MCR-S-...-DCI Current transducer up to 55 A, programmable and configurable: Data sheet, pages 1 to 10
Pages 1 to 10 of 19
The original document is the PDF (550 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Page 1
MCR-S-...-DCI Current transducer up to 55 A, programmable and configurable
INTERFACE Data sheet 100241_en_10 1
© PHOENIX CONTACT 2010-10-13
DC, AC, and distorted currents can be equally well measured.
Description
The MCR-S-...-DCI current transducers offer users the option of ordering a preconfigured device, configuring the device themselves via DIP switches or programming it with MCR/PI-CONF-WIN configuration software (Order No. 2814799).
Power
FL
IN
I
U,I
OUT
POWER
The MCR-S-1-5-UI-DCI module provides not only the standard 1 A and 5 A input signals, but also the option of setting current ranges of 0 ... 0.2 A to 0 ... 11 A progressively.
In addition to an analog output, these current transducers also have an optional relay and transistor output, e.g., for alarm monitoring. When ordering, the desired configuration to which the device is to be adapted must be specified (see order key on page 6 and page 9). Features – – – – –
Progressive adjustment of measuring range True r.m.s. value measurement 3-way electrical isolation according to EN 61010 With optional relay and transistor output 22.5 mm ME housing
With a measuring range of 0 ... 9.5 A to 0 ... 55 A, the MCR-S-10-50-UI-DCI is ideal for measuring higher motor currents.
Observe the safety notes on page 11.
Make sure you always use the latest documentation. It can be downloaded from the product at www.phoenixcontact.net/catalog. This data sheet is valid for the products listed on the following page:
Page 2
MCR-S-...-DCI
2
Table of contents
1
Description.................................................................................................................................. 1
2
Table of contents ........................................................................................................................ 2
3
Ordering data.............................................................................................................................. 3
4
Technical data ............................................................................................................................ 4 4.1 4.2
Technical data for MCR-S-1-5-UI(-SW)-DCI(-NC) (measuring range 0 A ... 0.2 A to 0 A ... 11 A) .................. 4 Technical data for MCR-S-10-50-UI(-SW)-DCI(-NC) (measuring range 0 A ... 9.5 A to 0 A ... 55 A) .............. 7
5
Design .......................................................................................................................................10
6
Installation and startup...............................................................................................................11 6.1 6.2 6.3 6.4 6.5
Safety notes ................................................................................................................................................. 11 Method of operation ..................................................................................................................................... 11 Electrical connection .................................................................................................................................... 11 Startup.......................................................................................................................................................... 12 Configuration flowchart................................................................................................................................. 12
7
Software package (adapter) ......................................................................................................18
8
Application examples.................................................................................................................19 8.1 8.2 8.3
100241_en_10
Motor current measurement ......................................................................................................................... 19 Acquisition of motor current peak loads........................................................................................................ 19 Lighting monitoring ....................................................................................................................................... 19
PHOENIX CONTACT
2
Page 3
MCR-S-...-DCI
3
Ordering data
MCR current transducer, for measuring AC, DC, and distorted Currents Description Type Measuring range 0 A ... 0.2 A to 0 A ... 11 A
Order No.
Pcs./Pkt.
Configured, with screw connection
MCR-S-1-5-UI-DCI1
2814634
1
Unconfigured, with screw connection
MCR-S-1-5-UI-DCI-NC
2814715
1
Measuring range 0 A ... 0.2 A to 0 A ... 11 A, with relay and transistor output Configured, with screw connection
MCR-S-1-5-UI-SW-DCI1
2814650
1
Unconfigured, with screw connection
MCR-S-1-5-UI-SW-DCI-NC
2814731
1
Configured, with through connection
MCR-S-10-50-UI-DCI1
2814647
1
Unconfigured, with through connection
MCR-S10-50-UI-DCI-NC
2814728
1
Measuring range 0 A ... 9.5 A to 0 A ... 55 A
Measuring range 0 A ... 9.5 A to 0 A ... 55 A, with relay and transistor switching output Configured, with through connection
MCR-S-10-50-UI-SW-DCI1
2814663
1
Unconfigured, with through connection
MCR-S10-50-UI-SW-DCI-NC
2814744
1
1
If no further details are given as to the configuration, the device is supplied in the standard configuration (see order key on page page 6 and page 9).
Accessories Description
Type
Order No.
Pcs./Pkt.
Configuration software
MCR/PI-CONF-WIN
2814799
1
Software adapter cable (stereo jack connector/25-pos. D-SUB) 1.2 m
MCR-TTL/RS232-E
2814388
1
Adapter cable, 9-pos. D-SUB female connector to 25-pos. D-SUB male connector
PSM-KAD 9 SUB 25/BS
2761295
1
100241_en_10
PHOENIX CONTACT
3
Page 4
MCR-S-...-DCI
4
Technical data
4.1
Technical data for MCR-S-1-5-UI(-SW)-DCI(-NC) (measuring range 0 A ... 0.2 A to 0 A ... 11 A)
Measuring input
MCR-S-1-5-UI-DCI (-NC)
Input current (AC, DC or distorted currents)
MCR-S-1-5-UI-SW-DCI (-NC) 0 A ... 11 A
Frequency range
15 Hz ... 400 Hz
Connection method
Screw terminal block 2.5 mm2
Overload capacity, continuous
2 x INom
Surge strength for 1 s
Output
20 x INom (100 A, maximum)
MCR-S-1-5-UI-DCI (-NC)
MCR-S-1-5-UI-SW-DCI (-NC)
Output current/load
0(4) mA ... 20 mA, 20 mA ... 0(4) mA / < 500 Ω
Output voltage/load
0(2) V ... 10 V, 10 V ... 0(2) V / > 10 kΩ 0(1) V ... 5 V, 5 V ... 0(1) V / > 10 kΩ ±10 V, ± 5 V / > 10 kΩ
Switching output Relay Output
MCR-S-1-5-UI-DCI (-NC)
MCR-S-1-5-UI-SW-DCI (-NC)
–
1 PDT
Contact material
AgSnO2, hard gold-plated
Max. switching voltage
30 V AC / 36 V DC
Continuous current load capacity
50 mA
If the specified maximum values are exceeded, the gold coating will be damaged. In subsequent operation, the following maximum switching voltages and currents apply: 250 V AC/DC; 2A. Transistor output
–
PNP output
Maximum transistor current
80 mA (not short-circuit-proof)
Output voltage during event
1 V under supply voltage
Threshold setting
–
1 % ... 110 %
Suppression time
–
0.1 s ... 20 s
Threshold value switch status indicator
–
Yellow LED
MCR-S-1-5-UI-DCI (-NC)
MCR-S-1-5-UI-SW-DCI (-NC)
General data Supply voltage Current consumption (without load)
20 V DC ... 30 V DC Approximately 40 mA
Approximately 50 mA
Transmission error of nominal value under nominal conditions:
< 0.5 %
Measuring range nominal value: operate threshold from measuring range nominal value Input signal form: Measurement mode: Ambient temperature: Supply voltage:
0 A ... 1 A/5 A/10 A 2% 50 Hz - sine true r.m.s. value 23 °C 24 V DC
Temperature coefficient Measuring rate Step response (10% ... 90 %)
< 0.025%/K 40 measurements/s with DC 5 measurements/s with AC 40 ms with DC 330 ms with DC
Safe isolation according to EN 50178, EN 61010 Input/output (analog), input/output (relay), input/output (transistor), input/supply
100241_en_10
300 V AC to ground (suitable for measuring in 400 V AC three-phase networks)
PHOENIX CONTACT
4
Page 5
MCR-S-...-DCI
General data (continued)
MCR-S-1-5-UI-DCI (-NC)
MCR-S-1-5-UI-SW-DCI (-NC)
Test voltage Input/output (analog), input/output (relay), input/output (transistor), input/supply
4 kV, 50 Hz, 1 min.
Output (analog)/output (relay), output (relay)/output (transistor)
4 kV, 50 Hz, 1 min.
Output (analog)/output (transistor), output (analog)/supply
500 V, 50 Hz, 1 min.
Ambient temperature (operation)
-20 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C ≥ 2 min.
Module warm-up time Supply voltage status indicator
Green LED
Degree of protection
IP20
Mounting position
Any
Mounting
Any
Dimensions (W x H x D)
22.5 mm x 99 mm x 114.5 mm
Housing material
Polyamide PA, non-reinforced
Approvals CE c
UL
U
PROCESS CONTROL EQUIPMENT FOR HAZARDOUS LOCATIONS 31ZN
Cl. I Zn. 2, AEx nC IIC T6 / Ex nC IIC T6 Cl. I Div. 2, Groups A, B, C and D A) This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non-hazardous locations only. B) Warning - explosion hazard - substitution of components may impair suitability for Class 1, Division 2. C) Warning - explosion hazard - do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
Conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC Noise immunity test according to EN 61000-6-21 Electrostatic discharge (ESD)
EN 61000-4-2
Criterion B2
8 kV air discharge
Electromagnetic HF field
EN 61000-4-3
Criterion A3
10 V/m
Fast transients (burst)
EN 61000-4-4
Criterion B2
EN 61000-4-5
Criterion B2
Input/output/power supply Surge current load (surge)
2 kV / 5 kHz 2 kV / 42 Ω
Input/output
1 kV / 2 Ω
Supply Conducted interference
EN 61000-4-6
Criterion A3
Input/output/power supply
10 V
Noise emission test according to EN 61000-6-4 Noise emission of housing
EN 550114
Class A5
1
EN 61000 corresponds to IEC 61000
2
Criterion B:
Temporary adverse effects on the operating behavior, which the device corrects automatically.
3
Criterion A:
Normal operating behavior within the specified limits.
4
EN 55011 corresponds to CISPR11
5
Class A:
100241_en_10
Industrial application, without special installation measures.
PHOENIX CONTACT
5
Page 6
MCR-S-...-DCI
Order Key for the MCR-S-1-5-UI(-SW)-DCI Current Transducer If incorrect or no customer order information is given, the standard configuration is delivered (shown as an example in the ordering key). Measuring Range Start Value
Order No.
2814634
/
0.00
MCR-S-1-5-UI-DCI
Measuring Range Final Value
/
5.00
Output signal
/
OUT01
0 A ... 7.5 A
0.2 A ... 11 A
OUT01 = 0 mA ... 20 mA
0.00 = 0 A
5.00 = 5 A
OUT02 = 4 mA ... 20 mA OUT03 = 0 V ... 10 V OUT04 = 2 V ... 10 V OUT05 = 0 V ... 5 V OUT06 = 1 V ... 5 V OUT13 = -5 V ... +5 V OUT14 = -10 V ... +10 V
2814650
Measuring Range Final Value
Measuring RangeStart Value
Order No.
/
MCR-S-1-5UI-SWI-DCI
0.00
/
5.00
Threshold value
Output signal
/
OUT01
0 A ... 7.5 A
0.2 A ... 11 A
OUT01 = 0 mA ... 20 mA
0.00 = 0 A
5.00 = 5 A
OUT02 = 4 mA ... 20 mA OUT03 = 0 V ... 10 V OUT04 = 2 V ... 10 V
/
50
1 % ... 110 %
Suppression time
/
3.0
0.1 s ... 20 s 3.0 = 3 s
50 = 50 % of the set measuring range final value (here: 2.5 A)
Switching behavior of relay and transistor
/
A
/
O
A = operating currentcontrolled
O = Above
R = Closed circuit currentcontrolled
U = Below
OUT05 = 0 V ... 5 V OUT06 = 1 V ... 5 V OUT13 = -5 V ... +5 V OUT14 = -10 V ... +10 V
100241_en_10
PHOENIX CONTACT
6
Page 7
MCR-S-...-DCI
4.2
Technical data for MCR-S-10-50-UI(-SW)-DCI(-NC) (measuring range 0 A ... 9.5 A to 0 A ... 55 A)
Measuring input
MCR-S-10-50-UI-DCI (-NC)
Input current (AC, DC or distorted currents)
MCR-S-10-50-UI-SW-DCI (-NC)
0 A ... 55 A (freely adjustable)
Frequency range
15 Hz ... 400 Hz
Connection method
Through connection 10.5 mm ∅
Overload capacity, continuous
Depends on the conductor
Current carrying capacity for 1 s
Depends on the conductor
Output
MCR-S-10-50-UI-DCI (-NC)
MCR-S-10-50-UI-SW-DCI (-NC)
Output current/load
0(4) mA ... 20 mA, 20 mA ... 0(4) mA / < 500 Ω
Output voltage/load
0(2) V ... 10 V, 10 V ... 0(2) V / > 10 kΩ 0(1) V ... 5 V, 5 V ... 0(1) V / > 10 kΩ ±10 V, ± 5 V / > 10 kΩ
Switching output Relay Output
MCR-S-10-50-UI-DCI (-NC)
MCR-S-10-50-UI-SW-DCI (-NC)
–
1 PDT
Contact material
AgSnO2, hard gold-plated 30 V AC / 36 V DC
Max. switching voltage
50 mA
Continuous current load capacity
If the specified maximum values are exceeded, the gold coating will be damaged. In subsequent operation, the following maximum switchingvoltages and currents apply: 250 V AC/DC; 2A. Transistor output
–
PNP output
Maximum transistor current
80 mA (not short-circuit-proof) 1 V under supply voltage
Output voltage during event Threshold setting
–
1 % ... 110 %
Suppression time
–
0.1 s ... 20 s
Threshold value switch status indicator
–
Yellow LED
MCR-S-10-50-UI-DCI (-NC)
MCR-S-10-50-UI-SW-DCI (-NC)
General data Supply voltage: Current consumption (without load)
20 V DC ... 30 V DC Approximately 40 mA
Approximately 50 mA
Transmission error of nominal value under nominal conditions:
< 0.5 %
Measuring range nominal value: operate threshold from measuring range nominal value Input signal form: Measurement mode: Ambient temperature: Supply voltage:
0 A ... 50 A 0.8 % 50 Hz - sine true r.m.s. value 23 °C 24 V DC
Temperature coefficient Measuring rate Step response (10% ... 90 %)
< 0.025%/K 40 measurements/s with DC 5 measurements/s with AC 40 ms with DC 330 ms with AC
Safe isolation according to EN 50178, EN 61010 Input/output (analog), input/output (relay), input/output (transistor), input/supply
100241_en_10
300 V AC to ground (suitable for measuring in 400 V AC three-phase networks)
PHOENIX CONTACT
7
Page 8
MCR-S-...-DCI
General data (continued)
MCR-S-10-50-UI-DCI (-NC)
MCR-S-10-50-UI-SW-DCI (-NC)
Test voltage Input/output (analog), input/output (relay), input/output (transistor), input/supply
4 kV, 50 Hz, 1 min.
Output (analog)/output (relay), output (relay)/output (transistor)
4 kV, 50 Hz, 1 min.
Output (analog)/output (transistor), output (analog)/supply
500 V, 50 Hz, 1 min.
Ambient temperature (operation)
-20 °C ... 60 °C
Ambient temperature (storage/transport)
-40 °C ... 85 °C ≥ 2 min.
Module warm-up time Supply voltage status indicator
Green LED
Degree of protection
IP20
Mounting position
Any
Mounting
Any
Dimensions (W x H x D)
22.5 mm x 99 mm x 114.5 mm
Housing material
Polyamide PA, non-reinforced
Approvals CE c
UL
U
PROCESS CONTROL EQUIPMENT FOR HAZARDOUS LOCATIONS 31ZN
Cl. I, Zn. 2, AEx nC IIC T6 / Ex nC IIC T6 Cl. I Div. 2, Groups A, B, C and D A) This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non-hazardous locations only. B) Warning - explosion hazard - substitution of components may impair suitability for Class 1, Division 2. C) Warning - explosion hazard - do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
Conformance with EMC Directive 2004/108/EG and Low Voltage Directive 2006/95/EG Noise immunity test according to EN 61000-6-21 Electrostatic discharge (ESD)
EN 61000-4-2
Criterion B2
8 kV air discharge
Electromagnetic HF field
EN 61000-4-3
Criterion A3
10 V/m
Fast transients (burst)
EN 61000-4-4
Criterion B2
EN 61000-4-5
Criterion B2
Input/output/power supply Surge current load (surge)
2 kV / 5 kHz 2 kV / 42 Ω
Input/output
1 kV / 2 Ω
Supply Conducted interference
EN 61000-4-6
Criterion A3
Input/output/power supply
10 V
Noise emission test according to EN 61000-6-4 Noise emission of housing
EN 550114
Class A5
1
EN 61000 corresponds to IEC 61000
2
Criterion B:
Temporary adverse effects on the operating behavior, which the device corrects automatically.
3
Criterion A:
Normal operating behavior within the specified limits.
4
EN 55011 corresponds to CISPR11
5
Class A:
100241_en_10
Industrial application, without special installation measures.
PHOENIX CONTACT
8
Page 9
MCR-S-...-DCI
Order Key for the MCR-S-10-50-UI(-SW)-DCI current transducer If incorrect or no customer order information is given, the standard configuration is delivered (shown as an example in the ordering key). Order No.
Measuring range start value
2814647
/
0.0
MCR-S-10-50-UI-DCI
Measuring range final value
/
50.0
Output signal
/
OUT01
0 A ... 37.5 A
9.5 A ... 55 A
OUT01 = 0 mA ... 20 mA
0.0 = 0 A
50.0 = 50 A
OUT02 = 4 mA ... 20 mA OUT03 = 0 V ... 10 V OUT04 = 2 V ... 10 V OUT05 = 0 V ... 5 V OUT06 = 1 V ... 5 V OUT13 = -5 V ... +5 V OUT14 = -10 V ... +10 V
2814663
MCR-S-10-50 -UI-SWI-DCI
Measuring range final value
Measuring rangestart value
Order No.
/
0.0
/
50.0
Threshold value
Output signal
/
OUT01
0 A ... 37.5 A
9.5 A ... 55 A
OUT01 = 0 mA ... 20 mA
0.0 = 0 A
50.0 = 50 A
OUT02 = 4 mA ... 20 mA OUT03 = 0 V ... 10 V OUT04 = 2 V ... 10 V
/
50
1 % ... 110 %
Suppression time
/
3.0
0.1 s ... 20 s 3.0 = 3 s
50 = 50 % of the set measuring range final value (here: 25 A)
Switching behavior of relay and transistor
/
A
/
O
A = Operating currentcontrolled
O = Above
R = Closed circuit currentcontrolled
U = Below
OUT05 = 0 V ... 5 V OUT06 = 1 V ... 5 V OUT13 = -5 V ... +5 V OUT14 = -10 V ... +10 V
100241_en_10
PHOENIX CONTACT
9
Page 10
MCR-S-...-DCI
Design 4
6
9
0
0 se E c se E c
20 T IM
S A P N
C
S W
12
1
I C -D W S I- T C -U OU N 50 S 0- I 4 -1 LA 1 -S E R 1
W
R
S
3
D WI-S -U 6 3 -504 6 -108 1
4
CI
S R- 2 MC-Nr.:
2 t.
Ar
/
S AL OV PR AP
9
N NE IO AT OB PR AP
MCR-S-1-5-UI-SW-DCI
6 7 8
2
S AL OV PR AP
1
5
M
N
/
1 2 3 4
8
8
N NE IO AT OB PR AP
Figure 1
W
A P t.
7
S
S
UI- 65 -5- 4
Ar
6
W
W
20 T IM
O
S
W
P
O
I 1A
5A
1 CI -D SW 0
4 R MC-Nr.:
5
1 D N G 2 D W N S G 1 D T 2 O N U D G O GN R ER Z E U
P
8
-1 1 -S 28
2
10
V 24
1 D N G 2 D W N S G 1 D T 2 O N U D G O GN R ER Z E
U
A
3
I C -D W S T I- U NC -U O -5 IS -1 A 14 -S EL R 1 1 N
R C
10
2
9
+
V 24
M
12
1
7
12
+
11
6
3
7
12
3
5
11
5
4
10
5
1 MCR-S-10-50-UI-SW-DCI
Structure using the example of the MCR-S-...-UI-SW-DCI(-NC) current transducer with relay and transistor output
Metal lock for mounting on the DIN rail Upper part of housing slides open for DIP switch setting Programming interface TIME potentiometer for threshold value suppression time (only for MCR-S-...-UI-SW-DCI(-NC)) "SW" LED (yellow): Threshold value switch (only for MCR-S-...-UI-SW-DCI(-NC)) "POWER" LED (green): Supply voltage ZERO/SPAN potentiometer Threshold value potentiometer (only for MCR-S-...-UI-SW-DCI(-NC)) The potentiometers on the front should only be adjusted using a screwdriver, which is safely isolated from the voltage at the input.
9
Cable feed-through (only for MCR-S-10-50-UI(-SW)-DCI(-NC))
100241_en_10
PHOENIX CONTACT
10