QUINT-PS-100-240AC/24DC/5 Single-Phase Primary-Switched Power Supply Unit, pages 1 to 6

Pages 1 to 6 of 11

The original document is the PDF (685 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Phoenix Contact Quint-PS100-240-24dc-5

Page 1

QUINT-PS-100-240AC/24DC/5 Single-Phase Primary-Switched Power Supply Unit

INTERFACE Data Sheet

© PHOENIX CONTACT - 12/2005

Description QUINT POWER devices are 60...960 W DC power supply units for universal use. This is ensured by the wide-range input, single and three-phase versions, and an international approval package.

All QUINT POWER devices are idling-proof and shortcircuit proof, and are available with a regulated and adjustable output voltage of 12, 24, and 48 V DC with output currents of 2.5, 5, 10, 20, 30, and 40 A.

QUINT POWER stands for guaranteed supply: powerful capacitors ensure mains buffering of more than 20 ms at full load.

Power supply units for use in Ex Zone 2, uninterruptible solutions, AS-i power supply units, and a QUINT diode complete the product range.

All three-phase devices provide the full output power, even in the event of a continuous phase failure. The POWER BOOST power reserve starts loads with high inrush currents and ensures that fuses are reliably tripped. Preventive function monitoring diagnoses impermissible operating states and minimizes downtimes in your system. An active transistor output and a floating relay contact are used for remote monitoring.

QUINT POWER is a built-in device. Installation and startup must only be carried out by qualified personnel. The relevant countryspecific regulations (e.g., VDE, DIN) must also be observed.

Danger The device contains dangerous live elements and high levels of stored energy. Never carry out work when the power is turned on. Risk of burns The housing temperature can reach high values depending on the ambient temperature and the load of the device. Make sure you always use the latest documentation. It can be downloaded at www.download.phoenixcontact.com. A conversion table is available on the Internet at www.download.phoenixcontact.com/general/7000_en_00.pdf. This data sheet is valid for all products listed on the following page:

100029_04_en

PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany Phone: +49 - 52 35 - 30 0 • Fax: +49 - 52 35 - 34 12 00 • www.phoenixcontact.com www.phoenixcontact.com/salesnetwork

1

Page 2

QUINT-PS-100-240AC/24DC/5

Ordering Data Product Description

Type

Order No.

Pcs./Pkt.

Single-phase primary-switched power supply unit

QUINT-PS-100-240AC/24DC/5

29 38 58 1

1

Accessories Description

Type

Order No.

Pcs./Pkt.

Assembly adapter for QUINT POWER 2.5 A and 5 A on S7 300 rails

QUINT-PS-ADAPTERS7/1

29 38 19 6

1

Technical Data Input Data Nominal input voltage range

100...240 V AC

Input voltage range

85...264 V AC, 90...350 V DC

Frequency range

45...65 Hz (0 Hz at DC input)

Current consumption

1.6 A (at 120 V AC (nominal load)), approximately 0.84 A (at 230 V AC (nominal load)), approximately

Inrush current surge

< 20 A (typical), inrush current limiting/Ι2t (25°C): < 2.5 A²s

Mains buffering (for nominal load)

> 20 ms (at 120 V AC), > 120 ms (at 230 V AC)

Typical switch-on time

<1s

Protective circuit

Transient surge protection varistor

Input fuse

5 A (slow-blow, internal)

Recommended backup fuse

Circuit breaker 6 A, 10 A or 16 A, Characteristic B

Discharge current to PE

< 3.5 mA

Connection method

COMBICON screw/plug-in connection

Stripping length

7 mm

Output Data Nominal output voltage

24 V DC ±1%

Setting range for the output voltage

22.5...28.5 V DC

Output current

5 A (-25...+60°C) 7.5 A (with POWER BOOST, -25...+40°C)

Derating

Above +60°C: 2.5% per Kelvin

Current limit

IBOOST = 7.5 A (for short circuit), approximately

Maximum capacitive load

Unlimited

System deviation

< 1% (static load change 10...90%) < 2% (dynamic load change 10...90%) < 0.1% (input voltage change ±10%)

Power dissipation Maximum nominal load Maximum no load

14 W 2W

Efficiency

> 89% for 230 V AC and nominal values

Rise time

< 2 ms (UOUT (10...90%))

Residual ripple/switching peaks (20 MHz)

< 100 mVpp (for nominal values)

Parallel connection

Yes, to create redundant systems and increase efficiency

Internal surge protection

Yes, limited to 35 V DC, approximately

Resistance to return supply

35 V DC

Connection method

COMBICON screw/plug-in connection

Stripping length

7 mm

DC OK Signal Output, Active Type of output

Transistor output, Uout > 0.9 x UN: High signal

Continuous current

40 mA, maximum

Output voltage

+24 V DC (signal)

100029_04_en

PHOENIX CONTACT

2

Page 3

QUINT-PS-100-240AC/24DC/5

DC OK Signal Output, Floating Type of output

Relay contact, Uout > 0.9 x UN: Contact closed

Continuous current

1 A, maximum

Maximum switching voltage

30 V AC/DC, maximum

General Data Insulation voltage Input/output

4 kV AC (type test)/2 kV AC (routine test)

Input/PE

3.5 kV AC (type test)/2 kV AC (routine test)

Insulation voltage output/PE

500 V DC (routine test)

Mounting position

On horizontal NS 35 DIN rail according to EN 60715

Degree of protection

IP20

Protection class

Ι, with PE connection

MTBF

> 500,000 h according to IEC 61709 (SN 29500)

Housing version

AluNox (AlMg1), closed

Weight

0.830 kg

Dimensions (width x height x depth)

55 mm x 130 mm x 125 mm

Dimensions (width x height x depth) for alternative assembly

122 mm x 130 mm x 58 mm

Status Indicators DC OK status indicator

Green LED (Uout < 0.9 x UN: LED flashes)

Climatic Data Ambient temperature (operation)

-25...+70°C (> 60°C derating)

Ambient temperature (storage/transport)

-40...+85°C

Maximum permissible humidity (operation)

95% (at +25°C, no condensation)

Vibration (operation)

< 15 Hz, amplitude ±2.5 mm according to IEC 60068-2-6 15...150 Hz, 2.3g, 90 minutes

Shock

30g in all space directions, according to IEC 60068-2-27

Pollution degree

2 according to EN 50178

Climatic class

3K3 according to EN 60721

Certification/Standards Electrical equipment of machines

EN 60204 (Surge Voltage Category III)

Safety transformers for switched-mode power supply units

EN 61558-2-17

Electrical safety (of IT equipment)

EN 60950/VDE 0805 (SELV), EN 61558-2-17 CB Scheme j

UL/C-UL Recognized UL 60950 u Industrial control equipment

UL/C-UL Listed UL 508 U LISTED

Electrical equipment for potentially explosive areas

UL/C-UL Recognized UL 1604, Class Ι, Division 2, Groups A, B, C, D

Shipbuilding

Germanischer Lloyd F, ABS

Electronic equipment for use in electrical power installations

EN 50178 (VDE 0160)

Safety extra-low voltage

PELV (EN 60204), SELV (EN 60950)

Safe isolation

DIN VDE 0100-410, DIN VDE 0106-1010

Protection against electric shock

DIN 57100-410

Protection against electric shock, basic requirements for safe isolation in electrical equipment

DIN VDE 0106-101

Limitation of harmonic line currents

According to EN 61000-3-2

Device safety

B (tested safety)

100029_04_en

PHOENIX CONTACT

3

Page 4

QUINT-PS-100-240AC/24DC/5

Conformance With EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC Noise Immunity Test According to EN 61000-6-21 Electrostatic discharge (ESD)

EN 61000-4-2

Criterion B2

Housing

Level 4

Air discharge 15 kV Contact discharge 8 kV Electromagnetic HF field

EN 61000-4-3

Criterion A3

Housing Level 3 Frequency range 80...1000 MHz/1.4...2.0 GHz Field strength 10 V/m

Fast transients (burst)

EN 61000-4-4

Criterion B2

Input 4 kV (Inst. Class 4, asymmetrical: Cable to ground) 2 kV (Inst. Class 4, symmetrical: Cable to cable) Output 0.5 kV (Level 1, asymmetrical: Cable to ground) 0.5 kV (Level 1, symmetrical: Cable to cable) Signal 1 kV (Level 1, asymmetrical: Cable to ground)

Surge current load (surge)

EN 61000-4-5

Criterion B2

Input 4 kV (Level 4, asymmetrical) Output 2 kV (Level 3, asymmetrical) Signal 1 kV (Level 2, asymmetrical)

Conducted interference

EN 61000-4-6

Criterion A3

Input/output/signal Level 3, asymmetrical Frequency range 0.15...80 MHz Voltage 10 V

Voltage dips

EN 61000-4-11 Criterion B

Input Mains buffering > 20 ms

Noise Emission Test According to EN 61000-6-3 Noise emission of housing

EN 55011 (EN 55022)4

Class B

Industrial and domestic applications

1

EN 61000 corresponds to IEC 61000

2

Criterion B:

Temporary adverse effects on the operating behavior, which the device corrects automatically.

3

Criterion A:

Normal operating behavior within the specified limits.

4

EN 55011 corresponds to CISPR11/EN 55022 corresponds to CISPR22

1

Structure 7

2

4

QUINT POWER

13 13

Figure 1

14

3

QUINT POWER

13

14

DC OK

3 4 5 6 7

13 14 D C

OK

Ou tp ut

2

DC

DC

24 V

5A

OK

22 Ad ,5-2 ju 8,5st V

D OK C

14 D C

AC input 85...264 V AC input voltage, 45...65 Hz frequency DC output 24 V DC output voltage (default), can be set between 22.5 and 28.5 V DC DC OK output active DC OK output floating Potentiometer (covered) 22.5...28.5 V DC DC OK LED Universal DIN rail adapter UTA 107

O

Ou K tp ut

DC

AC Inp 1 u L 00-2t N 40V

24 V

6

5A

5 1

DC

OK

Operating elements

Block Diagram L (+) N (-) PE

Figure 2

100029_04_en

DC OK 13 14

Block diagram

PHOENIX CONTACT

4

Page 5

QUINT-PS-100-240AC/24DC/5

Safety Notes and Warning Instructions Danger

Before startup please ensure:

The device contains dangerous live elements and high levels of stored energy.

–

Never carry out work when the power is turned on.

–

Risk of burns The housing temperature can reach high values depending on the ambient temperature and the load of the device. To ensure that the device can be operated safely and all functions can be used, please read these instructions carefully.

– – –

–

The mains has been connected correctly and protection is provided against electric shock. The device can be switched off outside the power supply according to EN 60950 regulations (e.g., by the line protection on the primary side). The protective conductor is connected. All supply lines have sufficient fuse protection and are the correct size. All output cables are the correct size for the maximum device output current or have separate fuse protection. Sufficient convection is ensured.

QUINT POWER is a built-in device. Installation and startup must only be carried out by qualified personnel. The relevant countryspecific regulations (e.g., VDE, DIN) must also be observed.

Installation

14

DC OK

QUINT POWER

13

Risk of burns The housing temperature can reach high values depending on the ambient temperature and the load of the device. To ensure sufficient convection, the following minimum spacing is required between other modules: 5 cm above and below the device. No minimum spacing to other modules at the sides is required for proper operation of the device.

Figure 3

100029_04_en

Convection

The power supply unit can be snapped onto all DIN rails according to EN 60715 and must be mounted horizontally (connection terminal blocks facing downwards).

PHOENIX CONTACT

5

Page 6

QUINT-PS-100-240AC/24DC/5

Mounting Position

(122)

Figure 4

(130)

QUINT POWER

230

115

50

(55)

Mounting position (dimensions in mm)

Narrow mounting position: Installation depth 125 mm (+ DIN rail)

Flat mounting position: Installation depth 58 mm (+ DIN rail)

Narrow Mounting Position (Default Upon Delivery) Assembly Position the module with the DIN rail guideway on the top edge of the DIN rail and then snap it downwards. Removal Release the snap-on catch using a screwdriver and then detach the module from the bottom edge of the DIN rail.

Figure 5

100029_04_en

Narrow mounting position

PHOENIX CONTACT

6