4 Channel Analog Output Module M/N 57C410
Manual36 pagesPDF 366 KB
Instruction manual for the Reliance Electric 57C410 4 channel analog output module for DCS 5000 and AutoMax racks.
Covers · 1 model
The models it covers
Summary
What is in it
The instruction manual for the Reliance Electric 4 channel analog output module, M/N 57C410, which plugs into a DCS 5000 or AutoMax rack. It describes the module's faceplate, LEDs and output circuits, installation and wiring for voltage and current outputs, module replacement, register organization and programming from BASIC and control block tasks, and diagnostics, with technical specifications, a block diagram, field connections and related components in the appendices.
Its parts
- Introduction
- Mechanical/Electrical Description
- Installation
- Programming
- Diagnostics and Troubleshooting
- Technical Specifications
- Module Block Diagram
- Field Connections
- Related Components
- Defining Variables in the Configuration Task
From the manual · read page by page
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
The Reliance Electric instruction manual J-3631-1 (June 1991) for the 57C410 4 channel analog output module, which plugs into a DCS 5000 or AutoMax rack. It covers installation and field wiring, the register format with programming examples, troubleshooting of wrong output data and bus errors, and the technical specifications. Some pages, including the cover and the field connection table, were read by OCR from a scan.
- Device
- 4 channel analog output module with four 12-bit D/A converters, for DCS 5000/AutoMax racks p. 7, 9
- Output ranges
- 5, 8 or 10 volts (10 ma max), or 4-20 ma with an external 12-48 volt supply and load <= 500 ohms p. 23
- Range selection
- Jumpers on the terminal strip select 5, 8 or 10 volts p. 9
- Resolution
- 12-bit on the voltage ranges, 11-bit on 4-20 ma p. 9
- Accuracy
- 0.10% of full scale (voltage output), 0.15% of full scale (current output) p. 23
- Isolation
- 2500 volt isolation to logic common; each channel has its own isolated common; voltage outputs current limited p. 7
- System power
- +5 volts: 2750 ma; +12 volts: 55 ma; -12 volts: 5 ma p. 23
- Power dissipation
- 13.7 Watts p. 23
- Dimensions
- Height 11.75 inches, width 1.25 inches, depth 7.375 inches p. 23
- Environment
- Operating 0 to 60 C; storage -40 to 85 C; humidity 5 to 90% non-condensing p. 23
- Terminal strip
- 57C374 terminal strip/cable assembly connects field wiring to the faceplate p. 9, 29
- Field terminals
- Five per channel: 5 volt jumper, voltage output, 8 volt jumper, current output, common; channel 0 on 1 to 5, channel 3 on 16 to 20 p. 27
- Data format
- Four 16-bit registers, one per channel; values +4095 through -4095; bit 15 sign, bits 1-11 data p. 17
- LEDs
- Four LEDs show the isolated power supply of each channel; lit means operational p. 10
What this manual walks you through
- Installing the module and mounting the terminal strip p. 13, 14, 15
- Wiring voltage and 4-20 ma field connections p. 13, 14
- Keying connectors so the wrong cable cannot be plugged in p. 15
- Checking each output with I/O MONITOR and a voltmeter p. 15, 16
- Replacing a module p. 16
- Register format and BASIC and control block examples p. 17, 18
- Troubleshooting wrong output data p. 19, 20, 21
- Troubleshooting a bus error p. 21, 22
- Defining local and remote I/O in the configuration task p. 31, 32, 34
Good to know
- Turn power off before inserting or removing the module or its cables; doing it live can cause unexpected machine motion. p. 2
- The module is static-sensitive: do not touch the rear connectors, keep it in an anti-static bag and leave the plastic cover on. p. 2
- Writing test values to the outputs can move the machine unexpectedly. p. 16
- Register bit 0 and bits 12 to 14 do not reach the converter, so limit values above +4095 in software. p. 18
- A field device with too low an impedance can trip the current limit and keep a voltage output from reaching its value. p. 20
Questions this manual answers
What does a 31 or 51 through 58 on the processor LED mean with a 57C410?
A bus error when the system tried to access the module, caused by a missing module, a module in the wrong slot or a faulty module. p. 21
How do I set a 57C410 channel for 5 or 8 volt output?
Connect a jumper on the terminal strip between the 5 volt or 8 volt terminal and that channel's voltage output. p. 13
What register value gives full scale output on the 57C410?
4095 gives +5.0V, +8.0V or +10.0V on the voltage ranges and 20 ma on the current output. p. 16
What do the four LEDs on the 57C410 show?
Each shows that the isolated power supply for its channel is working; if any is not lit, the module is malfunctioning. p. 10, 19
Which terminal strip goes with the 57C410?
The 57C374 terminal strip/cable assembly, which connects field signals to the module faceplate. p. 29
Contents
Chapters and sections
Each line opens the PDF at its page.
- J-3631-1 4 Channel Analog Output Module1
- Warning Notices2
- List of Figures5
- 1.0 Introduction7
- 2.0 Mechanical/Electrical Description9
- 3.0 Installation13
- 4.0 Programming17
- 5.0 Diagnostics and Troubleshooting19
- A Technical Specifications23
- B Module Block Diagram25
- C Field Connections27
- D Related Components29
- E Defining Variables in the Configuration Task31
- Back Cover36