Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 2 of 2

MCR-S-...-DCI Current transducer up to 55 A, programmable and configurable: Data sheet, pages 11 to 19

Pages 11 to 19 of 19

The original document is the PDF (550 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Phoenix Contact MCR-S-10-50-UI-SW-DCI

Page 11

MCR-S-...-DCI

6

Installation and startup

6.1

Safety notes During operation, certain parts of this electric measuring transducer may carry hazardous voltages. Disregarding this warning may result in serious personal injury or damage to property. MCR-S-...-DCI Modules must only be installed and started by qualified personnel. Qualified personnel are people who, because of their education, experience and instruction and their knowledge of relevant standards, regulations, accident prevention and service conditions, have been authorized by those responsible for the safety of the plant, to carry out any required operations and who are able to recognize and avoid any possible dangers. The transducer must not be started up when the housing is open. The potentiometers on the front should only be adjusted using a screwdriver, which is safely isolated from the voltage at the input. For applications with high operating voltages, ensure sufficient distance or insulation and provide shock protection. Safe and error-free operation of this device can only be ensured if transport, storage, and assembly are carried out correctly and operation and maintenance are carried out with care.

6.2

Method of operation

Connection to the input terminal blocks (MCR-S-1-5-...-DCI) or passing the live conductor through the current transducer (MCR-S-10-50-...-DCI) induces a magnetic flux in the stripwound core. The magnetic flux density is measured using a Hall sensor and converted proportionally from the input current to a voltage (Hall voltage). A subsequent true r.m.s. value converter enables DC, AC, and distorted currents to be measured. The signal is amplified for further processing and made available as a proportional analog signal at the output. 6.3

Electrical connection When operating this electric measuring transducer, the national regulations (e.g., in Germany, VDE 0100 "Conditions for the Erection of Electrical Power Installations with Nominal Voltages Below 1000 V") must be observed during the installation and selection of the electrical conductors.

Pin assignment Connection terminal block 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

100241_en_10

Description

(12) N/C contact1 (11) Center contact1 (14) N/O contact1 Not used 10 A input2 5 A input2 1 A input2 Reference ground for 1, 5, and 10 A input2 Current output Voltage output Reference ground for current or voltage output Reference ground for current or voltage output Operating voltage (+24 V DC) Reference ground for operating voltage Transistor output1 Reference ground for transistor output1

1

Only for MCR-S-...-SW-DCI(-NC)

2

Only for MCR-S-1-5-(-SW)-DCI(-NC)

PHOENIX CONTACT

11

Page 12

MCR-S-...-DCI

6.4

Startup

6.5.1

Configuration or programming

Before starting up the measuring transducer, please ensure that the module configuration data matches the measuring requirements. The configuration data for a preconfigured device can be found on the right hand side of the housing.

The MCR-S-...-DCI generation offers the advantage of a choice between configuration and programming. MCR/PI-CONF-WIN software can be used to freely program the true r.m.s. value current transducer.

If you are using an unconfigured transducer, there is a standard configuration which can be found in the order keys on page 6 and page 9. If the desired configuration does not match the label on the side of the housing or the standard configuration, refer to the section below.

Programming is explained in the software manual. The user-friendly configuration software runs under all popular Windows operating systems.

6.5

The rest of this section deals with configuration:

Configuration flowchart

6.5.2

Programming

Configuration or programming

In addition to programming, modules can be parameterized using DIP switches and potentiometers.

Opening the housing

Software package

Configuration via DIP switches Opening the housing

The transducer must not be started up when the housing is open. Release the locked upper part of the housing on both sides with the help of a screwdriver. The upper part of the housing and the electronics can now be pulled out approximately 3 cm. N

W

3

I 1A

5A

2

S

A

10

1

I C -D W S T I- U NC -U O -5 IS -1 A 14 -S EL R 1 1 N

R C M

12

Configuration of the input current range and measuring process

I DC W- 0 I-S -U 65 1-85 14 S

4

R- 2 MC-Nr.:

Configuration of the analog output

5 t.

Ar

6

7

8

Fine adjustment of the measuring

Threshold value output

No

Figure 3

Opening the housing

Yes Configuration of the threshold value output

Ready for operation

Figure 2

100241_en_10

Configuration flowchart

PHOENIX CONTACT

12

Page 13

MCR-S-...-DCI

6.5.3

Configuration of the input current range and measuring process

(Rough setting via DIP switches) Use DIP switch 9 to select the measuring process (true r.m.s. value or arithmetic average value). DIP 9 OFF DIP

ON

Description True r.m.s. value (AC and DC without without sign bitdetection) Arithmetic average value (DC with sign bitdetection)

10 ... 1

Figure 4 DIP 10 9 8 7 6 5 4 3 2 1 1

DIP switches Description Configuration via DIP switches/ programming via software Input current measurement: True r.m.s. value/arithmetic average value Operating current/closed circuit current behavior1 Above threshold value/ Below threshold value1

True r.m.s. value: The true r.m.s. value of an AC current corresponds by definition to the steady-state value that results from the instantaneous values of this current. This steady-state value generates the same thermal work in an ohmic resistor as a DC current of identical magnitude. The term "true r.m.s. value" simply indicates that distorted and pulsating currents are also measured. Arithmetic average value: The arithmetic average value is used to measure DC currents or to filter a DC portion from a pulsating current. Using the arithmetic average value on a symmetrical AC current would result in the measured value being "0". The arithmetic average value can be used to make bipolar DC currents available as analog standard signals at the output.

Setting the analog output signal

Setting the input measuring range

Only for MCR-S-...-SW-DCI(-NC)

Setting DIP switch 10 to configuration mode (DIP switch 10 to "OFF") switches all potentiometers to "active". DIP 10 OFF ON

100241_en_10

Description Configuration via DIP switches Programming via software (DIP switches 1 to 9 and potentiometer settings not relevant)

PHOENIX CONTACT

13

Page 14

MCR-S-...-DCI

MCR-S-1-5-...DCI: Optimum use of the measuring ranges SPAN Nominal SPAN DIP 1 DIP 2 range1 potentiopotentiometer meter -25% +25% 1 A input: Measuring range: 0 A ... 0.18 A to 0 A ...1.1 A 0 A ... 0.75 A 0 A ... 1.00 A 0 A ... 1.10 A OFF OFF 0 A ... 0.48 A 0 A ... 0.65 A 0 A ... 0.81 A OFF ON 0 A ... 0.30 A 0 A ... 0.40 A 0 A ... 0.50 A ON OFF 0 A ... 0.18 A 0 A ... 0.25 A 0 A ... 0.31 A ON ON 5 A input: Measuring range: 0 ... 0.94 A to 0 ... 5.5 A 0 A ... 3.75 A 0 A ... 5.00 A 0 A ... 5.50 A OFF OFF 0 A ... 2.43 A 0 A ... 3.25 A 0 A ... 4.06 A OFF ON 0 A ... 1.50 A 0 A ... 2.00 A 0 A ... 2.50 A ON OFF 0 A ... 0.94 A 0 A ... 1.25 A 0 A ... 1.56 A ON ON 10 A input: Measuring range: 0 ... 4.87 A to 0 ... 11 A 0 A ... 7.50 A 0 A ... 10.0 A 0 A ... 11.00 A OFF OFF 0 A ... 4.87 A 0 A ... 6.5 A 0 A ... 8.12 A OFF ON 1

The nominal range is adapted

6.5.4

Configuration of the analog output

Output 0 mA ... 20 mA 20 mA ... 0 mA 4 mA ... 20 mA 20 mA ... 4 mA 0 V ... 10 V 10 V ... 0 V 0 V ... 5 V 5 V ... 0 V 1 V ... 5 V 5 V ... 1 V -10 V ... 10 V 10 V ... -10 V -5 V ... 5 V 5 V ... -5 V 6.5.5

DIP 3 OFF OFF OFF OFF OFF OFF OFF OFF ON ON ON ON ON ON

DIP 4 OFF OFF OFF OFF ON ON ON ON OFF OFF ON ON ON ON

DIP 5 OFF OFF ON ON OFF OFF ON ON ON ON OFF OFF ON ON

DIP 6 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON

Configuration of the Threshold Value Output

The relay and transistor output of the threshold value versions (MCR-S-...-SW-DCI) are set after the input measuring range and the analog output have been adapted.

MCR-S-10-50-...DCI: Optimum use of the measuring range

Setting the switching threshold

SPAN Nominal SPAN DIP 1 DIP 2 range1 potentiopotentiometer meter -25% +25% Measuring range: 0 A ... 9.38 A to 0 A ... 55 A 0 A ... 37.5 A 0 A ... 50.0 A 0 A ... 55.0 A OFF OFF 0 A ... 24.4 A 0 A ... 32.5 A 0 A ... 40.6 A OFF ON 0 A ... 15.0 A 0 A ... 20.0 A 0 A ... 25.0 A ON OFF 0 A ... 9.38 A 0 A ... 12.5 A 0 A ... 15.6 A ON ON

The diagrams below (Figure 5 to Figure 8 on page 15) illustrate the four possible switching behavior options for the relay and transistor output. The various options for the operating behavior in threshold value mode are divided according to: – Operating current or closed circuit current principle – Threshold value triggered when value is below threshold – Value is above threshold value

1

The nominal range is adapted

If necessary, the corresponding switching behavior can be set via DIP switch 7 and DIP switch 8. DIP 7 DIP 8 Switching Behavior of Relay and Transistor Output Operating current-controlled OFF OFF when above threshold value Operating current-controlled ON OFF when below threshold value Closed circuit current-controlled OFF ON when above threshold value Closed circuit current-controlled ON ON when below threshold value

100241_en_10

See

Figure 5 Figure 6 Figure 7 Figure 8

PHOENIX CONTACT

14

Page 15

MCR-S-...-DCI

Switching behavior of relay and transistor output for the current transducer IIN

IIN

SW condition

SW condition t t

Operating voltage UB

Operating voltage UB

( H)

( H) ( L)

( L) t

Relay N/O contact (1) and transistor output (0) Relay N/C contact

Figure 5 t1 t1

(0) t

(0) t1 t1 t

Function diagram: Operating currentcontrolled when above threshold value

(1)

Figure 6 t t t

(0)

Relay contact

(1)

t

Relay N/O contact (1) and transistor output t t t

Function diagram: Closed circuit currentcontrolled when above threshold value IIN

IIN

SW condition

SW condition t t

Operating voltage UB

Operating voltage UB

( H)

( H) ( L)

( L)

Relay N/O contact (1) and transistor output (0) Relay contact t t

Relay contact t

(1)

Figure 7

(0) t

(0)

Function diagram: Operating currentcontrolled when below threshold value t

Relay N/O contact (1) and transistor output t t

(0) (1)

Figure 8 t t t

Function diagram: Closed circuit currentcontrolled when below threshold value

(0) = N/O contact and transistor open, N/C contact closed, LED off (1) = N/O contact and transistor closed, N/C contact open, LED on t1 can be set via software and potentiometer

100241_en_10

PHOENIX CONTACT

15

Page 16

MCR-S-...-DCI

12 se E c

W

W

9

E

S

Z S A P N

S W

3

I 1A

5A

Ground terminal block 8 8 8

1 D N G 2 D W N S G 1 D T 2 O N U D G O GN R ER

U O

A

Signal input terminal block 7 6 5

2

I C -D W S T I- U NC -U O -5 IS -1 A 14 -S L R RE 1 1 N

10

Signal input range 1A 5A 10 A

10

V 24 P

C M

12

1

When the green "POWER" LED is lit, the operating voltage of 20 V DC ... 30 V DC is connected. When using the MCR-S-...-DCI, ensure you use the correct signal input terminal block for your measuring range.

11

+

•

Close the module after roughly setting the input current range and preselecting the output signal. Connect the module to the signal lines and the operating voltage according to the instructions in "Electrical connection" on page 11.

20 T IM

•

Analog Output

0

Fine adjustment of the measuring transducer

I DC W- 0 I-S -U 65 1-5 14 S- 28 R

4

MC-Nr.:

5

Figure 9 t.

Ar

6

7

Potentiometers

ZERO and SPAN behavior (±25% each) are shown in Figure 10 and Figure 11: – ZERO potentiometer for zero point adjustment – SPAN potentiometer for final value adjustment OUT [%] 110 100

Allow the module to warm up for 2 minutes before starting the adjustment procedure. SPAN -25% -100

IN 100 SPAN +25%

[%]

-100 -110

Figure 10

Offset (ZERO) behavior

OUT [%] 110 100

SPAN +25% -25%

IN -100

100

[%]

-100 -110

Figure 11

100241_en_10

Final value (SPAN) behavior

PHOENIX CONTACT

16

Page 17

MCR-S-...-DCI

Adjustment structure

Threshold value output Operating voltage I

I

E

A

Signal input

Figure 12 •

•

•

A

A MCR-S

V U

A

Signal output

Adjustment structure

•

–

After connecting the operating voltage and signal lines, first adjust the zero point (offset). There should be no signal at the input (IE = 0). The analog output must correspond to a preselected output signal from the table on page 14. Adjust any inaccuracies using the ZERO potentiometer. To adjust the measuring range final value, a current should be specified which is the same level as the final value if possible. If this is not possible, one of the following adjustment formulae should be used:

IE (I - I )) IA = I0 + (––– IME x MA 0

•

IE UA = U0 + (––– * (UMA - U0)) IME

Example: The current transducer is to be set to the following values: Input measuring range: 0 A ... 5 A

IME = 5 A

Output measuring range: 0 mA ... 20 mA

I0 = 0 mA

– – – •

Specify a current for the module, which corresponds to the threshold value: Set the TIME potentiometer to "0 s" and turn the threshold value potentiometer according to the following instructions (see Figure 5 to Figure 8 on page 15): For Figure 5: Turn the threshold value potentiometer until the yellow "SW" LED lights up. For Figure 6: Turn the threshold value potentiometer until the yellow "SW" LED goes out. For Figure 7: Turn the threshold value potentiometer until the yellow "SW" LED goes out. For Figure 8: Turn the threshold value potentiometer until the yellow "SW" LED lights up. To prevent switching behavior at the binary output level during a brief overcurrent, a suppression time must be set using the TIME potentiometer. If the increased current is present for longer than the specified suppression time, the preselected switching behavior becomes active. The available setting range is 0 to 20 seconds.

When the yellow "SW" LED lights up (relay and transistor status display), the N/O contact of the PDT contact is closed and the N/C contact of the PDT contact is opened. The transistor output switches through.

IMA = 20 mA Constant current for configuration IE = 3 A • Adjust the calculated output current using the SPAN potentiometer to IA = 12 mA. When the voltage output is used, the same adjustment procedure is necessary.

100241_en_10

PHOENIX CONTACT

17

Page 18

MCR-S-...-DCI

7

Software package (adapter)

As an alternative to setting via DIP switches, the module can be programmed using the MCR/PI-CONF-WIN configuration software (Order No. 2814799). Software features – – – – – – – –

All configuration parameters can be entered in the computer The parameters entered in the computer can be saved to the measuring transducer The parameters available in the module can be exported The parameters can be saved to a drive of your choice A side-panel label can be created The programmed module parameters can be printed Bar graph display Monitoring function

The MCR-TTL/RS232-E software adapter cable (Order No. 2814388) can be used to connect the computer and the current transducer. This cable has a stereo jack connector on one end for connection to the current transducer and a 25-pos. D-SUB female connector on the other end for connection to a computer. For connection to the computer, an adapter cable for the interface converter is usually required (9-pos. D-SUB female connector to 25-pos. D-SUB male connector, Order No. 2761295).

100241_en_10

PHOENIX CONTACT

18

Page 19

MCR-S-...-DCI

8

Application examples

8.1

Motor current measurement Controller Frequency inverter

3 14

8

4 NC

0 sec

OUT I

OUT

POWER

9 + 24V ⁄

U

0

GND 1

$

GND 2

!

SW

%

GND 2

"

GND 1

&

30

OFFSET

2 11

7 1A

TIME

GAIN

6 5A

MCR-S-...

SW

1 12

Pow er

N

5 10 A

SW

Relais

L1

24V

Figure 13

Mains voltage

Motor current measurement

The use of MCR-S-...-DCI modules in one or more supply phases of the motor enables what is known as "motor monitoring" (Figure 13). The MCR current transducer can transfer corresponding standard signals about the motor load to the control system or service personnel. The true r.m.s. value measurement process means that AC, DC, and distorted currents can be measured. Even higher frequency currents up to 1 kHz can be acquired. 8.2

Acquisition of motor current peak loads 0

3 14

8

4 NC OUT

0 sec

OUT I

9

POWER + 24V

U

0

GND 1

$

GND 2

!

SW

%

GND 2

"

GND 1

&

1

2

3

Maintenance interval counter

⁄

30

OFFSET

2 11

7 1A

TIME

Pow er

6 5A

MCR-S-...

GAIN

1 12

SW

5 10 A

SW

Relais

L1

N

24V

Mains voltage

Figure 14

Acquisition of motor current peak loads

Large industrial motors must be overhauled and serviced at regular intervals. Installing an MCR current transducer in one phase of the motor feed line enables pulses to be generated with the relay or transistor switching output that can be measured using a simple meter (Figure 14). The service personnel can then use the motor starts and peak loads as a basis to provide efficient maintenance corresponding to the number of overloads. 8.3

Lighting monitoring

MCR current transducers can be used for monitoring lighting. If the strength of the current in a circuit is above or below a specified value after a suppressed switch-on time, there is a fault in the lighting circuit. If the lighting circuit fails, this signal status can be passed on to another control unit and the emergency lighting can be switched on. The same method can also be used with other power loads.

100241_en_10

PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49 - 52 35 - 30 0 PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300 www.phoenixcontact.com

19