Page 68

Presentation

0

Variable speed drives for asynchronous motors

0

Altivar 61: Reduction of current harmonics Option: Line chokes

Line chokes

L1 L2 Line choke

Altivar 61

M1 3

A line choke can be used to provide improved protection against overvoltages on the line supply and to reduce the current harmonics produced by the drive.

L3

Line chokes are compulsory on ATV 61HU40M3…HU75M3 drives supplied with a single phase 200…240 V 50/60 Hz supply voltage. They can be used instead of a DC choke. In this case, to order an ATV 61HD55M3X…HD90M3X and ATV 61HD90N4…HC63N4 drive without DC choke, add the letter D to the end of the drive’s reference, see pages 18 and 19. The recommended chokes can be used to limit the line current. They have been developed in line with standard EN 50178 (VDE 0160 level 1 high energy overvoltages on the line supply). The inductance values are defined for a voltage drop between phases of between 3% and 5% of the nominal line voltage. Values higher than this will cause loss of torque. These chokes should be installed upstream of the drive. Applications The use of line chokes is recommended in particular under the following circumstances: b Close connection of several drives in parallel b Line supply with significant disturbance from other equipment (interference, overvoltages) b Line supply with voltage imbalance between phases above 1.8% of the nominal voltage b Drive supplied by a line with very low impedance (in the vicinity of a power transformer 10 times more powerful than the drive rating) b Installation of a large number of frequency converters on the same line b Reduction of overload in cos ϕ correction capacitors, if the installation has a power factor correction unit

Characteristics: page 67

References: page 68

Dimensions: page 103

Schemes: pages 114 to 118

66 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 69

Characteristics

0

Variable speed drives for asynchronous motors

0

Altivar 61: Reduction of current harmonics Option: Line chokes

General characteristics Type of choke

VW3 A58501. A58502

Conformity to standards Degree of protection Atmospheric pollution Degree of pollution Vibration resistance Shock resistance Maximum relative humidity Ambient air temperature around the device

Choke Terminals

Operation

°C

Storage

°C

Isolation class Clearance distance in air Leakage distance in air Maximum operating altitude mm mm m

Voltage drop Maximum current

VW3 A4 551... A4 553

VW3 A4 554, A4 555

VW3 A4 556... A4 560

VW3 A4 561, A4 564, 565, A4 568, 569 EN 50178 (VDE 0160 level 1 high energy overvoltages on the line supply), IEC 60076 (with HD 398) IP 00 IP 20 IP 10 IP 00 3 C2, 3B1, 3S1 conforming to IEC 721.3.3 2 conforming to EN 50178 1.5 mm from 3…13 Hz, 1 gn from 13…200 Hz, conforming to IEC 60068-2 15 gn for 11 ms conforming to IEC/EN 60068-2-27 95% 0…+ 45 without derating Up to + 55°C with current derating of 2% per °C above 45°C - 25…+ 70 F 5.5 conforming to IEC 60664 11.5 conforming to IEC 60664 1000 without derating 1000…3000 with current derating of 1% per additional 100 m Between 3 % and 5% of the nominal supply voltage. Values higher than this will cause loss of torque. 1.65 x nominal current for 60 seconds

Connection characteristics Maximum connection capacity and tightening torque

VW3 A58501 VW3 A58502 VW3 A4 551, 552 VW3 A4 553 VW3 A4 554 VW3 A4 555 VW3 A4 556 VW3 A4 557, 558 VW3 A4 559…561 VW3 A4 564, 565 VW3 A4 568 VW3 A4 569

Presentation: page 66

References: page 68

16 mm2, (AWG 4) 1.2…1.4 Nm 6 mm2, (AWG 8) 0.8…1 Nm 2.5 mm 2, (AWG 12) 0.4…0.6 Nm 6 mm2, (AWG 8) 0.8…1 Nm 16 mm2, (AWG 4) 1.2…1.4 Nm 35 mm2, (AWG 0) 2.5…3 Nm Connected on a bar, Ø 6.5 mm – Connected on a bar, Ø 9 mm – Connected on a bar, Ø 11 mm – Connected on a bar, Ø 13 mm – Connected on a bar, Ø 11 mm – Connected on a bar, Ø 13 mm –

Dimensions: page 103

Schemes: pages 114 to 118

67 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 70

References

0

Variable speed drives for asynchronous motors

0

Altivar 61: Reduction of current harmonics Option: Line chokes

Line chokes For drives

Line Line choke supply Induct- Nominal Saturation Loss Line Isc ance current current value kA mH A A W

Number required per drive

Reference

Weight kg

Single phase supply voltage: 200…240 V 50/60 Hz ATV 61HU40M3

5

2

25

–

45

1

VW3 A58501

3.500

ATV 61HU55M3

5

1

45

–

50

1

VW3 A58502

3.500

ATV 61HU75M3

22

1

45

–

50

1

VW3 A58502

3.500

3-phase supply voltage: 200…240 V 50/60 Hz ATV 61H075M3

5

10

4

–

45

1

VW3 A4 551

1.500

ATV 61HU15M3, HU22M3

5

4

10

–

65

1

VW3 A4 552

3.000

ATV 61HU30M3

5

2

16

–

75

1

VW3 A4 553

3.500

ATV 61HU40M3

5

1

30

–

90

1

VW3 A4 554

6.000

ATV 61HU55M3

22

1

30

–

90

1

VW3 A4 554

6.000

ATV 61HU75M3, HD11M3X

22

0.5

60

–

94

1

VW3 A4 555

11.000

ATV 61HD15M3X

22

0.3

100

–

260

1

VW3 A4 556

16.000

ATV 61HD18M3X…HD45M3X

22

0.15

230

–

400

1

VW3 A4 557

45.000

ATV 61HD55M3XD

35

0.066

344

685

258

1

VW3 A4 561

47.000

ATV 61HD75M3XD

35

0.066

344

685

258

1

VW3 A4 561

47.000

ATV 61HD90M3XD

35

0.038

613

1150

307

1

VW3 A4 564

73.000

3-phase supply voltage: 380…480 V 50/60 Hz ATV 61H075N4, HU15N4

5

10

4

–

45

1

VW3 A4 551

1.500

ATV 61HU22N4…HU40N4

5

4

10

–

65

1

VW3 A4 552

3.000

ATV 61HU55N4, HU75N4

22

2

16

–

75

1

VW3 A4 553

3.500

ATV 61HD11N4, HD15N4

22

1

30

–

90

1

VW3 A4 554

6.000

ATV 61HD18N4, HD22N4

22

0.5

60

–

94

1

VW3 A4 555

11.000

ATV 61HD30N4…HD55N4

22

0.3

100

–

260

1

VW3 A4 556

16.000

ATV 61HD75N4

22

0.15

230

–

400

1

VW3 A4 557

45.000

ATV 61HD90N4D

35

0.155

184

370

220

1

VW3 A4 558

31.000

ATV 61HC11N4D

35

0.12

222

445

230

1

VW3 A4 559

35.000

ATV 61HC13N4D

35

0.098

264

530

245

1

VW3 A4 560

43.000

ATV 61HC16N4D

50

0.085

300

570

268

1

VW3 A4 568

46.000

50

0.066

344

685

258

1

VW3 A4 561

47.000

50

0.060

450

849

300

1

VW3 A4 569

70.000

ATV 61HC25N4D

50

0.060

450

849

300

1

VW3 A4 569

70.000

ATV 61HC31N4D

50

0.038

613

1150

307

1

VW3 A4 564

73.000

ATV 61HC40N4D

50

0.032

720

1352

428

1

VW3 A4 565

82.000

ATV 61HC50N4D

50

0.060

450

849

300

2

VW3 A4 569

70.000

ATV 61HC63N4D

50

0.038

613

1150

307

2

VW3 A4 564

73.000

Characteristics: page 67

Dimensions: page 103

ATV 61HC22N4D

Presentation: page 66

Motor P 200 kW Motor P 220 kW

Schemes: pages 114 to 118