Manual · Phoenix Contact
MCR-S-...-DCI Current transducer up to 55 A, programmable and configurable: Data sheet
Manual19 pagesPDF 550 KB
Data sheet for the Phoenix Contact MCR-S-...-DCI current transducers, including the MCR-S-10-50-UI-SW-DCI for currents up to 55 A.
Covers · 1 model
The models it covers
Summary
What is in it
Phoenix Contact's data sheet for the MCR-S-...-DCI family of programmable, configurable current transducers that measure DC, AC and distorted currents. It covers the MCR-S-1-5 versions (0.2 A to 11 A) and the MCR-S-10-50 versions (9.5 A to 55 A), with or without relay and transistor outputs. It gives ordering data, technical data, design, safety notes, electrical connection, startup and a configuration flowchart for DIP switch setup, the configuration software, and application examples such as motor current and lighting monitoring.
Its parts
- Description
- Table of contents
- Ordering data
- Technical data
- Design
- Installation and startup
- Software package (adapter)
- Application examples
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Phoenix Contact data sheet 100241_en_10 for the MCR-S-...-DCI current transducers, covering the MCR-S-1-5-UI(-SW)-DCI(-NC) and the MCR-S-10-50-UI(-SW)-DCI(-NC). It gives ordering data, technical data, the order keys and the terminal assignment. It shows how to set the range, the analog output and the threshold relay with DIP switches and potentiometers, or to program the unit with software.
- What it is
- Programmable current transducer for AC, DC and distorted currents, with true r.m.s. measurement p. 1
- Input range
- MCR-S-10-50-UI(-SW)-DCI(-NC): 0 A ... 55 A (freely adjustable), 15 Hz ... 400 Hz, through connection 10.5 mm p. 7
- Analog output
- 0(4) mA ... 20 mA or reverse, load < 500 Ω; 0(2) V ... 10 V, 0(1) V ... 5 V, ±10 V, ± 5 V, load > 10 kΩ p. 7
- Switching outputs
- MCR-S-10-50-UI-SW-DCI: 1 PDT relay (AgSnO2, hard gold-plated), 30 V AC / 36 V DC, 50 mA; PNP transistor output, 80 mA (not short-circuit-proof) p. 7
- Supply voltage
- 20 V DC ... 30 V DC p. 7
- Setup options
- Ordered preconfigured, set with DIP switches, or programmed with MCR/PI-CONF-WIN software p. 1
- Measuring modes
- True r.m.s. value or arithmetic average value (DC with sign), chosen with DIP switch 9 p. 13
- Threshold settings
- MCR-S-10-50-UI-SW-DCI: threshold 1 % ... 110 %, suppression time 0.1 s ... 20 s, yellow LED p. 7
- Accuracy and rate
- < 0.5 % transmission error, < 0.025%/K; 40 measurements/s with DC, 5 measurements/s with AC p. 7
- Isolation
- 300 V AC to ground, suitable for measuring in 400 V AC three-phase networks p. 7
- Operating temperature
- -20 °C ... 60 °C (storage -40 °C ... 85 °C) p. 8
- Size and housing
- 22.5 mm x 99 mm x 114.5 mm (W x H x D), IP20, polyamide PA housing p. 8
- Software and cables
- MCR/PI-CONF-WIN software 2814799; MCR-TTL/RS232-E adapter cable 2814388; PSM-KAD 9 SUB 25/BS adapter cable 2761295 p. 3
- Order numbers
- MCR-S-10-50-UI-SW-DCI configured 2814663; MCR-S10-50-UI-SW-DCI-NC unconfigured 2814744 p. 3
What this manual walks you through
- Opening the housing to reach the DIP switches p. 12
- Setting the input current range with DIP switches 1 and 2 p. 14
- Choosing the analog output signal with DIP switches 3 to 6 p. 14
- Choosing the relay and transistor switching behavior with DIP switches 7 and 8 p. 14, 15
- Fine adjustment of zero and span with the potentiometers p. 16, 17
- Setting the switching threshold and suppression time p. 17
- Programming with MCR/PI-CONF-WIN and connecting a computer p. 18
- Ordering a preconfigured unit with the order key p. 9
- Application examples: motor current, motor peak loads, lighting monitoring p. 19
Good to know
- The transducer must not be started up while the housing is open. p. 11
- Adjust the front potentiometers only with a screwdriver isolated from the input voltage. p. 11
- Exceeding the relay maximum values damages the gold coating; after that, 250 V AC/DC and 2A apply as maximums. p. 7
- Let the module warm up for 2 minutes before adjusting it. p. 16
- The manual states the unit is suitable for Class I, Division 2, Groups A, B, C and D or non-hazardous locations only. p. 8
Questions this manual answers
What current range does the MCR-S-10-50-UI-SW-DCI measure?
The MCR-S-10-50 versions measure 0 A to 55 A (freely adjustable) of AC, DC or distorted current, through a 10.5 mm through connection. p. 7
What supply voltage does the MCR-S-10-50-UI-SW-DCI need?
20 V DC to 30 V DC; the green POWER LED lights when it is connected. p. 16
How do I program the transducer from a computer?
Use MCR/PI-CONF-WIN software (2814799) with the MCR-TTL/RS232-E cable (2814388); a 9-pos. to 25-pos. D-SUB adapter cable (2761295) is usually also required. p. 18
Can it measure DC current with its sign?
Yes. DIP switch 9 selects the arithmetic average value, which measures DC with sign bit detection, instead of the true r.m.s. value. p. 13
What does the yellow SW LED mean?
When it lights, the relay N/O contact is closed, the N/C contact is open and the transistor output switches through. p. 17