CEI 60 664-1 Tension de choc assignée

www.phoenixcontact.com

Current monitor

Alimentación Tensión de alimentación Bornes de conexión (separados galvánicamente) Tolerancia Frecuencia nominal (bajo consulta) Potencia nominal de servicio Entrada de medición 1 Puenteo de arranque tiempo-margen de ajuste Retardo de reacción tiempo-margen de ajuste Magnitud de medida Entrada de medición Bornes de conexión Capacidad de sobrecarga Resistencia de entrada Umbral de conmutación máx. (referido a IN) mín. (referido a IN) Categoría de sobretensiones según IEC 60 664-1 Tensión transitoria de dimensionamiento del valor final de escala del valor final de escala

EMD-FL-C-10 28 66 02 2

MIN

Technische Daten Artikel Nr.

REL

Technical data Order No.

Phoenix Contact GmbH & Co. KG D-32823 Blomberg, Germany Fax +49-(0)5235-341200, Tel. +49-(0)5235-300 TNR 9016306-00 / 07.2004

EMD-FL-C-10

Caractéristiques techniques Référence

O ld Ho LAY DE MIN MAX

28 A2

Überwachungsrelais 1. Funktionen

DEUTSCH

Datos técnicos Código

Stromüberwachung von Gleich- und Wechselstrom in 1-Phasennetzen mit einstellbaren Schwellwerten, getrennt einstellbarer Anlaufüberbrückung und Auslöseverzögerung, Fehlerspeicher und folgenden über Drehschalter wählbaren Funktionen:

  • OVER Überstromüberwachung
  • UNDER Unterstromüberwachung
  • WIN Überwachung des Bereiches zwischen Schwellen MIN und MAX

2x 250 V AC 750 VA (3 A/250 V AC) 1250 VA (5 A/250 V AC)

Monitoring relay 1. Functions

5 A flink / fast / rapide / rápido 20 x 106 2 x 105 (1000 VA) 60/min. ( 100 VA) 6/min. (1000 VA) III 4 kV -25 °C … + 55 °C / -25 °C … +40 °C -25 °C … +70 °C 15 % … 85 % 3K3 3 100 % 500 ms III 4 kV ON blinkt / flashes / clignote / parpadea ON / OFF ON / OFF blinkt / flashes / clignote / parpadea IP40

ENGLISH

ENGLISH

Current monitoring of direct and alternating current in 1-phase networks with settable threshold values, starting override and response delay that can be set separately, fault memory and the following functions that can be selected with the rotary switch:

  • OVER overcurrent monitoring
  • UNDER undercurrent monitoring
  • WIN monitoring of the range between the thresholds MIN and MAX

Relais de surveillance 1. Fonctions

FRANÇAIS

FRANÇAIS

Surveillance de courants continus et alternatifs pour réseaux monophasés avec seuil, hystérésis et temporisation de déclenchement réglables, mémoire de défauts et fonctions suivantes sélectionnables par commutateur rotatif.

  • Surveillance de la surintensité OVER
  • Surveillance de la sous-intensité UNDER
  • Surveillance « fenêtre » de la plage entre les seuils MIN et MAX

(22,5 x 90 x 113) mm 0,16 kg IP20 1 Nm 1 x 0,5 … 2,5 mm2 1 x 4 mm2 2 x 0,5 … 1,5 mm2 2 x 2,5 mm2

Relé de control 1. Funciones

ESPAÑOL

ESPAÑOL

Control de corriente para corriente continua y alterna en redes monofásicas con valores umbral ajustables, puenteo de arranque y retardo de reacción ajustables por separado, memoria de fallos y las siguientes funciones seleccionables mediante conmutador giratorio:

  • OVER Control de sobrecorriente
  • UNDER Control de mínimo de corriente
  • WIN Control del margen entre los umbrales MIN y MAX

Blockschaltbild / Block diagram/ Diagramme schématique / Esquema de conjunto

1 81 6 I11 0 0 mI21 AI31 0 A 1 5G N D A 1 A 22 62 8A2 4 - 2 4 0 VA C /D C© Phoenix Contact 20042 5

Page 2 of Phoenix Contact EMD-FL-C-10 Manual

The text of page 2, from the PDF itself

DEUTSCH

ENGLISH

Strom-Überwachungsrelais EMD-FL-C-10

Art.-Nr.: 28 66 02 2 1. Geräteansicht, -anschlüsse, -bedienungselemente (Abb. 1):

1 LED: Versorgung U 2 LED: Schwellwert MAX 3 LED: Schwellwert MIN 4 LED: Ausgangsrelais R 5 Potentiometer START –

INm7REL0L UL FU NC OL TIO 25 N1626 18E L A Y DE L A YAnlaufunterdrückung0DMIN28 A289765Abb./Fig. 1L1 L2 L3 N 24V∼ 0VL1 L2 L3 NL1 L2 L3 NA1 GND 15 I1 I2 I3A1 GND 15 I1 I2 I3151525A1 GND 15 I1 I2 I325152516 18 26 2816 18 26 2816 18 26 2825 26 28 16 18 A225 26 28 16 18 A225 26 28 16 18 A2Abb./Fig. 2aAbb./Fig. 2bAbb./Fig. 2c

U LED U LED MAX LED MIN OL

OVER+LATCHLED REL,R Max MinSTARTDELAY< DELAYDELAYSTARTAbb./Fig. 3

U LED U LED MAX LED MIN UL

UNDER+LATCHLED REL,R Max MinSTARTDELAY< DELAYDELAY

2. Installation (Fig. 2)

2. Installation (fig. 2)

Vorsicht: Niemals bei anliegender Spannung arbeiten! Lebensgefahr!

D

E L

) I(N) 5% N s . 9 % I( .10 s 5 .. 00 .1 0.. ...10it 0.. 0,2Limit 1 e / im / T e elle / Lim it im Zeit / T chwelle s Off Ze halt chw s ld c Ho LAY S halt Sc DE MINX MA

Auslöseverzögerung

9 Drehschalter Funktion 0 Rastfuß

2. Installation (Abb. 2)

A Y E L A YDE L A YMDiaMIN9

DE LA 10 Y W (s U W ) O

460(%5 )AXSTARTAbb./Fig. 4

U LED U LED MAX LED MIN WL

Danger! Never carry out work on live parts! Danger of fatal injury!

Réf. : 28 66 02 2 1. Vue et raccordement du module, éléments de commande pour appareils (fig. 1) : 1 LED : Alimentation U 6 Potentiomètre MAX 2 LED : Valeur de seuil MAX 7 Potentiomètre MIN 3 LED : Valeur de seuil MIN 8 Potentiomètre DELAY – 4 LED : Relais de sortie R temporisation de déclenchement 5 Potentiomètre START – inhibition 9 Fonction commutateur rotatif de démarrage 0 Pied encliquetable

Das Überwachungsmodul ist auf alle 35 mm-Tragschienen nach EN 60 715 aufrastbar.

The monitoring module can be snapped onto all 35 mm DIN rails in acc. with EN 60 715.

Le module de surveillance s'encliquette sur tous les profilés de 35 mm selon EN 60 715.

Ein integriertes Weitbereichsnetzteil ermöglicht einen Versorgungsspannungsanschluss im Bereich von 24...240 V AC/DC.

An integrated wide range power supply unit allows voltage in the range of 24...240 V AC/DC to be connected.

Il accepte une large plage de tension d'entrée, de 24 à 240 V AC/DC.

3. Anschlussbeispiele3. Connection examplesMax MinSTARTDELAY< DELAYDELAYAbb./Fig. 5

U LED U LED MAX LED MIN WL WIN+LATCH

LED REL,R Max MinSTARTDELAYSTARTDELAYSTARTAbb./Fig. 6

2. Instalación (Fig. 2)

Abb. 2a): Messbereich 100 mA (I1)

Fig. 2a)
Abb. 2b): Messbereich 1 A (I2) Abb. 2c): Messbereich 10 A (I3)

El módulo de control puede encajarse sobre todos los carriles de 35 mm según EN 60 715. Una fuente de alimentación de largo alcance integrada facilita una conexión de la tensión de alimentación en el margen de 24...240 V AC/DC.

3. Exemples de raccordement

3. Ejemplos de conexión

Fig. 2a) : plage de mesure 100 mA (I1)

Fig. 2a)
Margen de medición 100 mA (I1)

Measuring range 100 mA (I1)

Fig. 2b) : plage de mesure 1 A (I2)

Fig. 2b)
Margen de medición 1 A (I2)
Fig. 2b)
Measuring range 1 A (I2)

Fig. 2c) : plage de mesure 10 A (I3)

Fig. 2c)
Margen de medición 10 A (I3)
Fig. 2c)
Measuring range 10 A (I3)

4. Description du fonctionnement

4. Descripción funcional

4. Funktionsbeschreibung

4. Functional description

Mit dem Anlegen der Versorgungsspannung U zieht das Ausgangsrelais R an (gelbe LED REL leuchtet) und die Anlaufüberbrückung (START) beginnt abzulaufen (grüne LED U blinkt). Während der Anlaufüberbrückung haben Änderungen des gemessenen Stromes keinen Einfluss auf die Stellung des Ausgangsrelais. Nach Ablauf der Anlaufüberbrückung leuchtet die grüne LED U stetig. Bei allen Funktionen blinken die LEDs MIN und MAX wechselweise, falls der Minimalwert für den gemessenen Strom größer als der Maximalwert gewählt wurde. %) Mit dem Drehschalter 9 wird die gewünschte Funktion eingestellt: 0 7 DE O = Überstromüberwachung OVER LA 10 U = Unterstromüberwachung UNDER Y W (s U W ) W = Windowfunktion WIN / Überwachung des Bereiches L O UL zwischen den Schwellen MIN und MAX FU NC OL WL = WIN + LATCH / Überwachung des Bereiches zwischen TIO N den Schwellen MIN und MAX mit Fehlerspeicher 26 UL = UNDER + LATCH / Unterstromüberwachung mit Fehler18 28 speicher OL = OVER + LATCH / Überstromüberwachung mit Fehlerspeicher

When supply voltage U is applied, output relay R picks up (yellow LED REL lights up) and the start override (START) begins its count down (green LED U flashes). During start override, changes in the measured current have no effect on the position of the output relay. Once the start override duration has expired, the green LED U remains permanently lit. LEDs MIN and MAX flash alternately for all functions if the minimum value selected for the measured current is greater than the maximum value. %) The desired function is set with rotary switch 9: 7 0 DE O = Overcurrent monitoring OVER LA 10 U = Undercurrent monitoring UNDER Y W (s U W ) W = Window function WIN / monitoring of the range between L O UL the thresholds MIN and MAX FU NC OL WL = WIN + LATCH / monitoring of the range between the TIO N thresholds MIN and MAX with fault memory 26 UL = UNDER + LATCH / undercurrent monitoring with fault 18 28 memory OL = OVER + LATCH / overcurrent monitoring with fault memory

A la mise sous tension d'alimentation U, le relais de sortie R est armé (la LED REL jaune s'allume) et le temps d'inhibition de démarrage (START) commence à se dérouler (la LED verte U clignote). Durant ce temps d'inhibition, les variations du courant mesuré n'ont aucune influence sur la position du relais de sortie. Une fois ce temps écoulé, la LED verte U reste allumée en permanence. Si la valeur MIN de la plage est supérieure à la valeur MAX (erreur de l'utilisateur), les LED MIN et MAX clignotent alternativement, quelque soit la fonction sélectionnée. %) La fonction désirée se règle avec le commutateur rotatif 9 : 7 0 DE O = Surveillance de la surintensité OVER LA 10 U = Surveillance de la sous-intensité UNDER Y W (s U W ) W = Fonction fenêtre WIN / surveillance de la plage entre les L O UL seuils MIN et MAX FU NC OL WL = WIN + LATCH / surveillance de la plage entre les seuils TIO N MIN et MAX avec mémoire de défauts 26 UL = UNDER + LATCH / surveillance de la sous-intensité avec 18 28 mémoire de défauts OL = OVER + LATCH / surveillance de la surintensité avec mémoire de défauts

Al aplicar la tensión de alimentación U se excita el relé de salida R (el LED REL amarillo se enciende) y se inicia el puenteo de arranque (START) (el LED U verde parpadea). Durante el puenteo de arranque los cambios de la corriente medida no influyen en la posición del relé de salida. Una vez transcurrido el puenteo de arranque, el LED U verde emite luz permanente. En todas las funciones parpadean alternativamente los LEDs MIN y MAX, si el valor mínimo para la corriente medida ha sido elegido más alto que el valor máximo. % ) Con el conmutador giratorio 9 se ajusta la función deseada: 7 0 DE O = Control de sobrecorriente OVER LA 10 U = Control de mínimo de corriente UNDER Y W (s U W ) W = Función Window WIN / Control del margen entre los L O UL umbrales MIN y MAX FU NC OL WL = WIN + LATCH / Control del margen entre los umbrales TIO N MIN y MAX con memoria de fallos 26 UL = UNDER + LATCH / Control de mínimo de corriente con 18 28 memoria de fallos OL = OVER + LATCH / Control de sobrecorriente con memoria de fallos

4.1. Überstromüberwachung – OVER, OVER + LATCH (Abb.3)

4.1. Overcurrent monitoring – OVER, OVER + LATCH (Fig. 3)

4.1. Surveillance de la surintensité – OVER, OVER + LATCH (fig. 3)

4.1. Control de sobrecorriente – OVER, OVER + LATCH (Fig.3)

Wenn der gemessene Strom den am MAX-Regler eingestellten Wert überschreitet, beginnt die eingestellte Auslöseverzögerung (DELAY) abzulaufen (rote LED MAX blinkt). Nach Ablauf der Verzögerungszeit (rote LED MAX leuchtet) fällt das Ausgangsrelais R ab (gelbe LED REL leuchtet nicht). Sinkt der gemessene Strom unter den am MIN-Regler eingestellten Wert (rote LED MAX leuchtet nicht), zieht das Ausgangsrelais R wieder an (gelbe LED REL leuchtet).

When the measured current exceeds the value set on the MAX regulator, the response delay (DELAY) starts to elapse (red LED MAX flashes). When the response delay has elapsed (red LED MAX lights up), output relay R drops out (yellow LED REL does not light up). If the measured current falls below the value set on the MIN regulator (red LED MAX does not light up), the output relay R picks up again (yellow LED REL lights up).

Quand l'intensité mesurée dépasse la valeur réglée sur le commutateur MAX, la temporisation du déclenchement (DELAY) commence à se dérouler (la LED rouge MAX clignote). Une fois la temporisation écoulée (la LED rouge MAX est allumée), le relais de sortie R retombe (la LED jaune REL est éteinte). Si l'intensité mesurée passe au-dessous de la valeur réglée sur le commutateur MIN (la LED rouge MAX est éteinte), le relais de sortie R est armé (la LED jaune REL est allumée).

Si la corriente medida sobrepasa el valor ajustado en el regulador MAX, se inicia el retardo de reacción ajustado (DELAY) (el LED MAX rojo parpadea). Una vez transcurrido el tiempo de retardo (el LED MAX rojo se enciende), el relé de salida R se desexcita (el LED REL amarillo está apagado). Si la corriente medida desciende por debajo del valor ajustado en el regulador MIN (el LED MAX rojo está apagado), el relé de salida R se excita de nuevo (el LED REL amarillo se enciende).

Si la mémoire de défauts a été activée (OVER + LATCH) et si l'intensité mesurée a dépassé la valeur réglée sur le commutateur MAX plus longtemps que la temporisation de déclenchement réglée, le relais de sortie R n'est pas réarmé quand l'intensité passe au-dessous de la valeur réglée sur le commutateur MIN. Après correction du défaut (coupure de la tension d'alimentation), le relais de sortie R est réarmé lors de la remise sous tension d'alimentation et le cycle de mesure recommence avec l'écoulement du temps d'inhibition de démarrage réglé (START).

Si se ha activado la memoria de fallos (OVER + LATCH) y si la corriente medida ha sobrepasado el valor ajustado en el regulador MAX durante un tiempo superior al retardo de reacción ajustado, no se excita el relé de salida R si la corriente desciende por debajo del valor ajustado en el regulador MIN. Después de la reposición del fallo (interrupción de la tensión de alimentación), el relé de salida R se excita al volver a aplicar la tensión de alimentación, y el ciclo de medición vuelve a comenzar una vez transcurrido el puenteo de arranque ajustado (START).

Wurde der Fehlerspeicher aktiviert (OVER + LATCH) und hat der gemessene Strom länger als die eingestellte Auslöseverzögerung den am MAX-Regler eingestellten Wert überschritten, zieht das Ausgangsrelais R nicht an, wenn der Strom unter den am MIN-Regler eingestellten Wert absinkt. Nach dem Zurücksetzen des Fehlers (Unterbrechen der Versorgungsspannung), zieht das Ausgangsrelais R beim erneuten Anlegen der Versorgungsspannung an und der Messzyklus beginnt wieder mit dem Ablauf der eingestellten Anlaufüberbrückung (START).

If the fault memory is activated (OVER + LATCH) and the measured current has exceeded the value set on the MAX regulator by longer than the response delay set, output relay R does not pick up if the current sinks below the value set on the MIN regulator. After clearing the error (interrupting the supply voltage), output relay R picks up when the supply voltage is reconnected and the measuring cycle begins again after the start override duration has expired (START).

4.2. Unterstromüberwachung – UNDER, UNDER + LATCH (Abb.4)

4.2. Undercurrent monitoring – UNDER, UNDER + LATCH (Fig. 4)

4.2. Surveillance de la sous-intensité – UNDER, UNDER + LATCH (fig. 4)

4.2. Control de mínimo de corriente – UNDER, UNDER + LATCH (Fig.4)

Wenn der gemessene Strom unter den am MIN-Regler eingestellten Wert sinkt, beginnt die eingestellte Auslöseverzögerung (DELAY) abzulaufen (rote LED MIN blinkt). Nach Ablauf der Verzögerungszeit (rote LED MIN leuchtet) fällt das Ausgangsrelais R ab (gelbe LED REL leuchtet nicht). Überschreitet der gemessene Strom den am MAX-Regler eingestellten Wert, zieht das Ausgangsrelais R wieder an (gelbe LED REL leuchtet).

When the measured current falls below the value set on the MIN regulator, the response delay (DELAY) starts to elapse (red LED MIN flashes). When the response delay has elapsed (red LED MIN lights up), output relay R drops out (yellow LED REL does not light up). If the measured current falls below the value set on the MAX regulator, the output relay R picks up again (yellow LED REL lights up).

Quand l'intensité mesurée passe au-dessous de la valeur réglée sur le commutateur MIN, la temporisation du déclenchement (DELAY) commence à se dérouler (la LED rouge MIN clignote). Une fois la temporisation écoulée (la LED rouge MIN est allumée), le relais de sortie R retombe (la LED jaune REL est éteinte). Si l'intensité mesurée dépasse la valeur réglée sur le commutateur MAX, le relais de sortie R est réarmé (la LED jaune REL est allumée).

Si la corriente medida desciende por debajo del valor ajustado en el regulador MIN, se inicia el retardo de reacción ajustado (DELAY) (el LED MIN rojo parpadea). Una vez transcurrido el tiempo de retardo (el LED MIN rojo se enciende), el relé de salida R se desexcita (el LED REL amarillo está apagado). Si la corriente medida sobrepasa el valor ajustado en el regulador MAX, el relé de salida R se excita de nuevo (el LED REL amarillo se enciende).

Wurde der Fehlerspeicher aktiviert (UNDER + LATCH) und ist der gemessene Strom länger als die eingestellte Auslöseverzögerung unter den am MIN-Regler eingestellten Wert abgesunken, zieht das Ausgangsrelais R nicht an, wenn der Strom den am MAX-Regler eingestellten Wert überschreitet. Nach dem Zurücksetzen des Fehlers (Unterbrechen der Versorgungsspannung), zieht das Ausgangsrelais R beim erneuten Anlegen der Versorgungsspannung an und der Messzyklus beginnt wieder mit dem Ablauf der eingestellten Anlaufüberbrückung (START).

If the fault memory is activated (UNDER + LATCH) and the measured current has dropped below the value set on the MIN regulator for longer than the response delay set, output relay R does not pick up if the current exceeds the value set on the MAX regulator. After clearing the error (interrupting the supply voltage), output relay R picks up when the supply voltage is reconnected and the measuring cycle begins again after the start override duration has expired (START).

Si la mémoire de défauts a été activée (UNDER + LATCH) et si l'intensité mesurée est passée au-dessous de la valeur réglée sur le commutateur MIN plus longtemps que la temporisation de déclenchement réglée, le relais de sortie R n'est pas réarmé quand l'intensité dépasse la valeur réglée sur le commutateur MAX. Après correction du défaut (coupure de la tension d'alimentation), le relais de sortie R est réarmé lors de la remise sous tension d'alimentation et le cycle de mesure recommence avec l'écoulement du temps d'inhibition de démarrage réglé (START).

Si se ha activado la memoria de fallos (UNDER + LATCH) y si la corriente medida ha descendido por debajo del valor ajustado en el regulador MIN durante un tiempo superior al retardo de reacción ajustado, no se excita el relé de salida R si la corriente sobrepasa el valor ajustado en el regulador MAX. Después de la reposición del fallo (interrupción de la tensión de alimentación), el relé de salida R se excita al volver a aplicar la tensión de alimentación, y el ciclo de medición vuelve a comenzar una vez transcurrido el puenteo de arranque ajustado (START).

WIN+LATCH

LED REL,R

Código: 28 66 02 2 1. Conexiones y elementos de operación del módulo (Fig. 1): 1 LED: Alimentación U 6 Potenciómetro MAX 2 LED: Valor umbral MAX 7 Potenciómetro MIN 3 LED: Valor umbral MIN 8 Potenciómetro DELAY – 4 LED: Relé de salida R Retardo de reacción 5 Potenciómetro START – 9 Conmutador giratorio "Función" Supresión de arranque 0 Pie de encaje Atención: ¡No trabajar nunca con la tensión conectada! ¡Peligro de muerte!

Attention : Ne jamais travailler sur un module sous tension ! Danger de mort !

EMD-FL-C-103m

X MA D IN LE D M LE R D LE

DMINgraU ) AX U D &M LE<40 51(%00 )

U U D LE X MA D IN LE D M LE R D LE X A M

IN eMDMA XEMD-FL-C-10MAX MIN310Current monitor70ST AR 10 50 T (s 70 )

ng ch hu ER ac r r OV erw ito (fo üb on ER omnt m ND Strrre m: U Cugram

E L A YU23g anEMD-FL-C-10DiaA1 I1 GN D I2 15 I3<1

6 Potentiometer MAX 7 Potentiometer MIN 8 Potentiometer DELAY –

Order No.: 28 66 02 2 1. View of the device, equipment connections and operating elements (fig. 1): 1 LED: Supply U 6 Potentiometer max 2 LED: Threshold value max 7 Potentiometer min 3 LED: Threshold value min 8 Potentiometer DELAY – 4 LED: Output relay R response delay 5 Potentiometer START – 9 Rotary switch function start suppression 0 Snap-on foot

ESPAÑOL Relé de control de corriente EMD-FL-C-10

EMD-FL-C-10Ord:W

Relais de surveillance de l'intensité EMD-FL-C-10

EMD-FL-C-10

0 -1 -C02 2 FL66 D-. 28 o EM .N

FRANÇAIS

Current monitoring relay EMD-FL-C-10

4.3. Windowfunktion – WIN, WIN + LATCH (Abb.5/Abb.6)

4.3. Window function – WIN, WIN + LATCH (Fig. 5/Fig. 6)

4.3. Fonction fenêtre – WIN, WIN + LATCH (fig. 5/fig. 6)

4.3. Función Window – WIN, WIN + LATCH (Fig.5/Fig.6)

Das Ausgangsrelais R zieht an (gelbe LED REL leuchtet), wenn der gemessene Strom den am MIN-Regler eingestellten Wert überschreitet. Wenn der gemessene Strom den am MAX-Regler eingestellten Wert überschreitet, beginnt die eingestellte Auslöseverzögerung (DELAY) abzulaufen (rote LED MAX blinkt). Nach Ablauf der Verzögerungszeit (rote LED MAX leuchtet), fällt das Ausgangsrelais R ab (gelbe LED REL leuchtet nicht). Das Ausgangsrelais R zieht wieder an (gelbe LED REL leuchtet), wenn der gemessene Strom wieder unter den Maximumwert absinkt (rote LED MAX leuchtet nicht). Sinkt der gemessene Strom unter den am MIN-Regler eingestellten Wert, beginnt die eingestellte Auslöseverzögerung (DELAY) abzulaufen (rote LED MIN blinkt). Nach Ablauf der Verzögerungszeit (rote LED MIN leuchtet), fällt das Ausgangsrelais R ab (gelbe LED REL leuchtet nicht).

The output relay R picks up (yellow LED REL lights up) if the measured current exceeds the value set on the MIN regulator. When the measured current exceeds the value set on the MAX regulator, the response delay (DELAY) starts to elapse (red LED MAX flashes). When the response delay has elapsed (red LED MAX lights up), output relay R drops out (yellow LED REL does not light up). The output relay R picks up again (yellow LED REL lights up) when the measured current drops below the maximum value again (red LED MAX does not light up). If the measured current falls below the value set on the MIN regulator, the response delay (DELAY) starts to elapse (red LED MIN flashes). When the response delay has elapsed (red LED MIN lights up), output relay R drops out (yellow LED REL does not light up).

Wurde der Fehlerspeicher aktiviert (WIN + LATCH) und ist der gemessene Strom länger als die eingestellte Auslöseverzögerung unter den am MIN-Regler eingestellten Wert abgesunken, dann zieht das Ausgangsrelais R beim Überschreiten des Minimumwertes nicht an. Hat der gemessene Strom den am MAX-Regler eingestellten Wert länger als die eingestellte Auslöseverzögerung überschritten, dann zieht das Ausgangsrelais R beim Absinken des Stromes unter den Maximumwert ebenfalls nicht an. Nach dem Zurücksetzen des Fehlers (Unterbrechen der Versorgungsspannung), zieht das Ausgangsrelais R beim erneuten Anlegen der Versorgungsspannung an und der Messzyklus beginnt wieder mit dem Ablauf der eingestellten Anlaufüberbrückung (START).

If the fault memory is activated (WIN + LATCH) and the measured current has dropped below the value set on the MIN regulator for longer than the response delay set, output relay R does not pick up if the minimum value is exceeded. If the measured current has exceeded the value set on the MAX regulator by longer than the response delay set, output relay R also does not pick up if the current sinks below the maximum value. After clearing the error (interrupting the supply voltage), output relay R picks up when the supply voltage is reconnected and the measuring cycle begins again after the start override duration has expired (START).

Le relais de sortie R est réarmé (la LED jaune REL est allumée) quand l'intensité mesurée dépasse la valeur réglée sur le commutateur MIN. Quand l'intensité mesurée dépasse la valeur réglée sur le commutateur MAX, la temporisation du déclenchement (DELAY) commence à se dérouler (la LED rouge MAX clignote). Une fois la temporisation écoulée (la LED rouge MAX est allumée), le relais de sortie R retombe (la LED jaune REL est éteinte). Le relais de sortie R est réarmé (la LED jaune REL est allumée) quand l'intensité mesurée passe de nouveau au-dessous de la valeur maximale (la LED rouge MAX est éteinte). Quand l'intensité mesurée passe au-dessous de la valeur réglée sur le commutateur MIN, la temporisation du déclenchement (DELAY) commence à se dérouler (la LED rouge MIN clignote). Une fois la temporisation écoulée (la LED rouge MIN est allumée), le relais de sortie R retombe (la LED jaune REL est éteinte).

El relé de salida R se excita (el LED REL amarillo se enciende), si la corriente medida sobrepasa el valor ajustado en el regulador MIN. Si la corriente medida sobrepasa el valor ajustado en el regulador MAX, se inicia el retardo de reacción ajustado (DELAY) (el LED MAX rojo parpadea). Una vez transcurrido el tiempo de retardo (el LED MAX rojo se enciende), el relé de salida R se desexcita (el LED REL amarillo está apagado). El relé de salida R se excita de nuevo (el LED REL amarillo se enciende), si la corriente medida desciende de nuevo por debajo del valor máximo (el LED MAX rojo está apagado). Si la corriente medida desciende por debajo del valor ajustado en el regulador MIN, se inicia el retardo de reacción ajustado (DELAY) (el LED MIN rojo parpadea). Una vez transcurrido el tiempo de retardo (el LED MIN rojo se enciende), el relé de salida R se desexcita (el LED REL amarillo está apagado).

Si la mémoire de défauts a été activée (WIN + LATCH) et si l'intensité mesurée est passée au-dessous de la valeur réglée sur le commutateur MIN plus longtemps que la temporisation de déclenchement réglée, le relais de sortie R n'est pas armé quand la valeur minimale est dépassée. Si l'intensité mesurée a dépassé la valeur réglée sur le commutateur MAX plus longtemps que la temporisation de déclenchement réglée, le relais de sortie R n'est pas non plus réarmé quand l'intensité passe au-dessous de la valeur maximale. Après correction du défaut (coupure de la tension d'alimentation), le relais de sortie R est réarmé lors de la remise sous tension d'alimentation et le cycle de mesure recommence avec l'écoulement du temps d'inhibition de démarrage réglé (START).

Si se ha activado la memoria de fallos (WIN + LATCH) y si la corriente medida ha descendido por debajo del valor ajustado en el regulador MIN durante un tiempo superior al retardo de reacción ajustado, no se excita el relé de salida R al sobrepasarse el valor mínimo. Si la corriente medida ha sobrepasado el valor ajustado en el regulador MAX durante un tiempo superior al retardo de reacción ajustado, tampoco se excita el relé de salida R al descender la corriente por debajo del valor máximo. Después de la reposición del fallo (interrupción de la tensión de alimentación), el relé de salida R se excita al volver a aplicar la tensión de alimentación, y el ciclo de medición vuelve a comenzar una vez transcurrido el puenteo de arranque ajustado (START).