Page 7
QUINT-PS-100-240AC/24DC/5
Flat Mounting Position
Figure 6
Flat mounting position
A flat mounting position can be achieved by mounting the module onto the DIN rail at a 90° angle. Mount the DIN rail adapter (UTA 107) as shown in Figure 6.
No additional assembly material is required. Mounting screws: Torx T10 (torque 0.8...0.9 Nm).
Connection of Various Types of Network: 100...240 V AC Networks The device can be connected to single-phase AC networks or to two external conductors for three-phase networks (TN, TT or IT network according to VDE 0100-300/ IEC 60364-3) with nominal voltages of 100...240 V AC.
TN-S
L N PE
Figure 7
100029_04_en
+ -
TT
TN-C L N PE
An all-pole disconnecting device must be provided for 2-phase operation using two external conductors for a three-phase network.
L PEN L N PE
+ - iT
L1 L2 L3
L N L N PE
+ -
L N PE
+ -
100...240 V AC networks
PHOENIX CONTACT
7
Page 8
QUINT-PS-100-240AC/24DC/5
Connection of the Connecting Cable The device is equipped with COMBICON connectors. This connection method enables quick device connection and visible isolation of the electrical connection, if required. Connectors may only be operated when the power is switched off. Use a screwdriver with the correct blade width for wiring. The cable cross sections listed in the table on the right can be connected. 13
14
Solid
Stranded
AWG
Torque
[mm²]
Stripping Length
[Nm]
[mm]
Input
0.2...2.5
0.2...2.5
25...14
0.5...0.6
7 mm
Output
0.2...2.5
0.2...2.5
25...14
0.5...0.6
7 mm
Signal
0.2...2.5
0.2...2.5
25...14
0.5...0.6
7 mm
For reliable and safe-to-touch connections, strip the cable ends according to the table.
DC OK
13 14 D C
OK
Input (1)
Ou tp ut
DC
DC
24 V
5A
The 100...240 V AC connection is made using the L, N, and 5 screw connections. OK
22 Ad ,5-2 ju 8,5st V
AC Inp 1 u L 00-2t N 40V
1
Figure 8
Input
Fuses An internal fuse is provided for device protection. Additional device protection is not required. If an internal fuse is blown, this is most probably due to a device fault. In this case, the device should be checked in the factory. Recommended Backup Fuse Circuit breaker 6 A, 10 A or 16 A, Characteristic B (or equivalent). A suitable fuse should be provided for DC applications. Protecting the Primary Side The device must be installed according to the specifications of EN 60950. It must be possible to switch off the device using a suitable disconnecting device outside the power supply. For example, primary side line protection could be used.
100029_04_en
PHOENIX CONTACT
8
Page 9
QUINT-PS-100-240AC/24DC/5
Output
13 14
4
QUINT POWER
13 13
14
3
QUINT POWER
13
14
14 D C
OK
2
DC
DC
24 V
5A
OK
Figure 10
22 Ad ,5-2 ju 8,5st V
Floating contact
D OK C
14 D C O
Ou K tp ut
DC
AC Inp 1 u L 00-2t N 40V
24 V
DC
Figure 9
+ + - -
DC OK 30 V AC/DC, 1 A, maximum
DC OK
13
Ou tp ut
DC OK
Floating Contact
5A
6 5
When opened, the floating signal contact indicates that the output voltage has fallen more than 10% below the set value. Signals and ohmic loads up to a maximum of 30 V and currents up to a maximum of 1 A can be switched. With heavy inductive loads, e.g., a relay, a suitable protective circuit (e.g., free-wheeling diode) is required.
OK
Output
Active Signal Output
The connection is made using the "+" and "-" screw connections on the screw connection 2. The output voltage set upon delivery is 24 V DC. The output voltage can be set on the potentiometer 5. Protecting the Secondary Side The device is electronically short-circuit-proof and idlingproof. In the event of an error, the output voltage is limited to a maximum of 35 V DC. Make sure that all output cables are the correct size for the maximum output current or have separate fuse protection. The cable cross sections in the secondary circuit must be large enough to keep the voltage drops on the cables as low as possible. Signaling
13 14
24 V DC 40 mA
Figure 11
DC OK
Connecting the Output
+ + - DC OK
Active signal output
The 24 V DC signal is between the "DC OK" and "-" connection terminal blocks and can be loaded with 40 mA maximum. This signal output indicates that the output voltage has fallen more than 10% below the set value when "active high" changes to "low". The DC OK signal is isolated from the power output. This ensures that a separate supply does not enter from devices connected in parallel. The 24 V DC signal can be connected directly to a logic input for evaluation.
The two DC OK outputs are for preventive function monitoring of the power supply unit. A floating signal contact 4 and an active DC OK signal 3 are available. In addition, the DC OK LED 6 can be used to evaluate the function of the power supply directly at the installation location (see "Status Indicator: DC OK LED" on page 10).
100029_04_en
PHOENIX CONTACT
9
Page 10
QUINT-PS-100-240AC/24DC/5
Signal Loop 1
Output
+ + - -
13
14
DC OK
14
DC OK
Output 13
The two signal outputs described above can be easily combined.
2
Example: Monitoring two devices
+ + - -
Use the active alarm output of device 1 and loop in the floating alarm output of device 2. In the event of an error, a group error message is output. Any number of devices can be looped. This signal combination saves wiring costs and logic inputs.
DC OK
Figure 12
Signal loop
Status Indicator: DC OK LED The green DC OK LED enables local function evaluation in the control cabinet. DC OK LED Active DC OK switching output Floating DC OK output Cause Meaning
ON Flashing U = +24 V (with reference to "-") U = 0 V (with reference to "-")
OFF U = 0 V (with reference to "-")
Closed
Open
Open
Output voltage greater than 90% Output voltage less than 90% of of the set voltage the set voltage Output voltage and current OK QUINT POWER operating, but: – Error at the load – Current consumption greater than IBOOST – Output short circuit
No voltage at the output QUINT POWER not operating, because: – No mains voltage present – The primary side fuse has blown – The device is faulty
Function Output Characteristic Curve
UOUT [V] UN
PN
< 60°C
< 40°C
IN Figure 13
PBOOST
IBOOST IOUT [A]
Output characteristic curve
The U/I characteristic curve ensures that both heavy capacitive loads and loads with DC/DC converters can be supplied by QUINT POWER in the input circuit. Connected fuses are tripped. The selectivity in your system configuration is ensured at all times. – UN = +24 V – IN = 5 A – IBOOST = 7.5 A – PN = 120 W – PBOOST = 180 W
At ambient operating temperatures Tamb < +40°C, the device can continuously supply an IBOOST current at nominal voltage. In the event of heavier loads the working point demonstrates the U/I characteristic curve shown in the figure. The output current is limited to IBOOST. The secondary voltage is reduced until the short circuit on the secondary side is removed.
100029_04_en
PHOENIX CONTACT
10
Page 11
QUINT-PS-100-240AC/24DC/5
Output current [A]
Temperature Response IBOOST IN
Redundancy Operation
IN
IN
+-
+-
+ 0 0
20
40
Ambient operating temperature [°C]
Figure 14
+-
60
Figure 15
Σ = IN
Redundancy operation
Temperature response
At an ambient operating temperature of up to +40°C, the device continuously supplies the IBOOST output current. The device can supply a nominal output current of IN up to an ambient operating temperature of +60°C. The output power must be decreased by 2.5% per Kelvin temperature increase for ambient operating temperatures over +60°C. At ambient operating temperatures above +70°C or in the event of a thermal overload, the device does not switch off. The output power is decreased to such an extent that device protection is provided. Once the device has cooled down, the output power is increased again.
Redundant circuits are suitable for supplying systems, which place particularly high demands on operational safety. If a fault occurs in the primary circuit of the first power supply unit, the second device automatically takes over the entire power supply, without interruption, and vice versa. For this purpose, the power supply units to be connected in parallel must be large enough that the total current requirements of all loads can be fully met by one power supply unit. External decoupling diodes are required for 100% redundancy (QUINT-DIODE/40, Order No. 29 38 96 3).
Parallel Operation Devices of the same type can be connected in parallel to increase both redundancy and power. The default setting does not have to be adjusted. A maximum of five devices can be connected in parallel. If the output voltage is adjusted, an even current distribution can be ensured by precisely setting all power supply units that are operated in parallel to the same output voltage. To ensure symmetrical current distribution we recommend that all cable connections from the power supply unit to the DIN rail are the same length and have the same cross section. Depending on the system, for parallel connection of more than two power supply units a protective circuit should be installed at each individual device output (e.g., decoupling diode or DC fuse). This prevents high return currents in the event of a secondary device fault.
Increasing Power
IN
+-
IN
+-
+ +Figure 16
Σ = 2 * IN
Increasing power
The output current can be increased to n x IN where n is the number of devices connected in parallel. Parallel connection for increasing power is used when extending existing systems. A parallel connection is recommended if the power supply unit does not cover the current consumption of the most powerful load. Otherwise, the loads should be divided over independent individual devices. A maximum of five devices can be connected in parallel.
© PHOENIX CONTACT 12/2005
100029_04_en
PHOENIX CONTACT