Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 1 of 4

4 Channel Analog Output Module M/N 57C410, pages 1 to 9

Pages 1 to 9 of 36

The original document is the PDF (366 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Reliance Electric 57C410

Page 1 read from a scan by OCR; it may hold reading errors

4 Channel Analog Output Module

M/N 570410

Instruction Manual J-3631 -1 eS ELECTRIC&L

Page 2

The information in this user's manual is subject to change without notice. WARNING THIS UNIT AND ITS ASSOCIATED EQUIPMENT MUST BE INSTALLED, ADJUSTED AND MAINTAINED BY QUALIFIED PERSONNEL WHO ARE FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF ALL EQUIPMENT IN THE SYSTEM AND THE POTENTIAL HAZARDS INVOLVED. FAILURE TO OBSERVE THESE PRECAUTIONS COULD RESULT IN BODILY INJURY.

WARNING INSERTING OR REMOVING THIS MODULE OR ITS CONNECTING CABLES MAY RESULT IN UNEXPECTED MACHINE MOTION. POWER TO THE MACHINE SHOULD BE TURNED OFF BEFORE INSERTING OR REMOVING THE MODULE OR ITS CONNECTING CABLES. FAILURE TO OBSERVE THESE PRECAUTIONS COULD RESULT IN BODILY INJURY.

CAUTION THIS MODULE CONTAINS STATIC-SENSITIVE COMPONENTS. CARELESS HANDLING CAN CAUSE SEVERE DAMAGE. DO NOT TOUCH THE CONNECTORS ON THE BACK OF THE MODULE. WHEN NOT IN USE, THE MODULE SHOULD BE STORED IN AN ANTI-STATIC BAG. THE PLASTIC COVER SHOULD NOT BE REMOVED. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN DAMAGE TO OR DESTRUCTION OF THE MATERIAL.

is a registered trademark of Reliance Electric Company or its subsidiaries. Copyright Reliance Electric Industrial Company 1991.

Page 3 read from a scan by OCR; it may hold reading errors

1.0

2.0

3.0

4.0

5.0

Table of Contents

Introduction 1.0.0... 00. cece cece cece eee eee 1-1 Mechanical/Electrical Description ..........000eeeeeeeeeeeeee 2-1 2.1 Mechanical Description ............. 0... eee eee 2-1 2.2 Electrical Description .......... 00... 2-1 Installation 0.0.0... c cece cece cece eens 3-1 3.1 WIFINg 2... eee eee eee 3-1 3.2 Initial Installation 0.0.0.0... eee eee eee 3-1 3.3 Module Replacement........... 0... eee eee 3-4 ProgrammMing ........:cccee cece cece e eee eens 4-1 4.1 Register Organization ........... 0. cece eee eee 4-1 4.2 Configuration ....... 6. . eects 4-1 4.3 Reading And Writing Data In Application Tasks .............. 4-2

4.3.1 BASIC Task Example .......... 0.00 cece eee eee eee 4-2

4.3.2 Control Block Task Example ............... 000s eee eee 4-2 4.4 Restrictions ....... 0... eee eee eee 4-2

4.4.1 DataLimitations ............. 0.0 eee eee 4-2 Diagnostics And Troubleshooting ..............c cece eee ees 5-1 5.1 Incorrect Data... 0.2 eee eee eee 5-1

5.2 BUS Error ....... cnet nee e eee eens 5-3

Page 4

II

Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1

Module Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1

Field Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-1

Related Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1

Defining Variables in the Configuration Task . . . . . . . . . . . . . . . . . . . . E-1

Page 5 read from a scan by OCR; it may hold reading errors

List of Figures

Figure 2.1. - Typical Output Circuit......... 2. eee eee 2-2 Figure 2.2 - Module Faceplate .............. 0.0 ccc eee 2-3 Figure 3.1 - Typical Field Connections for Voltage Output ............. 3-2 Figure 3.2 - Typical Field Connections for 4-20 ma Current Output ..... 3-2 Figure 3.3 - Rack SlotNumbers ............. 0... c cece eee eee 3-3

Figure 4.1. - Organization of Register Bits ................ cece eee eee 4-1

Page 6

fafadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa afdfdsfdsfdfdsfdsfsadfda asfdfaddfdd

Page 7

The products described in this instruction manual are manufactured or distributed by Reliance Electric Company or its subsidiaries. This 4 Channel Analog Output Module contains four 12Ćbit D/A converter channels. Each channel can provide +5 volts, +8 volts, +10 volts, or a 4-20 ma current output. Output signals have 2500 volt isolation to logic common. Each channel has its own independent isolated common. The voltage outputs are current limited to protect the device in the event of a short circuit. Typically, this module is used to output voltage or current signals to devices such as drive and process controllers. This manual describes the functions and specifications of the module. It also includes a detailed overview of installation and servicing procedures, as well as examples of programming methods. Related publications that may be of interest: J-2611

DCS 5000 PRODUCT SUMMARY

J-3675

DCS 5000 ENHANCED BASIC LANGUAGE INSTRUCTION MANUAL

J-3600

DCS 5000 CONTROL BLOCK LANGUAGE INSTRUCTION MANUAL

J-3602

DCS 5000 LADDER LOGIC LANGUAGE INSTRUCTION MANUAL

J-3629

DCS 5000 REMOTE I/O INSTRUCTION MANUAL

J-3630

ReSource AutoMax PROGRAMMING EXECUTIVE INSTRUCTION MANUAL VERSION 1.0

J-3635

DCS 5000 PROCESSOR MODULE INSTRUCTION MANUAL

J-3649

AutoMax CONFIGURATION TASK MANUAL

J-3650

AutoMax PROCESSOR MODULE INSTRUCTION MANUAL

J-3675

AutoMax ENHANCED BASIC LANGUAGE INSTRUCTION MANUAL

J-3676

AutoMax CONTROL BLOCK LANGUAGE INSTRUCTION MANUAL

J-3677

AutoMax LADDER LOGIC LANGUAGE INSTRUCTION MANUAL

J-3684

ReSource AutoMax PROGRAMMING EXECUTIVE INSTRUCTION MANUAL VERSION 2.0

J-3750

ReSource AutoMax PROGRAMMING EXECUTIVE INSTRUCTION MANUAL VERSION 3.0

IEEE 518 GUIDE FOR THE INSTALLATION OF ELECTRICAL EQUIPMENT TO MINIMIZE ELECTRICAL NOISE INPUTS TO CONTROLLERS FROM EXTERNAL SOURCES

1-1

Page 8

fafadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa afdfdsfdsfdfdsfdsfsadfda asfdfaddfdd

Page 9

2.0 MECHANICAL/ELECTRICAL DESCRIPTION The following is a description of the faceplate LEDs, field termination connectors, and electrical characteristics of the field connections.

2.1

Mechanical Description The output module is a printed circuit board assembly that plugs into the backplane of the DCS 5000/AutoMax rack. It consists of a printed circuit board, a faceplate, and a protective enclosure. The faceplate contains tabs at the top and bottom to simplify removing the module from the rack. Module dimensions are listed in Appendix A. The faceplate of the module contains a female connector socket and 4 LED indicators that show the status of the onĆboard isolated power supplies. Output signals leave the module via a multiĆconductor cable (M/N 57C374; see Appendix D). One end of this cable attaches to the faceplate connector, while the other end of the cable has stakeĆon connectors that attach to a terminal strip for easy field wiring. The faceplate connector socket and cable plug are keyed to prevent the cable from being plugged into the wrong module. On the back of the module are two edge connectors that attach to the system backplane.

2.2

Electrical Description The output module contains 4 D/A converters that provide 12Ćbit resolution for +5 volts, +8 volts, and +10 volts, and 11Ćbit resolution for 4-20 ma current outputs. Each D/A converter has its own isolated common. Output signals have 2500 volt isolation to logic common. Refer to the block diagram in Appendix B. Each output circuit consists of three operational amplifiers. The first amplifier provides the voltage output. Jumpers are provided on the terminal strip to select an output range of 5, 8, or 10 volts. Current limiting is provided to protect the device against short circuits. A capacitor in the feedback path of this amplifier serves as a first order low pass output filter where the break frequency is approximately 100 hz. The other two amplifiers are used to generate the 4-20 ma current output. A circuit diagram is shown in figure 2.1.

2-1