The text of a manual · part 11 of 30
Variable speed drives Altivar 61 Catalogue: DC chokes
Pages 64 to 67 of 211, from Variable speed drives Altivar 61 Catalogue
The original document is the PDF (4.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Telemecanique Altivar 61 ATV61, Schneider Altivar 61 ATV61 and Square D Altivar 61 ATV61
Page 64
Presentation
0
Variable speed drives for asynchronous motors
0
Altivar 61: Reduction of current harmonics Option: DC chokes
The main solutions for reducing current harmonics are as follows: b DC chokes, see below b Line chokes, see page 66 b 16% and 10% passive filters, see page 69 b Use of passive filters with a DC choke, see pages 69 to 73 These 4 solutions can be used on the same installation. It is always easier and less expensive to handle current harmonics at installation level as a whole rather than at the level of each individual unit, particularly when using passive filters and active compensators.
DC chokes
PO
PA/+
DC choke
L1 M1 3
L2
PC/–
L3
DC chokes are used to reduce current harmonics in order to comply with standard IEC/61000-3-2 for drives on which the line current is greater than 16 A and less than 75 A. Using the DC choke with the drive complies with draft standard IEC/61000-3-12 provided that the RSCE u 120 (1) at the point of connection to the public network. 120 represents the minimum value of RSCE (1) for which the values in table 4 of draft standard IEC/61000-3-12 are not exceeded. It is the responsibility of the installer or the user to ensure that the device is connected correctly to a connection point with an RSCE u 120. The DC choke is connected to the drive power terminals.
Altivar 61
It is supplied as standard with ATV 61HD55M3X, HD90M3X and ATV 61HD90N4…HC63N4 drives and is integrated into ATV 61WpppN4 and ATV 61WpppN4C drives. Applications Reduction of current harmonics. Reduction of THD to 5% or to 10% in association with passive filters, see pages 69 to 73. Maintaining the motor torque in relation to the DC choke. (1) Short-circuit ratio
Characteristics: page 65
References: page 65
Dimensions: page 103
Schemes: pages 114 to 117, 123 and 124
62 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 65
Presentation (continued)
Variable speed drives for asynchronous motors
0
0
Altivar 61: Reduction of current harmonics Option: DC chokes
Example of current harmonic levels for ATV 61H075M3…ATV 61HD90M3X drives (1) Motor power
For ATV 61 drives kW HP
Line supply Line Line current Isc A kA
Current harmonic levels H1 H5 H7 H11 H13
H17
H19
H23
H25
H29
H31
H35
H37
H41
H43
H47
H49
A
%
%
%
%
%
%
%
%
%
%
%
%
5.6 4.97 5.36 5.24 5.2 5.3 5.38 5.37 5.3 5.2 5.23 4.86 4.97 5.01
4.63 4.19 4.1 3.94 3.73 4.03 4.09 4.08 4.1 3.9 3.99 3.44 3.54 3.49
4.07 3.54 3.8 3.67 3.61 3.72 3.82 3.77 3.7 3.7 3.63 3.29 3.33 3.33
3.42 3.08 3 2.88 2.71 2.98 2.98 3.01 3 2.9 2.95 2.52 2.6 2.55
3.18 2.71 2.9 2.76 2.68 2.79 2.91 2.82 2.7 2.7 2.68 2.38 2.36 2.33
2.71 2.43 2.37 2.27 2.14 2.36 2.35 2.37 2.4 2.3 2.32 1.98 2.03 1.96
2.59 2.17 2.29 2.15 2.06 2.17 2.31 2.19 2.1 2.1 2.04 1.77 1.72 1.66
2.24 2.01 1.95 1.87 1.76 1.94 1.92 1.94 1.9 1.9 1.89 1.62 1.63 1.53
2.17 1.78 1.85 1.71 1.61 1.71 1.87 1.73 1.6 1.7 1.57 1.34 1.26 1.2
1.91 1.7 1.66 1.58 1.49 1.63 1.63 1.62 1.6 1.6 1.57 1.34 1.32 1.19
1.86 1.5 1.52 1.37 1.27 1.36 1.54 1.37 1.2 1.3 1.22 1.02 0.94 0.9
1.66 1.47 1.44 1.37 1.28 1.4 1.4 1.38 1.3 1.3 1.32 1.12 1.06 0.9
%
%
%
%
THD (2)
3-phase supply voltage: 230 V 50 Hz, with optional DC choke 0.75 1 1.5 2 2.2 3 3 – 4 5 5.5 7.5 7.5 10 11 15 15 20 18.5 25 22 30 30 40 37 50 45 60
H075M3 3.05 HU15M3 6.04 HU22M3 8.33 HU30M3 11.12 HU40M3 14.53 HU55M3 19.2 HU75M3 26.1 HD11M3X 36.6 HD15M3X 48.6 HD18M3X 60 HD22M3X 70.28 HD30M3X 96.9 HD37M3X 116.1 HD45M3X 138.7
5 5 5 5 5 8 15 15 15 22 22 22 22 22
2.81 5.55 7.64 10.19 13.29 17.9 23.9 34.2 45.8 56 65.92 88.78 107.9 130.5
31.99 20.91 8.88 33.65 21.59 8.14 34.89 21.11 8.78 35.17 20.68 8.71 36.23 20.51 8.73 30.68 17.26 8.75 35.23 21.09 8.82 30.91 17.12 8.86 28.3 14.9 8.8 31.5 17.1 8.7 29.81 15.91 8.7 36.68 19.42 8.38 33.09 16.4 8.59 30.15 13.86 8.65
7.36 6.84 6.72 6.48 6.2 6.31 6.71 6.36 6.2 6.1 6.15 5.67 5.59 5.38
41.27 42.4 43.33 43.22 43.91 38 43.96 38.14 35 38.5 36.62 43.51 39.24 35.7
3-phase supply voltage: 230 V 50 Hz, with DC choke supplied as standard with the drive 55 75 90
75 100 125
HD55M3X 120 HD75M3X 163.0 HD90M3X 196.06
14 35 35
109.29 39.77 18.67 7.98 4.67 4.16 2.59 2.61 1.81 1.76 1.35 1.23 1.02 0.87 0.78 0.63 0.59 45.36 148.35 38.83 20.24 8.2 5.43 4.58 3.15 3.04 2.24 2.17 1.7 1.62 1.33 1.23 1.06 0.94 0.84 45.51 177.16 40.75 21.04 8.1 5.26 4.42 2.93 2.88 2.06 2.04 1.55 1.49 1.21 1.12 0.95 0.85 0.75 47.41
Example of current harmonic levels for ATV 61H075N4…ATV 61HC63N4 drives (1) Motor power
For ATV 61 drives kW HP
Line supply Line Line current Isc A kA
Current harmonic levels H1 H5 H7 H11 H13
H17
H19
H23
H25
H29
H31
H35
H37
H41
H43
H47
H49
A
%
%
%
%
%
%
%
%
%
%
%
%
5.6 5.61 5.41 5.88 5.52 6.12 5.28 5.41 5.43 5.39 5.28 5.32 5.23 4.85 4.98 4.84
4.8 4.74 4.36 4.57 4.17 5.18 3.95 4.02 4.02 4.04 4.09 4.07 4 3.48 3.62 3.52
4.1 4.06 3.89 4.24 3.93 4.45 3.78 3.8 3.82 3.78 3.75 3.73 3.65 3.33 3.38 3.21
3.5 3.49 3.2 3.38 3.05 3.83 2.89 2.95 2.94 2.98 3.03 3.01 2.97 2.54 2.67 2.59
3.2 3.16 3.01 3.28 3 3.48 2.9 2.86 2.88 2.83 2.85 2.79 2.71 2.44 2.44 2.25
2.8 2.76 2.53 2.67 2.4 3.04 2.28 2.32 2.32 2.34 2.4 2.37 2.34 2 2.09 2
2.6 2.57 2.43 2.63 2.38 2.85 2.32 2.23 2.24 2.18 2.25 2.15 2.07 1.85 1.81 1.61
2.3 2.28 2.09 2.19 1.98 2.52 1.88 1.9 1.9 1.9 1.97 1.94 1.9 1.64 1.69 1.58
2.2 2.15 2.01 2.16 1.93 2.4 1.9 1.77 1.78 1.7 1.81 1.69 1.61 1.42 1.37 1.17
1.9 1.94 1.77 1.86 1.68 2.14 1.59 1.6 1.6 1.58 1.67 1.62 1.58 1.38 1.39 1.25
1.9 1.83 1.7 1.8 1.58 2.06 1.58 1.42 1.43 1.33 1.48 1.33 1.26 1.1 1.04 0.88
1.7 1.68 1.53 1.6 1.45 1.85 1.37 1.37 1.37 1.33 1.44 1.38 1.32 1.17 1.14 0.96
%
%
%
%
THD (2)
3-phase supply voltage: 400 V 50 Hz, with optional DC choke 0.75 1 1.5 2 2.2 3 3 – 4 5 5.5 7.5 7.5 10 11 15 15 20 18.5 25 22 30 30 40 37 50 45 60 55 75 75 100
H075N4 HU15N4 HU22N4 HU30N4 HU40N4 HU55N4 HU75N4 HD11N4 HD15N4 HD18N4 HD22N4 HD30N4 HD37N4 HD45N4 HD55N4 HD75N4
1.77 3.34 4.83 6.13 8.24 10.81 15.01 21.1 28.2 33.9 40.87 54.1 66.43 83.11 98.6 134
5 5 5 5 5 22 10 9 12 12 22 20 22 22 22 22
1.61 3.03 4.4 5.67 7.51 9.83 13.8 19.3 25.8 31.9 37.85 50.6 62.6 75.56 91.69 125.9
34.6 23.7 8.9 35.55 23.53 8.95 35.79 22.77 8.7 31.61 18.82 9.41 36.16 21.63 9 34.85 23.08 9.68 34.09 20.49 8.57 35.22 20.11 8.95 35.22 20.01 8.98 28.36 15.16 8.85 32.79 18.73 8.6 29.97 16.26 8.75 28.49 15.01 8.63 38.31 20.96 8.24 32.94 16.76 8.5 30.65 14.43 8.4
7.8 7.65 7.11 6.82 8.17 4.05 6.43 6.5 6.49 6.18 6.42 6.27 6.08 5.81 5.68 5.4
44.95 45.48 45 40.08 44.72 45.19 42.25 43.1 43.06 35.23 40.4 36.99 35.13 45.59 39.29 36.2
3-phase supply voltage: 400 V 50 Hz, with DC choke supplied as standard with the drive 90 125 HD90N4 158.81 35 145.1 36.72 20.66 8.33 6.19 4.93 3.78 3.43 2.75 2.56 2.13 1.99 1.72 1.59 1.4 1.29 1.16 44.26 110 150 HC11N4 188.59 35 175.53 33.15 16.56 8.29 5.6 4.81 3.57 3.26 2.58 2.36 1.97 1.77 1.53 1.36 1.2 1.04 0.95 39.26 132 200 HC13N4 226.53 35 209.69 34.91 17.14 8.21 5.36 4.66 3.33 3.11 2.4 2.22 1.82 1.64 1.41 1.24 1.1 0.94 0.86 40.86 160 250 HC16N4 271.34 50 251.7 34 17.22 8.28 5.59 4.8 3.51 3.23 2.56 2.35 1.94 1.76 1.51 1.34 1.2 1.04 0.95 40.24 200 300 HC22N4 337.95 50 313.51 34.38 16.75 8.23 5.33 4.65 3.32 3.09 2.39 2.2 1.81 1.63 1.38 1.22 1.07 0.91 0.84 40.24 220 350 HC22N4 369.49 50 344.77 32.98 15.54 8.23 5.26 4.66 3.33 3.07 2.39 2.17 1.79 1.57 1.35 1.16 1.03 0.86 0.79 38.53 250 400 HC25N4 418.15 50 390.95 32.69 14.89 8.15 5.14 4.56 3.26 2.98 2.32 2.07 1.71 1.48 1.29 1.07 0.97 0.78 0.72 37.95 280 450 HC31N4 471.17 50 437.41 34.78 15.9 8.1 4.92 4.44 3.04 2.86 2.16 1.97 1.6 1.4 1.21 1 0.9 0.72 0.67 40.05 315 500 HC31N4 526.6 50 492.29 33.1 14.44 8.08 4.85 4.41 3.05 2.81 2.15 1.9 1.57 1.32 1.15 0.92 0.84 0.65 0.61 37.99 355 – HC40N4 591.92 50 554.81 32.59 13.7 8 4.73 4.32 2.99 2.71 2.09 1.8 1.5 1.22 1.08 0.84 0.78 0.57 0.55 37.2 400 600 HC40N4 660.94 50 622.77 31.23 12.61 7.95 4.71 4.26 2.99 2.63 2.06 1.71 1.45 1.12 1.01 0.75 0.7 0.51 0.49 35.57 500 700 HC50N4 834.65 50 781.47 33.52 13.05 7.75 4.28 3.97 2.65 2.37 1.82 1.49 1.26 0.96 0.88 0.63 0.61 0.43 0.42 37.54 560 800 HC63N4 930.84 50 874.82 32.5 12.37 7.76 4.28 3.96 2.67 2.34 1.78 1.46 1.21 0.86 0.79 0.56 0.54 0.39 0.38 36.39 630 900 HC63N4 1037.11 50 980.2 31.06 11.11 7.64 4.23 3.81 2.63 2.15 1.73 1.27 1.13 0.77 0.73 0.5 0.48 0.39 0.36 34.61 (1) Example of current harmonic levels up to harmonic order 49 for a 400 V/50 Hz supply with chokes connected between the PO and PA/+ terminals on the Altivar 61. (2) Total harmonic distortion conforming to draft standard IEC 61000-3-12.
Characteristics: page 65
References: page 65
Dimensions: page 103
Schemes: pages 114 to 117, 123 and 124
63 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 66
Presentation (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61: Reduction of current harmonics Option: DC chokes
Example of current harmonic levels for ATV 61WpppN4 and ATV 61WpppN4C drives (1) 3-phase supply voltage: 400 V 50 Hz, with integrated DC choke Motor power
For ATV 61 drives kW HP 0.75 1
Line supply Line Line current Isc A kA 1.75 5
Current harmonic levels H1 H5 H7 H11 H13
H17
H19
H23
H25
H29
H31
H35
H37
H41
H43
H47
H49
THD (2)
A % % % % % % % % % % % % % % % % W075N4 1.61 32.12 22.41 8.97 7.96 5.77 5 4.25 3.69 3.36 2.93 2.78 2.43 2.37 2.08 2.06 1.81 42.65 W075N4C 1.5 2 WU15N4 3.38 5 3.08 34.84 23.58 8.77 7.71 5.60 4.77 4.11 3.51 3.24 2.78 2.67 2.30 2.26 1.96 1.96 1.71 45.12 WU15N4C 2.2 3 WU22N4 4.77 5 4.38 33.37 22.01 8.8 7.48 5.6 4.7 4.1 3.48 3.23 2.76 2.65 2.28 2.24 1.94 1.93 1.69 43.12 WU22N4C 3 – WU30N4 6.39 5 5.84 35.07 22.41 8.51 7.38 5.36 4.63 3.89 3.43 3.04 2.73 2.48 2.26 2.08 1.93 1.79 1.67 44.48 WU30N4C 4 5 WU40N4 8.39 5 7.64 36.07 22.73 8.45 7.27 5.29 4.52 3.82 3.33 2.97 2.65 2.42 2.19 2.02 1.86 1.73 1.61 45.34 WU40N4C 5.5 7.5 WU55N4 10.71 22 9.9 30.94 21 9.56 8.22 6.09 5.31 4.47 3.94 3.52 3.14 2.9 2.6 2.45 2.21 2.11 1.92 41.41 WU55N4C 7.5 10 WU75N4 15.10 22 13.73 35.93 23.66 8.72 7.55 5.53 4.65 4.03 3.41 3.16 2.7 2.59 2.23 2.19 1.89 1.88 1.64 45.9 WU75N4C 11 15 WD11N4 20.75 22 19.35 29.81 18.76 9.1 7.38 5.76 4.79 4.2 3.56 3.29 2.83 2.69 2.34 2.26 1.99 1.93 1.72 38.88 WD11N4C 15 20 WD15N4 28.74 22 26.24 35.65 22.28 8.55 7.22 5.32 4.50 3.83 3.32 2.97 2.63 2.41 2.17 2.01 1.84 1.71 1.58 44.79 WD15N4C 18.5 25 WD18N4 35.41 22 32.11 37.49 23.29 8.44 7.13 5.22 4.36 3.74 3.19 2.88 2.52 2.32 2.08 1.93 1.75 1.63 1.51 46.65 WD18N4C 22 30 WD22N4 41.66 22 37.87 37.21 22.55 8.38 6.95 5.16 4.26 3.69 3.13 2.84 2.47 2.29 2.02 1.89 1.7 1.6 1.46 45.99 WD22N4C 30 40 WD30N4 54.02 22 50.77 29.05 16.24 8.66 6.55 5.39 4.32 3.86 3.22 2.96 2.55 2.36 2.09 1.92 1.76 1.59 1.5 36.54 WD30N4C 37 50 WD37N4 66.15 22 62.09 29.46 16.33 8.76 6.51 5.41 4.25 3.85 3.15 2.93 2.48 2.32 2.03 1.86 1.7 1.52 1.45 36.89 WD37N4C 45 60 WD45N4 80.82 22 75.33 31.82 17.26 8.57 6.24 5.22 4.02 3.69 2.97 2.78 2.34 2.18 1.91 1.73 1.59 1.39 1.35 38.98 WD45N4C 55 75 WD55N4 100.42 22 92.45 35.41 19.11 8.24 6.06 4.92 3.78 3.43 2.77 2.57 2.16 2 1.73 1.6 1.42 1.3 1.18 42.51 WD55N4C 75 100 WD75N4 133.88 22 125.86 30.11 14.93 8.5 5.85 5.07 3.82 3.49 2.81 2.56 2.19 1.92 1.76 1.46 1.43 1.12 1.18 36.35 WD75N4C 90 125 WD90N4 164.46 35 152.4 33.86 17.83 8.24 5.98 4.93 3.8 3.43 2.8 2.57 2.18 2 1.75 1.6 1.43 1.29 1.18 40.65 WD90N4C (1) Example of current harmonic levels up to harmonic order 49 for a 400 V/50 Hz supply with chokes connected between the PO and PA/+ terminals on the Altivar 61. (2) Total harmonic distortion conforming to draft standard IEC 61000-3-12.
Characteristics: page 65
References: page 65
Dimensions: page 103
Schemes: pages 114 to 117, 123 and 124
64 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 67
Characteristics, references
0
Variable speed drives for asynchronous motors
0
Altivar 61: Reduction of current harmonics Option: DC chokes
General characteristics Degree of protection Maximum relative humidity Ambient air temperature around the device
Operation
°C
Storage
°C m
Maximum operating altitude Voltage drop Maximum current
IP 20 95% - 10…+ 50 without derating Up to 60°C with current derating of 2.2% per °C above 50°C - 40…+ 65 1000 without derating 1000…3000 with current derating of 1% per additional 100 m 4 to 6% 1.65 x nominal current for 60 seconds
Connection characteristics Type of terminal Maximum connection capacity and tightening torque
VW3 A4 511
Earth 10 mm2 (AWG 6) 1.2…1.4 Nm 10 mm2 (AWG 6) 1.2…1.4 Nm 10 mm2 (AWG 6) 1.2…1.4 Nm 10 mm2 (AWG 6) 1.2…1.4 Nm 10 mm2 (AWG 6) 1.2…1.4 Nm –
VW3 A4 512
–
VW3 A4 501…505 VW3 A4 506 VW3 A4 507 VW3 A4 508, 509 VW3 A4 510
Power supply 2.5 mm 2 (AWG 12) 0.4…0.6 Nm 4 mm2 (AWG 10) 0.5…0.8 Nm 6 mm2 (AWG 8) 0.8…1 Nm 10 mm2 (AWG 6) 1.2…1.4 Nm 35 mm2 (AWG 0) 2.5…3 Nm Connected on a bar, Ø 9 – Connected on a bar, Ø 9 –
DC chokes (1) For drives
Inductance value mH
Nominal current A
Loss
Reference
W
Weight kg
3-phase supply voltage: 200…240 V 50/60 Hz ATV 61H075M3 6.8 ATV 61HU15M3 3.2 ATV 61HU22M3 2.2 ATV 61HU30M3 1.6 ATV 61HU40M3, 1.2 HU55M3 ATV 61HU75M3 0.7 ATV 61HD11M3X, 0.52 HD15M3X ATV 61HD18M3X, 0.22 HD22M3X ATV 61HD30M3X… 0.09 HD45M3X
8 14.3 19.2 27.4 44
22.5 32 33 43 61
VW3 A4 503 VW3 A4 505 VW3 A4 506 VW3 A4 507 VW3 A4 508
1.700 2.200 2.500 3.000 4.500
36 84.5
30.5 77
VW3 A4 509 VW3 A4 510
2.500 6.200
171.2
86
VW3 A4 511
15.500
195
73
VW3 A4 512
10.000
3-phase supply voltage: 380…480 V 50/60 Hz ATV 61H075N4 18 2.25 7.7 VW3 A4 501 0.650 ATV 61HU15N4 10 4.3 11 VW3 A4 502 1.000 ATV 61HU22N4, 6.8 8 22.5 VW3 A4 503 1.700 HU30N4 ATV 61HU40N4 3.9 10.7 27 VW3 A4 504 1.650 ATV 61HU55N4 3.2 14.3 32 VW3 A4 505 2.200 ATV 61HU75N4 2.2 19.2 33 VW3 A4 506 2.500 ATV 61HD11N4 1.6 27.4 43 VW3 A4 507 3.000 ATV 61HD15N4, 1.2 44 57.5 VW3 A4 508 4.300 HD18N4 ATV 61HD22N4… 0.52 84.5 98.3 VW3 A4 510 5.600 HD37N4 ATV 61HD45N4… 0.22 171.2 128 VW3 A4 511 9.100 HD75N4 (1) For ATV 61HD55M3X…HD90M3X, ATV 61HD90N4…HC63N4 drives, the choke is supplied as standard with the drive. It is integrated into ATV 61Wppp N4 and ATV 61Wppp N4C drives.
Presentation: pages 62 to 64
Dimensions: page 103
Schemes: pages 114 to 117, 123 and 124
65 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com