Phoenix Contact EMD-FL-C-10
Current monitoring of direct and alternating current in 1-phase networks with settable threshold values, starting override and response delay that can be set separately, fault memory and the following functions that can be selected with the rotary switch: OVER over current monitoring, UNDER undercurrent monitoring, WIN monitoring of the range between the thresholds MIN and MAX.
Supply voltage 24 V \'85 240 V AC/DC
Connection terminal blocks (electrically isolated) A1 - A2
Tolerance -15% ... +10% AC / -20% ... +25% DC
Nominal frequency on request: 48 Hz ... 400 Hz or 16.6 Hz
Nominal operational power 4.5 VA (1.5 W)
Circuit points:
1 LED: Supply U
2 LED: Threshold value MAX
3 LED: Threshold value MIN
4 LED: Output relay R
5 Potentiometer START starting override
6 Potentiometer MAX
7 Potentiometer MIN
8 Potentiometer DELAY response delay
9 Rotary switch function
10 Snap-on foot
cab-bat-pow-acc
Cables, batteries, power supplies and other accessories are sold separately unless otherwise stated.