Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 13 of 30

Variable speed drives Altivar 61 Catalogue: Passive filters

Pages 71 to 75 of 211, from Variable speed drives Altivar 61 Catalogue

The original document is the PDF (4.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Telemecanique Altivar 61 ATV61, Schneider Altivar 61 ATV61 and Square D Altivar 61 ATV61

Page 71

Presentation, characteristics

0

Variable speed drives for asynchronous motors

0

Altivar 61: Reduction of current harmonics Option: Passive filters

Passive filters L1 Altivar 61

L2 L3

The passive filter is used to reduce current harmonics with total harmonic distortion factors of less than 16% or 10%. These ratios may be less than 10% or 5% if the filter is used with a DC choke, see pages 62 and 70 to 73. For applications requiring stricter control of current harmonics, the filter can be controlled via the drive on the basis of the load, see page 122. Applications Reduction of current harmonics in order to use drives in the first environment.

Passive filter

General characteristics Degree of protection Maximum relative humidity Ambient air temperature around the device

IP 20

Operation

°C

Storage

°C

Maximum operating altitude m

Class F humidity without condensation 5%…85% 5…+ 40 without derating Up to 55°C with current derating of 3% per additional °C - 25…+ 55 1000 without derating 1000…4000 with current derating of 5% per additional 1000 m

Electrical characteristics Range Nominal voltage ± 10%

400 V 380…415 a

460 V 440…480 a

Operating frequency

50 ± 5 %

60 ± 5 %

Overload capacity

1.5 x Irms (A)

Efficiency

98 % (2% of thermal losses)

V

THDI (1)

%

Cos ϕ

≤ 16 At 75% of the line current: 0.85 At 100% of the line current: 0.99 At 150% of the line current: 1

Connection characteristics Maximum connection capacity VW3 A4 601…604 16 mm2 VW3 A4 605…609 50 mm2 VW3 A4 610, 611, 614 Connected on a bar, Ø 12.5 Connected on a bar, Ø 16.5 VW3 A4 612, 613, 615…617 Connected on a bar, Ø 16.5 VW3 A4 618 VW3 A4 621, 622 16 mm2 VW3 A4 623…627 50 mm2 VW3 A4 628, 629 Connected on a bar, Ø 12.5 Connected on a bar, Ø 16.5 VW3 A4 630…637 Connected on a bar, Ø 16.5 VW3 A4 638 16 mm2 VW3 A4 641…644 VW3 A4 645…648 50 mm2 VW3 A4 649 Connected on a bar, Ø 12.5 Connected on a bar, Ø 16.5 VW3 A4 650…655 Connected on a bar, Ø 16.5 VW3 A4 656 16 mm2 VW3 A4 661…663 VW3 A4 664…666 50 mm2 VW3 A4 667, 668 Connected on a bar, Ø 12.5 Connected on a bar, Ø 16.5 VW3 A4 669…675 Connected on a bar, Ø 16.5 VW3 A4 676 (1) The total current harmonic distortion (THDI) is indicated for a total voltage harmonic distortion (THDU) < 2% and a short-circuit ratio (RSCE) > 66%, and only for the nominal current of the passive filter. If these conditions are not adhered to, the total current harmonics will be reduced without any guarantee of level.

References: pages 70 to 73

Dimensions: pages 104 and 105

Schemes: page 122

69 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 72

References

0

Variable speed drives for asynchronous motors

0

Altivar 61: Reduction of current harmonics Option: Passive filters

Passive filters: 3-phase power supply 400 V 50 Hz Motor rating kW

For drives

HP

Line supply Filter Line current In (2) A

A

Number required per drive

Reference

Weight kg

THDI 16% (1) 0.75 1 ATV 61H075N4 3.30 6 1 VW3 A4 601 15.000 1.5 2 ATV 61HU15N4 4.00 6 1 VW3 A4 601 15.000 2.2 3 ATV 61HU22N4 5.00 6 1 VW3 A4 601 15.000 3 – ATV 61HU30N4 6.00 6 1 VW3 A4 601 15.000 4 5 ATV 61HU40N4 7.80 10 1 VW3 A4 602 19.000 5.5 7.5 ATV 61HU55N4 10.00 10 1 VW3 A4 602 19.000 7.5 10 ATV 61HU75N4 14.00 19 1 VW3 A4 603 21.000 11 15 ATV 61HD11N4 19.00 19 1 VW3 A4 603 21.000 15 20 ATV 61HD15N4 26.00 26 1 VW3 A4 604 22.000 18.5 25 ATV 61HD18N4 32.00 35 1 VW3 A4 605 34.000 22 30 ATV 61HD22N4 38.00 43 1 VW3 A4 606 38.000 30 40 ATV 61HD30N4 52.00 72 1 VW3 A4 607 56.000 37 50 ATV 61HD37N4 63.00 72 1 VW3 A4 607 56.000 45 60 ATV 61HD45N4 77.00 101 1 VW3 A4 608 69.000 55 75 ATV 61HD55N4 91.00 101 1 VW3 A4 608 69.000 75 100 ATV 61HD75N4 126.00 144 1 VW3 A4 609 97.000 90 125 ATV 61HD90N4 156.00 144 1 VW3 A4 609 97.000 110 150 ATV 61HC11N4 187.00 180 1 VW3 A4 610 103.000 132 200 ATV 61HC13N4 234.00 216 1 VW3 A4 611 112.000 160 250 ATV 61HC16N4 287.00 289 1 VW3 A4 612 135.000 200 300 ATV 61HC22N4 353.50 370 1 VW3 A4 613 155.000 220 350 ATV 61HC22N4 390.00 370 1 VW3 A4 613 155.000 250 400 ATV 61HC25N4 445.00 216 2 VW3 A4 611 112.000 280 450 ATV 61HC31N4 485.00 289 2 VW3 A4 612 135.000 315 500 ATV 61HC31N4 543.00 289 2 VW3 A4 612 135.000 355 – ATV 61HC40N4 592.00 289 2 VW3 A4 612 135.000 400 600 ATV 61HC40N4 670.00 325 2 VW3 A4 619 155.000 500 700 ATV 61HC50N4 840.00 289 3 VW3 A4 612 135.000 560 800 ATV 61HC63N4 978.00 370 3 VW3 A4 613 155.000 630 900 ATV 61HC63N4 1091.00 370 3 VW3 A4 613 155.000 (1) If a DC choke (see page 62) is used with VW3 A4 601 to VW3 A4 613 and VW3 A4 619 passive filters, the THD will be ≤ 10%. These reduced current harmonics are obtained on condition that the THDU is < 2% and the RSCE is > 66% and only for the nominal current of the passive filter. (2) In: Nominal filter current.

Presentation: page 69

Characteristics: page 69

Dimensions: pages 104 and 105

Schemes: page 122

70 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 73

References (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61: Reduction of current harmonics Option: Passive filters

Passive filters: 3-phase power supply 400 V 50 Hz (continued) Motor rating kW

For drives

HP

Line supply Filter Line current In (2) A

A

Number required per drive

Reference

Weight kg

THDI 10% (1) 0.75 1 ATV 61H075N4 3.30 6 1 VW3 A4 621 21.000 1.5 2 ATV 61HU15N4 4.00 6 1 VW3 A4 621 21.000 2.2 3 ATV 61HU22N4 5.00 6 1 VW3 A4 621 21.000 3 – ATV 61HU30N4 6.00 6 1 VW3 A4 621 21.000 4 5 ATV 61HU40N4 7.80 10 1 VW3 A4 622 27.000 5.5 7.5 ATV 61HU55N4 10.00 10 1 VW3 A4 622 27.000 7.5 10 ATV 61HU75N4 14.00 19 1 VW3 A4 623 28.000 11 15 ATV 61HD11N4 19.00 19 1 VW3 A4 623 28.000 15 20 ATV 61HD15N4 26.00 26 1 VW3 A4 624 40.000 18.5 25 ATV 61HD18N4 32.00 35 1 VW3 A4 625 49.000 22 30 ATV 61HD22N4 38.00 43 1 VW3 A4 626 52.000 30 40 ATV 61HD30N4 52.00 72 1 VW3 A4 627 88.000 37 50 ATV 61HD37N4 63.00 72 1 VW3 A4 627 88.000 45 60 ATV 61HD45N4 77.00 101 1 VW3 A4 628 150.000 55 75 ATV 61HD55N4 91.00 101 1 VW3 A4 628 150.000 75 100 ATV 61HD75N4 126.00 144 1 VW3 A4 629 167.000 90 125 ATV 61HD90N4 156.00 144 1 VW3 A4 629 167.000 110 150 ATV 61HC11N4 187.00 180 1 VW3 A4 630 178.000 132 200 ATV 61HC13N4 234.00 216 1 VW3 A4 631 224.000 160 250 ATV 61HC16N4 287.00 289 1 VW3 A4 632 271.000 200 300 ATV 61HC22N4 353.50 370 1 VW3 A4 633 320.000 220 350 ATV 61HC22N4 390.00 370 1 VW3 A4 633 320.000 250 400 ATV 61HC25N4 445.00 216 2 VW3 A4 631 224.000 280 450 ATV 61HC31N4 485.00 289 2 VW3 A4 632 271.000 315 500 ATV 61HC31N4 543.00 289 2 VW3 A4 632 271.000 355 – ATV 61HC40N4 592.00 289 2 VW3 A4 632 271.000 400 600 ATV 61HC40N4 670.00 325 2 VW3 A4 639 284.000 500 700 ATV 61HC50N4 840.00 289 3 VW3 A4 632 271.000 560 800 ATV 61HC63N4 918.00 370 3 VW3 A4 633 320.000 630 900 ATV 61HC63N4 1091.00 370 3 VW3 A4 633 320.000 (1) If a DC choke (see page 62) is used with VW3 A4 621 to VW3 A4 633 and VW3 A4 639 passive filters, the THD will be ≤ 5%. These reduced current harmonics are obtained on condition that the THDU is < 2% and the RSCE is > 66% and only for the nominal current of the passive filter. (2) In: Nominal filter current.

Presentation: page 69

Characteristics: page 69

Dimensions: pages 104 and 105

Schemes: page 122

71 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 74

References (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61: Reduction of current harmonics Option: Passive filters

Passive filters: 3-phase power supply 460 V 60 Hz Motor rating kW

For drives

HP

Line supply Filter Line current In (2) A

A

Number required per drive

Reference

Weight kg

THDI 16% (1) 0.75 1 ATV 61H075N4 2.50 6 1 VW3 A4 641 15.000 1.5 2 ATV 61HU15N4 3.00 6 1 VW3 A4 641 15.000 2.2 3 ATV 61HU22N4 4.20 6 1 VW3 A4 641 15.000 3 – ATV 61HU30N4 6.00 6 1 VW3 A4 641 15.000 4 5 ATV 61HU40N4 7.00 10 1 VW3 A4 642 19.000 5.5 7.5 ATV 61HU55N4 10.00 10 1 VW3 A4 642 19.000 7.5 10 ATV 61HU75N4 13.00 19 1 VW3 A4 643 23.000 11 15 ATV 61HD11N4 19.00 19 1 VW3 A4 643 23.000 15 20 ATV 61HD15N4 24.00 26 1 VW3 A4 644 34.000 18.5 25 ATV 61HD18N4 32.00 35 1 VW3 A4 645 42.000 22 30 ATV 61HD22N4 35.00 35 1 VW3 A4 645 42.000 30 40 ATV 61HD30N4 46.40 43 1 VW3 A4 646 45.000 37 50 ATV 61HD37N4 58.70 72 1 VW3 A4 647 61.000 45 60 ATV 61HD45N4 67.90 72 1 VW3 A4 647 61.000 55 75 ATV 61HD55N4 82.60 101 1 VW3 A4 648 75.000 75 100 ATV 61HD75N4 108.00 101 1 VW3 A4 648 75.000 90 125 ATV 61HD90N4 134.00 180 1 VW3 A4 649 107.000 110 150 ATV 61HC11N4 163.00 180 1 VW3 A4 649 107.000 132 200 ATV 61HC13N4 234.00 217 1 VW3 A4 656 119.000 160 250 ATV 61HC16N4 287.00 289 1 VW3 A4 650 145.000 200 300 ATV 61HC22N4 353.00 370 1 VW3 A4 651 185.000 220 350 ATV 61HC22N4 390.00 370 1 VW3 A4 651 185.000 250 400 ATV 61HC25N4 444.00 217 2 VW3 A4 656 119.000 280 450 ATV 61HC31N4 485.00 289 2 VW3 A4 650 145.000 315 500 ATV 61HC31N4 543.00 289 2 VW3 A4 650 145.000 355 – ATV 61HC40N4 592.00 289 2 VW3 A4 650 145.000 400 600 ATV 61HC40N4 670.00 325 2 VW3 A4 657 165.000 500 700 ATV 61HC50N4 760.00 370 2 VW3 A4 651 185.000 560 800 ATV 61HC63N4 858.00 325 3 VW3 A4 657 165.000 630 900 ATV 61HC63N4 964.00 325 3 VW3 A4 657 165.000 (1) If a DC choke (see page 62) is used with VW3 A4 641 to VW3 A4 651, VW3 A4 656 and VW3 A4 657 passive filters, the THD will be ≤ 10%. These reduced current harmonics are obtained on condition that the THDU is < 2% and the RSCE is > 66% and only for the nominal current of the passive filter. (2) In: Nominal filter current.

Presentation: page 69

Characteristics: page 69

Dimensions: pages 104 and 105

Schemes: page 122

72 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 75

References (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61: Reduction of current harmonics Option: Passive filters

Passive filters: 3-phase power supply 460 V 60 Hz Motor rating kW

For drives

HP

Line supply Filter Line current In (2) A

A

Number required per drive

Reference

Weight kg

THDI 10% (1) 0.75 1 ATV 61H075N4 2.50 6 1 VW3 A4 661 21.000 1.5 2 ATV 61HU15N4 3.00 6 1 VW3 A4 661 21.000 2.2 3 ATV 61HU22N4 4.20 6 1 VW3 A4 661 21.000 3 – ATV 61HU30N4 6.00 6 1 VW3 A4 661 21.000 4 5 ATV 61HU40N4 7.00 10 1 VW3 A4 662 27.000 5.5 7.5 ATV 61HU55N4 10.00 10 1 VW3 A4 662 27.000 7.5 10 ATV 61HU75N4 13.00 19 1 VW3 A4 663 28.000 11 15 ATV 61HD11N4 19.00 19 1 VW3 A4 663 28.000 15 20 ATV 61HD15N4 24.00 26 1 VW3 A4 664 41.000 18.5 25 ATV 61HD18N4 32.00 35 1 VW3 A4 665 49.000 22 30 ATV 61HD22N4 35.00 35 1 VW3 A4 665 49.000 30 40 ATV 61HD30N4 46.40 43 1 VW3 A4 666 56.000 37 50 ATV 61HD37N4 58.70 72 1 VW3 A4 667 80.000 45 60 ATV 61HD45N4 68.00 72 1 VW3 A4 667 80.000 55 75 ATV 61HD55N4 82.60 101 1 VW3 A4 668 98.000 75 100 ATV 61HD75N4 108.00 101 1 VW3 A4 668 98.000 90 125 ATV 61HD90N4 134.00 180 1 VW3 A4 669 151.000 110 150 ATV 61HC11N4 163.00 180 1 VW3 A4 669 151.000 132 200 ATV 61HC13N4 234.00 217 1 VW3 A4 676 171.000 160 250 ATV 61HC16N4 287.00 289 1 VW3 A4 670 215.000 200 300 ATV 61HC22N4 353.50 370 1 VW3 A4 671 250.000 220 350 ATV 61HC22N4 390.00 370 1 VW3 A4 671 250.000 250 400 ATV 61HC25N4 444.00 217 2 VW3 A4 676 171.000 280 450 ATV 61HC31N4 485.00 289 2 VW3 A4 670 240.000 315 500 ATV 61HC31N4 543.00 289 2 VW3 A4 670 240.000 355 – ATV 61HC40N4 592.00 289 2 VW3 A4 670 240.000 400 600 ATV 61HC40N4 670.00 325 2 VW3 A4 677 215.000 500 700 ATV 61HC50N4 760.00 370 2 VW3 A4 671 250.000 560 800 ATV 61HC63N4 858.00 325 3 VW3 A4 677 240.000 630 900 ATV 61HC63N4 964.00 325 3 VW3 A4 677 240.000 (1) If a DC choke (see page 62) is used with VW3 A4 661 to VW3 A4 671, VW3 A4 676 and VW3 A4 677 passive filters, the THD will be ≤ 5%. These reduced current harmonics are obtained on condition that the THDU is < 2% and the RSCE is > 66% and only for the nominal current of the passive filter. (2) In: Nominal filter current.

Presentation: page 69

Characteristics: page 69

Dimensions: pages 104 and 105

Schemes: page 122

73 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com