PNOZ X3 Operating Instructions
Manual20 pagesPDF 646 KB
Multilingual operating instructions for the Pilz PNOZ X3 safety relay: functions, operating modes, installation, wiring and data.
Names · 1 model
The models it names
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
Pilz operating instructions for the PNOZ X3 safety relay, printed in German, English, French, Spanish, Italian and Dutch. The relay interrupts a safety circuit for E-STOP pushbuttons and safety gates. The sheet covers safety regulations, authorized applications, the unit description and features, function description with internal wiring diagram, single and two-channel operating modes, automatic and monitored manual reset, installation, operation, connection examples and technical data.
From the manual
Key facts from this manual
Each line names its page in the PDF.
Operating instructions for the Pilz PNOZ X3 safety relay, printed in German, English, French, Spanish, Italian and Dutch. It covers the PNOZ X3 only. It explains the operating modes, how to wire the supply, reset and input circuits, how faults show up, and the technical data and order numbers.
- Device
- Safety relay that interrupts a safety circuit, used with E-STOP pushbuttons and safety gates p. 1
- Relay outputs
- 3 safety contacts (N/O) and 1 auxiliary contact (N/C), positive-guided p. 1
- Supply voltage
- Versions for 24 V AC/DC, 42 V AC, 48 V AC, 110 V AC, 115 V AC, 120 V AC, 230 V AC and 240 V AC; every unit also runs on 24 V DC p. 1, 8
- Contact terminals
- Safety contacts 13-14, 23-24, 33-34; auxiliary contact 41-42; semiconductor output Y32 p. 2
- Contact rating
- AC15: 230 V/5 A; DC13: 24 V/6 A (EN 60947-5-1) p. 6
- Contact fuse
- Blow-out fuse 10 A quick or 6 A slow, or safety cut-out 24 V AC/DC: 6 A, characteristic B/C p. 6
- Semiconductor output
- 24 V DC, 20 mA, short circuit-proof; fed with +24 V DC on Y31 and 0 V on B2 p. 4, 6
- Response times
- Drop-out on E-STOP typ. 15 ms, max. 30 ms; switch-on delay with monitored reset typ. 35 ms, max. 50 ms p. 6
- Input cable resistance
- Max. single-channel 150 Ohm DC, 180 Ohm AC; dual-channel with short detection 15 Ohm DC, 30 Ohm AC p. 6
- Temperature
- Ambient -20 ... +55 °C; storage -40 ... +85 °C p. 7
- Protection type
- Mounting area IP54, housing IP40, terminals IP20 p. 7
- Size and weight
- 87 x 45 x 121 mm (H x W x D), 375 g p. 7
- Screw terminals
- 1 flexible core 0.20 ... 4.0 mm2 (24 - 10 AWG); torque 0.6 Nm p. 7
- Order numbers
- 774 310, 774 311, 774 312, 774 314, 774 315, 774 316, 774 318, 774 319 p. 8
What this manual walks you through
- Connecting the supply voltage (AC on A1 and A2, DC on B1 and B2) p. 4
- Setting automatic reset or manual reset with monitoring p. 4
- Wiring a single-channel or two-channel input circuit p. 4
- Adding external contactors in the feedback loop p. 4, 5
- Connecting the semiconductor output to a PLC p. 4, 5
- Connection examples for E-STOP and safety gate circuits p. 4, 5
- Recognizing faults: earth faults, welded contacts, an unlit Power LED p. 5
- Estimating contact life from the service life graph p. 8
Good to know
- In the automatic-reset examples of Fig. 2 and 7 the unit starts by itself after a power loss; external circuitry must prevent an unintended start-up. p. 4
- For overvoltage category III: with more than 50 VAC or 120 VDC on the unit, connected control elements and sensors need a rated insulation voltage of at least 250 V. p. 1
- The unit should be panel mounted, since dust or dampness can impair its function. p. 1
- The safety data of the relay outputs hold only while the values in the service life graphs are met. p. 7
- With manual reset with monitoring, the reset circuit must be closed at least 300 ms after the input circuit closes. p. 2
Questions this manual answers
What outputs does the Pilz PNOZ X3 have?
Three positive-guided safety contacts (N/O) and one auxiliary contact (N/C), plus a semiconductor output Y32 that conducts when relays K1 and K2 are energised. p. 1, 2
How do I get a PNOZ X3 working again after an earth fault on DC?
Remove the cause of the fault and switch the operating voltage off for about 1 minute; the unit is then ready for operation. p. 5
Why is the Power LED on my PNOZ X3 not lit?
The manual gives a short circuit or a loss of supply voltage as the cause. p. 5
How do I wire the PNOZ X3 for automatic reset?
Bridge terminals S13-S14. In the automatic-reset examples (Fig. 2 and 7) S33-S34 is left unconnected. p. 4