For the Reliance Electric 57C410
Page 19
5.0 DIAGNOSTICS AND TROUBLESHOOTING This section explains how to troubleshoot the module and field connections.
5.1
Incorrect Data Problem: The output is either always off, always on, or different than expected. The possible causes of this are a module in the wrong slot, a malfunctioning module, or a programming error. It is also possible that the output is either not wired or wired to the wrong device. Use the following procedure to isolate the problem: Step 1.
Verify that the output module is in the correct slot and that the I/O definitions are correct. Refer to figure 3.3. Verify that the slot number being referenced agrees with the slot number defined in the configuration task. For this module, the register number is always zero. Verify that the register number of the output module agrees with the D/A channel number (0-3). For remote I/O installations, also verify that the master slot and drop number are defined correctly.
Step 2.
Verify that the isolated power supplies are working. Make certain that the four LEDs on the module faceplate are lit. If any of them are not lit, the module is malfunctioning.
Step 3.
Verify that the terminal board is wired correctly. Confirm that all connections at the terminal strip are tight. Verify that each of the analog output channels is wired to the correct device and that the jumpers on the terminal strip (if required) are connected. Refer to figures 3.1 and 3.2.
Step 4.
Verify that the module can be accessed. Connect the programming terminal to the system and run the ReSource Software. Stop all programs that may be running. Connect a voltmeter to the voltage output of each channel being checked. Use the I/O MONITOR function and write the values in table 1 to the channel being investigated. The voltmeter should read the voltages listed in table 1. If it does, the problem lies in the user application program (proceed to step 7). If the values exceed the accuracy limit, the offset and gain adjustment are not correct and the module is malfunctioning.
5-1
Page 20
WARNING BE CAREFUL WHEN WRITING TO THE OUTPUTS TO INSURE THAT NO UNEXPECTED MACHINE MOTION WILL RESULT. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN BODILY INJURY OR DAMAGE TO EQUIPMENT. Step 5.
Verify that the external field device(s) meet module specifications. To test voltage outputs, remove the wires for the field devices from the terminal strip and repeat the test in step 4. If the voltmeter now reads the correct values, either the module is malfunctioning or the output device impedance is too low and the current limit feature is preventing the channel from outputing the proper voltage. Verify the hardware functionality by systematically swapping out modules. After each swap, if the problem is not corrected, replace the original module before swapping out the next module. To test 4-20 ma current outputs, remove the connector from the face of the module. Connect a voltmeter across the terminal strip connections that are wired to the load and verify that the voltage is within specifications. Next, connect a current meter across the terminal strip connections and verify that the current is approximately 20 ma. If these tests are not successfull, the problem lies in the field wiring or the external device. Check the cable for continuity between the faceplate connector and the terminal strip. Remember to replace any wires or connectors that have to be removed.
Step 6.
Verify that the hardware is working correctly. Verify the hardware functionality by systematically swapping out modules. After each swap, if the problem is not corrected, replace the original module before swapping out the next module. To test local I/O, first replace the output module. Next, replace the processor module (s). If the problem persists, take all of the modules out of the backplane except one processor module and the output module. If the problem is now corrected, one of the other modules in the rack is malfunctioning. Reconnect the other modules one at a time until the problem reappears. If none of these tests reveals the problem, replace the backplane. To test remote I/O, first verify that the remote I/O system is communicating with the drop that contains the output module being tested. Next, determine whether the output module is the only module in the rack that is not working. If more than one module is not working correctly, the problem most likely lies in the remote I/O system. If the problem does not lie in the system, it probably involves the remote rack.
5-2
Page 21
To test the remote rack, first replace the output module. Next, replace the slave remote I/O module. If the problem persists, take all of the modules out of the remote backplane except the slave remote I/O module and the output module. If the problem is now corrected, one of the other modules in the rack is malfunctioning. Reconnect the other modules one at a time until the problem reappears. If the problem proves to be neither in the remote I/O system nor in the remote rack, try replacing the backplane. Step 7.
Verify that the user application program is correct. If none of the above steps has corrected the problem, verify that the application program that uses the symbolic names assigned to the module has defined those names as COMMON. Verify that the symbolic name in question is being referenced in the application program. This can be done indirectly by monitoring the name with the VARIABLE MONITOR function in the ReSource software.
Problem: A or through appears on the processor module's LED. This error message indicates that there was a bus error when the system attempted to access the module. The possible causes of this error are a missing module, a module in the wrong slot, or a malfunctioning module. Refer to the DCS Processor Module Instruction Manual (J-3635) or AutoMax Processor Module Instruction Manual (J-3650) for more information. Use the following procedure to isolate a bus error: Step 1.
Verify that the output module is in the correct slot and that the I/O definitions are correct. Refer to figure 3.3. Verify that the slot number being referenced agrees with the slot number defined in the configuration task. Verify that the register number of the output module agrees with the D/A channel number (0-3). For remote I/O installations, also verify that the master slot and remote drop number are defined correctly.
Step 2.
Verify that the module can be accessed. Connect the programming terminal to the system and run the ReSource Software. Stop all programs that may be running. Use the I/O MONITOR function to display each of the channels. If the programmer is able to monitor the outputs, then try to write zeros to the outputs.
5-3
Page 22
WARNING BE CAREFUL WHEN WRITING TO THE OUTPUTS TO INSURE THAT NO UNEXPECTED MACHINE MOTION WILL RESULT. FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN BODILY INJURY OR DAMAGE TO EQUIPMENT. If the programmer is able to read and write to the output module, the problem lies in the application software and you need to refer to step 1 again. If the programmer cannot read and write the outputs, the problem lies in the hardware (proceed to step 3). Step 3.
Verify that the hardware is working correctly. Verify the hardware functionality by systematically swapping out the output module, the processor module(s), and the backplane. After each swap, if the problem is not corrected, replace the original item before swapping out the next item. For remote I/O installations, systematically swap out the output module, the slave remote module, and the backplane. After each swap, if the problem is not corrected, replace the original item before swapping out the next item.
5-4
Page 23
-
D Storage temperature: -40_ C Ć 85_ C D Operating temperature: 0_ C Ć 60_ C D Humidity: 5-90% nonĆcondensing
D 13.7 Watts
D Height: 11.75 inches D Width: 1.25 inches D Depth: 7.375 inches
D +5 volts: 2750 ma D +12 volts: 55 ma D -12 volts: 5 ma
D Number of channels: 4 D Output ranges: +5 volts, 10 ma max +8 volts, 10 ma max +10 volts, 10 ma max 4-20 ma, external power ăsupply required (12-48 volts) ăload impedance <= 500 ohms. D Resolution:
voltage outputs -12 bits including sign 4-20 ma - 11 bits (sign bit always 0)
D Accuracy:
+ 0.10% of full scale (voltage output) + 0.15% of full scale (current output)
D Output Filter: +5 Volts Ć + 8 Volts Ć +10 Volts Ć 4-20 ma Ć first order 200 Hz low pass first order 125 Hz low pass first order 100 Hz low pass none
D Voltage outputs shortĆcircuit protected D Each channel individually isolated D 2500 volt isolation between logic common and outputs
A-1
Page 24
fafadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa afdfdsfdsfdfdsfdsfsadfda asfdfaddfdd
Page 25
-
4 Channel Analog Output (57C410)
Channel 0
ADDRESS ID BUS ADDRESS ADDRESS ID BUS DECODER OUTPUT BUFFER
WDOG OK BD RESET INITIALIZE
CONTROL LOGIC
BYTE HI EN
I S O L A T I O N
DATA
ISOL
10V
2
8V
3
CUR
4
COM
5
5V
6
10V
7
8V
8
CUR
9
COM
10
5V
11
10V
12
8V
13
CUR
14
COM
15
5V
16
10V
17
8V
18
CUR
19
COM
20
Channel 1
READ MEM XFER ACK GATE OUTPUT BUFFER INPUT DATA BUFFER BUS
I S O L A T I O N
DATA
Power Channel 2
INPUT DATA BUFFER
+5V +12V
OUTPUT BUFFER
Isolated Digital to Analog Converter Power
I S O L A T I O N
DATA
Digital to Analog Converter
ISOL Power Channel 3
Channel 0 Channel 1 Channel 2
Digital to Analog Converter
ISOL
GATE
+12V
1
Power
WRITE MEM
+5V
Digital to Analog Converter
5V
OUTPUT BUFFER
Channel 3
I S O L A T I O N
DATA
ISOL
Digital to Analog Converter
Power
Channel 0 ISOL Power Channel 1 ISOL Power Channel 2 ISOL Power Channel 3 ISOL Power
B-1
Page 26
fafadfdfdasfdsfdsdsdfdsfdsfdsfsdfdsa afdfdsfdsfdfdsfdsfsadfda asfdfaddfdd
Page 27
Appendix C
Field Connections
Channel Pin No. Function 1 5 volt jumper 2 voltage output 0 3 8 volt jumper 4 current output 5 common 6 5 volt jumper voltage output 1 8 8 volt jumper 9 current output 10 common 11 5 volt jumper 12 voltage output 2 13 8 volt jumper 14 current output 15 common 16 5 volt jumper 17 voltage output 3 18 8 volt jumper 19 current output 20 common
C-1