The text of a manual · part 2 of 4

4 Channel Analog Output Module M/N 57C410, pages 10 to 18

Pages 10 to 18 of 36

The original document is the PDF (366 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Reliance Electric 57C410

Page 10

5V 8V

OUTPUT BUFFER

I O S P O T L I A C T A I L O N

Digital

10V VOLTAGE OUTPUT to DATA

Analog

4mA offset

ConĆ verter

CURRENT OUTPUT

COMMON

Figure 2.1 Ć Typical Output Circuit There are 4 LED indicators on the faceplate of the module. The LEDs are arranged in the same order as the output terminals on the faceplate. They are numbered sequentially from zero through three, corresponding to the D/A converter channels. The LED indicators display the status of the four isolated power supplies on the module. A lit LED indicates that the power supply for that channel is operational. See figure 2.2.

2-2

Page 11 read from a scan by OCR; it may hold reading errors

fo

ANALOG OUTPUT 570410

ISOL POWER 0 ISOL POWER 1 ISOL POWER 2 ISOL POWER 3 loememe)

\e) m

5 lel lel el le eel eee x

©

On © O- Vo O- GO B= O= Ns 2s OF O

T nwo © NO i

RELIANCE, ELECTRICS

Figure 2.2 - Module Faceplate

2-3

Page 12

fafadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa afdfdsfdsfdfdsfdsfsadfda asfdfaddfdd

Page 13

3.0 INSTALLATION This section describes how to install and remove the module and its cable assembly.

3.1

Wiring The installation of wiring should conform to all applicable codes. To reduce the possibility of electrical noise interfering with the proper operation of the control system, exercise care when installing the wiring from the system to the external devices. For detailed recommendations refer to IEEE 518.

3.2

Initial Installation Use the following procedure to install the module: Step 1.

Turn off power to the system. All power to the rack as well as all power to the wiring leading to the module should be off.

Step 2.

Mount the terminal strip (M/N 57C374) on a panel. The terminal strip should be mounted to permit easy access to the screw terminals. Make certain that the terminal strip is close enough to the rack so that the cable will reach between the terminal strip and the module.

Step 3.

Fasten field wires to the terminal strip. Typical field connections for voltage output and for 4-20 ma current output are shown in figures 3.1 and 3.2, respectively. Refer to Appendix C for the arrangement of terminal strip connections. Note that for each channel there is only one common, regardless of whether voltage or current output is desired. If you require either 5 volt or 8 volt outputs, you must connect a jumper between the desired voltage and the voltage output on the terminal strip. Make certain that all field wires are securely fastened.

3-1

Page 14

Optional 5V Jumper if required

Twisted Pair

1 2 3

Optional 8V Jumper if required

Voltage Output USER DEVICE

4 5

Common

Figure 3.1 Ć Typical Field Connections for Voltage Output

1 2 3 4 5

< 500 Current Output

USER LOAD

Power Supply (12 Ć 48V)

+

-

Common

Figure 3.2 Ć Typical Field Connections for 4-20 ma Current Output

3-2

Step 4.

Take the module out of its shipping container. Take it out of the antiĆstatic bag, being careful not to touch the connectors on the back of the module.

Step 5.

Insert the module into the desired slot in the rack. Refer to figure 3.3. Use a screwdriver to secure the module into the slot.

Page 15

Typical 16 Slot Rack

16

Typical 10 Slot Rack

P/S

0

1

2

10

3

4

5

6

7

8

9

10 11 12 13 14 15

Figure 3.3 Ć Rack Slot Numbers Step 6.

Attach the terminal strip connector (M/N 57C374) to the mating half on the module. Make certain that the connector is the proper one for this module. Use a screwdriver to secure the connector to the module. Note that both the module and the terminal strip connector have that should be used to prevent the wrong cable from being connected to the module. Rotate the keys on the module and the connector so that they can be connected together securely. It is recommended that, for modules so equipped, the keys on each successive module in the rack be rotated one position to the right of the keys on the preceeding module. Since the keys on the connectors must match their particular modules for the connector to fit, this method will eliminate the possibility of the wrong connector being plugged into a module.

Step 7.

Turn on power to the system. Verify that the four LEDs indicating each isolated power status are lit.

Step 8.

Verify the installation by connecting the programming terminal to the system and running the ReSource Software. Stop all programs that may be running. Use the I/O MONITOR function. If the module is in the local rack, enter the module slot number and register (0-3, corresponding to the four D/A converter channels). If the module is in a remote rack, enter the module slot number of the master remote I/O module, remote I/O drop number (also called the remote rack number), output module slot number, and register (0-3). Write a series of values to each of the channels and verify the analog voltage with a voltmeter. Refer to table 1 for the approximate voltages or currents that should be read.

3-3

Page 16

WARNING BE CAREFUL WHEN WRITING TO THE OUTPUTS TO INSURE THAT NO UNEXPECTED MACHINE MOTION WILL RESULT. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN BODILY INJURY OR DAMAGE TO EQUIPMENT. Table 1

3.3 value

+5V

+8V

+10V

4-20 ma

ă4095

+5.0V

+8.0V

+10.0V

20 ma

ă2047

+2.5V

+4.0V

+5.0V

12 ma

0

0.0V

0.0V

0.0V

ă4 ma

-2047

-2.5V

-4.0V

-5.0V

ă0 ma

-4095

-5.0V

-8.0V

-10.0V

ă0 ma

Module Replacement Use the following procedure to replace a module:

3-4

Step 1.

Turn off power to the rack and all connections.

Step 2.

Use a screwdriver to loosen the screws holding the connector to the module. Remove the connector.

Step 3.

Loosen the screws that hold the module to the rack. Remove the module from the slot in the rack.

Step 4.

Place the module in the antiĆstatic bag it came in, being careful not to touch the connectors on the back of the module. Place the module in the cardboard shipping container.

Step 5.

Take the new module out of the antiĆstatic bag, being careful not to touch the connectors on the back of the module.

Step 6.

Insert the module into the desired slot in the rack. Use a screwdriver to secure the module into the slot.

Step 7.

Attach the field terminal connector (M/N 57C374) to the mating half on the module. Make certain that the connector keys are oriented correctly and that the connector is the proper one for this module (see step 6 in 3.2 Initial Installation). Use a screwdriver to secure the connector to the module.

Step 8.

Turn on power to the rack.

Page 17

4.0 PROGRAMMING This section describes how the data is organized in the module and provides examples of how the module is accessed by the application software. For more detailed information, refer to DCS 5000 Enhanced BASIC Language Instruction Manual (J-3600) or AutoMax Enhanced Basic Language Instruction Manual (J-3675).

4.1

Register Organization The data in the module is organized as four 16Ćbit registers, one for each D/A converter channel. The data in each register is treated as a single precision integer limited to values in the range of +4095 through -4095. Bit 15 is the sign bit and bits 1-11 are the 2's complement data value. Refer to figure 4.1. 15 14

13

12

11

10

9

8

7

6

5

4

3

2

1

0 register 0

S

S

S

S

Channel 0 Data

- register 1

S

S

S

S

Channel 1 Data

- register 2

S

S

S

S

Channel 2 Data

- register 3

S

S

S

S

Channel 3 Data

-

S = sign bit - = not used Figure 4.1 Ć Organization of Register Bits

4.2

Configuration Before any application programs can be written, it is necessary to configure, or set, the definitions of systemĆwide variables, i.e. those that must be globally accessible to all tasks. For DCS 5000 and AutoMax Version 2.1 and earlier, you define systemĆwide variables by writing a Configuration task. For AutoMax Version 3.0 and later, you define systemĆwide variables using the AutoMax Programming Executive. After these variables are defined, you can generate the configuration file automatically, which eliminates the requirement to write a configuration task for the rack. If you are using AutoMax Version 2.1 or earlier, refer to Appendix E for examples that show how to define variables in the configuration task. If you are using AutoMax Version 3.0 or later, see the AutoMax Programming Executive (J-3750) for information about configuring variables.

4-1

Page 18

4.3

Reading And Writing Data In Application Tasks In order for an output module to be referenced by application software, it is first necessary to assign symbolic names to the physical hardware. In AutoMax Version 2.1 and earlier, this is accomplished by either IODEF or RIODEF statements in the configuration task. In AutoMax Version 3.0 and later, you assign symbolic names using the Programming Executive. Each application program that references the symbolic names assigned to the module must declare those names COMMON. The frequency with which tasks, or application programs, read their inputs and write their outputs depends on the language being used. Ladder logic and control block tasks read inputs once at the beginning of each scan and write outputs once at the end of scan. BASIC tasks read an input and write an output for each reference throughout the scan.

4.3.1

BASIC Task Example 2000 3500 5000 5500 6000

COMMON DISPLAY% ! DISPLAY% = -2048 ! END

\!Display value

The symbolic name DISPLAY% references the analog output channel.

4.3.2

Control Block Task Example 2400 3500 5000 5500 6000

COMMON DISPLAY% ! CALL INVERTER( INPUT=2048, & ąOUTPUT=DISPLAY%) ! END

\!Display value

The symbolic name DISPLAY% references the analog output channel.

4.4

Restrictions

4.4.1

Data Limitations Register bit 0 is not connected to the D/A converter. Writing to it will have no effect on the analog output value. When the data is read back, bit 0 will always return 0. Register bits 12, 13, and 14 are also not connected to the D/A converter. If you expect that the digital value to be written to an output will exceed the range +4095, place a software limit on the value before writing it to the analog output. Otherwise, if a value greater than +4095 is written to the analog output, the output will be the analog value proportional to the value of bits 1-11 and the sign bit 15.

4-2