Spec sheet · Pilz
PNOZ X9 E-STOP relays, safety gate monitors, Up to PL e of EN ISO 13849-1
Spec sheet8 pagesPDF 435 KB
Data sheet for the Pilz PNOZ X9 safety relay for monitoring E-STOP pushbuttons, safety gates and light barriers.
Covers · 1 model
The models it covers
Summary
What is in it
Pilz's data sheet for the PNOZ X9, a safety relay for monitoring E-STOP pushbuttons, safety gates and light barriers, up to PL e of EN ISO 13849-1. It lists unit and safety features, the block diagram and function description (single and dual-channel operation, automatic, manual and monitored reset), a timing diagram, wiring for supply, input, reset and feedback circuits, terminal configuration, installation and dimensions, full technical details and order references.
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Data sheet for the Pilz PNOZ X9 safety relay, which monitors E-STOP pushbuttons, safety gates and light barriers. It describes the contacts and outputs, the input and reset modes, wiring examples, terminal layout, installation and technical details.
- Device
- Safety relay for E-STOP pushbuttons, safety gates and light barriers p. 1
- Relay contacts
- 7 safety contacts (N/O) and 2 auxiliary contacts (N/C), instantaneous, positive-guided p. 1
- Semiconductor outputs
- 2: supply voltage present (Y35) and switch status (Y32) p. 1, 2
- Input modes
- Single-channel, or dual-channel with or without detection of shorts across contacts p. 2
- Reset modes
- Automatic start, manual reset or monitored reset p. 2
- Contact terminals
- Safety 13-14, 23-24, 33-34, 43-44, 53-54, 63-64, 73-74; auxiliary 81-82, 91-92 p. 2
- Input and reset terminals
- Inputs S11-S12, S21-S22, S52; reset circuit S33-S34 p. 2
- Feedback loop
- Y1-Y2, for contacts of external contactors p. 4
- Indicators
- LEDs for switch status channel 1/2, supply voltage, reset circuit and input circuits p. 1
- Mounting
- 35 mm DIN rail, in a cabinet of at least IP54 p. 5
- More contacts
- Contact expansion modules or external contactors/relays p. 2
- Wire
- Copper wire rated 60/75 °C p. 2
- Stated standards
- The data sheet states up to PL e of EN ISO 13849-1, and EN 60947-5-1, EN 60204-1, VDE 0113-1 p. 1
What this sheet walks you through
- Wiring the AC or DC supply p. 3
- Wiring E-STOP, safety gate and light barrier input circuits p. 3
- Wiring automatic, manual or monitored reset p. 4
- Connecting the feedback loop and semiconductor output p. 4
- Working out the maximum cable run in the input circuit p. 2
- Mounting the relay on a DIN rail p. 5
- Reading the timing diagram for each reset mode p. 2
Good to know
- A fuse should be fitted before the output contacts to prevent contact welding. p. 2
- Output contacts with capacitive or inductive loads need fuse protection. p. 2
- Single-channel operation has no redundancy in the input circuit. p. 2
- The data sheet is for configuration only; installation and operation follow the operating instructions supplied with the unit. p. 6
- Secure the unit on a vertical 35 mm DIN rail with a fixing element such as an end angle. p. 5
Questions this sheet answers
How many safety contacts does the Pilz PNOZ X9 have?
7 safety contacts (N/O) and 2 auxiliary contacts (N/C), plus 2 semiconductor outputs. p. 1
What can a PNOZ X9 monitor?
E-STOP pushbuttons, safety gates and light barriers. p. 1
What reset modes does the PNOZ X9 support?
Automatic start, manual reset and monitored reset. With monitored reset the reset circuit must close and open again. p. 2
What are terminals S33 and S34 on the PNOZ X9?
The reset circuit. p. 2
How is the PNOZ X9 mounted?
On a 35 mm DIN rail inside a control cabinet of at least IP54, secured with a fixing element. p. 5
The whole text · 1 part
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file