Spec sheet · Pilz
PNOZ X3: E-STOP relays, safety gate monitors
Spec sheet9 pagesPDF 419 KB
Data sheet for the Pilz PNOZ X3 safety relay for E-STOP pushbuttons and safety gates: features, wiring, dimensions and technical data.
Covers · 1 model
The models it covers
Summary
What is in it
Pilz data sheet for the PNOZ X3 safety relay, which monitors E-STOP pushbuttons and safety gates up to PL e of EN ISO 13849-1. It lists unit and safety features, approvals, a block diagram and function description (single- and dual-channel operation, automatic and monitored reset), timing diagram, wiring and preparation for operation, terminal configuration, installation and dimensions, service life graph, full technical details and order references for each supply voltage.
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Pilz data sheet for the PNOZ X3 safety relay, used to monitor E-STOP pushbuttons and safety gates. It describes the contacts and semiconductor output, the single- and dual-channel operating modes, and the wiring of the supply, input, reset and feedback circuits. It also gives the terminal layout, installation, a contact service life graph, technical details and the order references.
- Device type
- Safety relay for monitoring E-STOP pushbuttons and safety gates p. 1
- Outputs
- Positive-guided relay outputs: 3 safety contacts (N/O) and 1 auxiliary contact (N/C), instantaneous; 1 semiconductor output p. 1
- Terminals
- Safety contacts 13-14, 23-24, 33-34; auxiliary contact 41-42; semiconductor output Y31, Y32; reset circuit S13-S14, S33-S34 p. 2, 4
- Connections
- E-STOP pushbutton, safety gate limit switch, reset button p. 1
- Operating modes
- Single-channel, or dual-channel with detection of shorts across contacts; automatic start or monitored reset p. 2
- LEDs
- Switch status channel 1/2 and supply voltage p. 1
- Supply voltage variants
- 24 V AC/DC, 42 V AC, 48 V AC, 110 V AC, 115 V AC, 120 V AC, 230 V AC, 240 V AC p. 9
- Mounting
- Vertical 35 mm DIN rail with a fixing element, inside a control cabinet of at least IP54 p. 5
- Contact expansion
- More instantaneous safety contacts through contact expansion modules or external contactors p. 2
- Service life example
- AC15 inductive load of 0.2 A: 1 000 000 cycles contact service life p. 6
- Wiring
- Copper wire rated 60/75 °C; a fuse before the output contacts p. 2
- Order numbers
- 774 310, 774 311, 774 312, 774 314, 774 315, 774 316, 774 318, 774 319 (one per supply voltage variant) p. 9
- Standards
- The data sheet states it meets EN 60947-5-1, EN 60204-1 and VDE 0113-1 p. 1
- Document
- Pilz data sheet 1002239-EN-01-2011-02 p. 1
What this sheet walks you through
- Wiring the supply voltage and the single- or dual-channel input circuits p. 3
- Wiring the reset circuit and a feedback loop from external contactors p. 4
- Wiring the semiconductor output p. 4
- Reading the timing diagram p. 2
- Calculating the maximum cable run in the input circuit p. 2
- Reading the terminal configuration p. 5
- Mounting the unit on a DIN rail p. 5
- Estimating contact life from the service life graph p. 6
Good to know
- The data sheet is meant for configuration only; installation and operation follow the operating instructions supplied with the unit. p. 6
- A fuse should be connected before the output contacts to prevent contact welding. p. 2
- Single-channel operation has no redundancy in the input circuit. p. 2
- The safety-related data of the relay outputs is valid only if the service life graph values are met. p. 8
- The data sheet recommends the semiconductor outputs for switching 24 VDC loads. p. 6
Questions this sheet answers
How many safety contacts does the PNOZ X3 have?
Three N/O safety contacts and one N/C auxiliary contact, all instantaneous, plus one semiconductor output. p. 1
Which PNOZ X3 terminals are the safety contacts?
13-14, 23-24 and 33-34 are the safety contacts; 41-42 is the auxiliary contact, for example for a display. p. 2
Can the PNOZ X3 be wired single-channel?
Yes. Single-channel operation has no input redundancy but detects earth faults; dual-channel operation also detects shorts across contacts. p. 2
How is the PNOZ X3 mounted?
On a vertical 35 mm DIN rail secured with a fixing element, inside a control cabinet rated at least IP54. p. 5
What supply voltages does the PNOZ X3 come in?
24 V AC/DC, or 42, 48, 110, 115, 120, 230 or 240 V AC. p. 9
The whole text · 1 part
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file