The text of a manual · part 14 of 30
Variable speed drives Altivar 61 Catalogue: additional EMC input filters
Pages 76 to 79 of 211, from Variable speed drives Altivar 61 Catalogue
The original document is the PDF (4.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Telemecanique Altivar 61 ATV61, Schneider Altivar 61 ATV61 and Square D Altivar 61 ATV61
Page 76
Presentation
0
Variable speed drives for asynchronous motors
0
Altivar 61 Option: additional EMC input filters
Integrated filters
L1 M1 3
L2
The Altivar 61 drive, except for the ATV 61HpppM3X, has built-in radio interference input filters to meet the EMC standard for variable speed electrical power drive “products” IEC/EN 61800-3, edition 2, category C2 or C3 in environment 1 or 2 and to comply with the European directive on EMC (electromagnetic compatibility).
L3
ATV 61HpppM3 ATV 61ppppN4 ATV 61WpppN4C with integrated filter
Drives
ATV 61H075M3…HU22M3 ATV 61HU30M3…HU75M3 ATV 61H075N4…HU40N4 ATV 61HU55N4…HD15N4 ATV 61HD18N4…HC63N4 ATV 61WpppN4 ATV 61WpppN4C
Maximum length of shielded cable according to EN 55011, class A (1) Group 1 (2) Group 2 (2) LF (3) HF (3) LF (3) HF (3) m m m m 10 5 – – – – 10 5 10 5 – – – – 10 5 – – 50 25 80 50 – – 80 50 20 5
Additional EMC input filters L1 L2
Additional EMC filter
L3
Altivar 61
M1 3
Applications Additional EMC input filters can be used to meet more stringent requirements and are designed to cut down conducted emissions on the line supply below the limits of standard EN 55011 group 1, class A or B (2). For the ATV 61HpppM3, ATV 61HD11M3X…HD45M3X and ATV 61H075N4…HD75N4 drives, the additional EMC filters can be mounted next to or under the device. They act as a support for the drives and are attached to them via tapped holes. For the ATV61HD90N4…HC63N4 drives, the additional EMC filters are only mounted at the side of the drives. Use according to the type of network Use of these additional filters is only possible on TN (neutral connection) and TT (neutral to earth) type networks. Standard IEC/EN 61800-3, appendix D2.1, states that on IT networks (impedance or isolated neutral), filters can cause permanent insulation monitors to operate in a random manner. In addition, the effectiveness of additional filters on this type of network depends on the type of impedance between neutral and earth, and therefore cannot be predicted. In the case of a machine which needs to be installed on an IT network, one solution consists of inserting an isolation transformer and placing the machine locally on a TN or TT network. (1) Maximum lengths for shielded cables connecting motors to drives, for a factory-set switching frequency of 2.5 or 4 kHz, depending on the rating (see page 10). If motors are connected in parallel, it is the total length that should be taken into account. (2) See page 8. (3) LF: low switching frequency. HF: high switching frequency. These frequencies depend on the drive rating. Drives Switching frequency LF HF kHz kHz ATV 61HpppM3 4 4.1…16 ATV 61H075N4…HD30N4 ATV 61HD37N4…HD75N4 2…2.5 2.6…12 ATV 61HD90N4…HC63N4 2…4 4.1…8 ATV 61W075N4…WD45N4 8 8.1…16 ATV 61W075N4C…WD45N4C 8 8.1…16 ATV 61WD55N4…WD90N4 4 4.1…16 ATV 61WD55N4C…WD90N4C 4 4.1…16
Characteristics: Page 75
References: Pages 76 and 77
Dimensions: Pages 106 and 107
Schemes: Page 122
74 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 77
Characteristics
0
Variable speed drives for asynchronous motors
0
Altivar 61 Option: additional EMC input filters
General characteristics Type of EMC filter Conformity to standards
VW3 A4 401…409 EN 133200
Degree of protection
IP 20 and IP 41 on upper part
IP 00 IP 30 with VW3 A9 601, 602 kits 93% without condensation or dripping water conforming to IEC 68-2-3
Maximum relative humidity Ambient temperature around the unit
Operation Storage
°C °C m
50/60 Hz three phase
V
Maximum operating altitude
Vibration resistance Shock resistance Maximum nominal voltage
VW3 A4 410…413
- 10…+ 50 - 25…+ 45 - 40…+ 65 - 25…+ 85 1000 without derating 1000…3000 derating the current by 1% per additional 100 m. Limited to 2000 m for the “Corner Grounded” distribution network 1.5 mm peak to peak from 3…13 Hz, 1 gn peak from 13…150 Hz, in accordance with IEC 60068-2-6 15 gn for 11 ms in accordance with IEC/EN 60068-2-27 240 + 10 % 480 + 10 %
Connection characteristics Maximum connection capacity VW3 A4 401 and tightening torque VW3 A4 402 VW3 A4 403 VW3 A4 404 VW3 A4 405…407 VW3 A4 408 VW3 A4 409 VW3 A4 410…412 VW3 A4 413
Presentation: Page 74
References: Pages 76 and 77
4 mm2 (AWG 10). 0.6 Nm 6 mm2 (AWG 8). 1.5 Nm 10 mm2 (AWG 6). 1.5 Nm 16 mm2 (AWG 4). 2 Nm 50 mm2 (AWG 0). 6 Nm 150 mm2 (300 kcmil). 25 Nm 25 mm2 (AWG 2). 4 Nm Bar connection, M10 – Bar connection, 2 x M12 –
Dimensions: Pages 106 and 107
Schemes: Page 122
75 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 78
References
0
Variable speed drives for asynchronous motors
0
Altivar 61 Option: additional EMC input filters
Additional EMC input filters Drives
Maximum length of shielded cable (1) EN 55011 (5) EN 55011 (5) class A Gr1 class B Gr1 LF (6) HF (6) LF (6) HF (6) m m m m
In (2)
Il (3)
Loss (4)
A mA
W
Reference
Weight kg
Three phase supply voltage: 200…240 V 50/60 Hz ATV 61H075M3, HU15M3
100
50
50
20
12
4
10
VW3 A4 401
2.200
ATV 61HU22M3…HU40M3
100
50
50
20
26
4.4
18
VW3 A4 402
4.000
ATV 61HU55M3
100
50
50
20
35
3
24
VW3 A4 403
5.800
ATV 61HU75M3
100
50
50
20
46
10
19
VW3 A4 404
7.000
ATV 61HD11M3X, HD15M3X
200
100
50
25
72
33
34
VW3 A4 405
12.000
ATV 61HD18M3X, HD22M3X
200
100
50
25
90
33
34
VW3 A4 406
15.000
ATV 61HD30M3X...HD45M3X
200
100
50
25
180
80
58
VW3 A4 408
40.000
ATV 61HD55M3X, HD75M3X
100
50
50
25
273
285
60
VW3 A4 410
22.000
ATV 61HD90M3X
100
50
50
25
336
500
125
VW3 A4 411
22.000
Three phase supply voltage: 380…480 V 50/60 Hz ATV 61H075N4…HU22N4
100
50
50
20
12
7
5
VW3 A4 401
2.200
ATV 61HU30N4, HU40N4
100
50
50
20
26
8
6
VW3 A4 402
4.000
ATV 61HU55N4, HU75N4
100
50
50
20
35
7
14
VW3 A4 403
5.800
ATV 61HD11N4
100
50
50
20
46
14
13
VW3 A4 404
7.000
ATV 61HD15N4 (7), HD18N4
300
200
100
100
72
60
14
VW3 A4 405
12.000
ATV 61HD22N4
300
200
100
100
90
60
11
VW3 A4 406
15.000
ATV 61HD30N4, HD37N4
300
200
100
100
92
60
30
VW3 A4 407
17.000
ATV 61HD45N4…HD75N4
300
200
100
100
180
140
58
VW3 A4 408
40.000
ATV 61HD90N4…HC16N4
300
150
50
25
273
500
60
VW3 A4 410
22.000
ATV 61HC22N4…HC31N4
300
150
50
25
546
500
125
VW3 A4 411
25.000
ATV 61HC40N4, HC50N4
300
150
50
25
728
500
210
VW3 A4 412
25.000
ATV 61HC63N4
300
150
50
25
1456
200
380
VW3 A4 413
34.000
(1) The filter selection tables give the maximum lengths for shielded cables connecting motors to drives for a switching frequency of 1 to 16 kHz (see page 10). These limits are given as examples only as they vary depending on the stray capacitance of the motors and the cables used. If motors are connected in parallel, it is the total length that should be taken into account. (2) Filter nominal current. (3) Maximum earth leakage current at 230 V and at 400 V 50 Hz on a TT network. (4) Via thermal dissipation. (5) See page 8. (6) LF: low switching frequency. HF: high switching frequency. These frequencies depend on the drive rating: For drives Switching frequency LF HF kHz kHz ATV 61HpppM3 4 4.1…16 ATV 61H075N4…HD11N4 ATV 61HD11M3X, HD15M3X 3.5...4 4.1…12 ATV 61HD15N4…HD30N4 ATV 61HD18M3X...HD45M3X 2…2.5 2.6…12 ATV 61HD37N4...HD75N4 ATV 61HD55M3X...HD90M3X 2.5…4 4.1…8 ATV 61HD90N4...HC63N4 2…4 4.1…8 (7) It is possible to use a special filter VW3 A4 409 with a leakage current Il (3) of 14 mA, which enables a maximum motor cable length of 100 m.
Presentation: Page 74
Characteristics: Page 75
Dimensions: Pages 106 and 107
Schemes: Page 122
76 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 79
References (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61 Option: additional EMC input filters
IP 30 protection kits Description
Presentation: Page 74
Mechanical device consisting VW3 A4 410, 411 of an IP 30 cover and cable clips
VW3 A9 601
Weight kg –
VW3 A4 412, 413
VW3 A9 602
–
Characteristics: Page 75
For filters
Dimensions: Page 107
Reference
Schemes: Page 122
77 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com