Presentation

0

Variable speed drives for asynchronous motors

0

Altivar 61: Output filters

The Altivar 61 drive includes as standard a software function used to limit overvoltages at the motor terminals. Depending on the cable lengths or the type of application, it may be necessary to use output filters: b Motor chokes used to limit the dv/dt b Sinus filters that are particularly effective for long cable runs Cable length (2)

10…50 m

50…100 m

100…150 m

150…300 m

300…600 m

600…1000 m

Shielded cable ATV 61HpppM3 ATV 61H075N4…HD15N4 ATV 61HpppM3X ATV 61HD18N4…HC63N4

Software function Motor choke (1) Software function (1)

– Motor choke

–

Unshielded cable ATV 61H075M3, HU15M3 ATV 61H075N4...HU22N4 ATV 61HU22M3...HU30M3 ATV 61HU30N4…HU55N4 ATV 61HU40M3…HU75M3 ATV 61HU75N4…HD15N4 ATV 61HD11M3X…HU45M3X ATV 61HU18N4…HD75N4 ATV 61HD55M3X…HD90M3X ATV 61HD90N4…HC63N4

Software function (1)

–

Software function (1)

Motor choke or sinus filter Motor choke

Software function (1)

Motor choke

Sinus filter

Sinus filter

Software function (1)

Motor choke

Sinus filter

Software function (1)

Motor choke

2 motor chokes connected in series

–

–

(1) The software function limits the overvoltage at the motor terminals to twice the DC bus voltage. For any application with braking cycles, the DC bus voltage rises to more than the supply voltage multiplied by 2. You must check the electrical characteristics of the motor before using this function. (2) For an application with several motors connected in parallel, the cable length must include all tap-offs. Recommended cable types: b Shielded cables: “GORSE” cable, type GUOSTV-LS/LH; “PROTOFLEX” cable, type EMV2YSL CY, b Unshielded cables: “GORSE” cable, type H07 RN-F4GXX; “BELDEN” cable, type 2950X

Schemes: page 122

78 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 81

Presentation, characteristics

0

Variable speed drives for asynchronous motors

0

Altivar 61: Output filters Option: Motor chokes

Motor chokes Altivar 61 drives have been designed for operation with the following maximum motor cable lengths: For drives M1 3

Altivar 61

Motor choke

ATV 61HpppM3 ATV 61HD11M3X, HD15M3X ATV 61H075N4…HD18N4 ATV 61HD18M3X…HD90M3X ATV 61HD22N4…HC63N4

Maximum length of motor cable (1) Shielded cable Unshielded cable m m u 50 u 100 u 100 u 200

The motor choke enables operation beyond these motor cable length limits and/or can limit the dv/dt to 500 V/µs at the motor terminals. It also enables: b Overvoltages on the motor terminals to be limited as follows: v 1000 V to 400 V a (rms value) v 1150 V to 460 V a (rms value) b Interference caused by opening a contactor placed between the filter and the motor to be filtered b The motor earth leakage current to be reduced

General characteristics (2) Type of choke Maximum drive switching frequency

ATV 61HpppM3 ATV 61HD11M3X, HD15M3X ATV 61H075N4…HD30N4 ATV 61HD18M3X…HD90M3X ATV 61HD37N4…HC63N4 Maximum drive output frequency Degree of protection

Thermal protection Temperature controlled switch (3) Ambient air temperature around the device

Tripping temperature Maximum voltage Maximum current Operation Storage kHz

VW3 A5 101…103 4 kHz

2.5

Hz

100 IP 00

°C V A °C °C

By temperature controlled switch 125 250 a 0.5 - 10…+ 50 - 25…+ 70

VW3 A5 104…108

IP 00 IP 20 with kits VW3 A9 612 and VW3 A9 613 – – – –

Connection characteristics 10 mm2 (AWG 6) 1.5 Nm Connected on a bar, Ø 11 mm – VW3 A5 104 Connected on a tag connector, M10 – VW3 A5 105, 106 Connected on a tag connector, M12 – VW3 A5 107, 108 Connected on a tag connector, 2 x M12 – (1) These values are given for a maximum switching frequency of 2.5 or 4 kHz depending on the rating. (2) Choke performance is ensured by not exceeding the cable lengths between the motor and the drive given in the table above. For an application with several motors connected in parallel, the cable length must include all tap-offs. If a cable longer than that recommended is used, the motor chokes may overheat. (3) The contact should be connected in sequence (used for signalling or controlling the line contactor). Maximum connection capacity VW3 A5 101, 102 and tightening torque VW3 A5 103

References: page 80

Dimensions: pages 108 to 110

Schemes: page 122

79 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 82

References

0

Variable speed drives for asynchronous motors

0

Altivar 61: Output filters Option: Motor chokes

Motor chokes For drives

Maximum length Loss of motor cable (1) Shielded Unshielded m m W

Nominal Sold current in lots of

Unit reference

A

Weight kg

3-phase supply voltage: 200…240 V 50/60 Hz

VW3 A5 101

ATV 61H075M3…HU22M3

150

300

150

12

–

VW3 A5 101

5.500

ATV 61HU30M3…HU75M3

200

260

250

48

–

VW3 A5 102

8.000

300

300

350

90

–

VW3 A5 103

10.000

ATV 61HD11M3X…HD22M3X

150

300

350

90

–

VW3 A5 103

10.000

ATV 61HD30M3X…HD45M3X

150

300

430

215

3

VW3 A5 104

17.300

ATV 61HD55M3X, HD75M3X

150

300

475

314

3

VW3 A5 105

29.600

ATV 61HD90M3X

250

300

530

481

3

VW3 A5 106

44.400

75

90

150

12

–

VW3 A5 101

5.500

85

95

250

48

–

VW3 A5 102

8.000

160

200

350

90

–

VW3 A5 103

10.000

85

95

250

48

–

VW3 A5 102

8.000

160

200

350

90

–

VW3 A5 103

10.000

200

300

430

215

3

VW3 A5 104

17.300

140

170

350

90

–

VW3 A5 103

10.000

150

300

430

215

3

VW3 A5 104

17.300

97

166

350

90

–

VW3 A5 103

10.000

200

300

430

215

3

VW3 A5 104

17.300

ATV 61HD45N4…HD75N4

150

300

430

215

3

VW3 A5 104

17.300

ATV 61HD90N4

200

300

430

215

3

VW3 A5 104

17.300

ATV 61HC11N4, HC13N4

150

250

475

314

3

VW3 A5 105

29.600

ATV 61HC16N4

250

300

530

481

3

VW3 A5 106

44.400

ATV 61HC22N4

250

300

530

481

3

VW3 A5 106

44.400

ATV 61HC25N4

200

250

598

759

3

VW3 A5 107

64.500

ATV 61HC31N4

200

250

598

759

3

VW3 A5 107

64.500

200

250

598

759

3

VW3 A5 107

64.500

250

300

682

1188

3

VW3 A5 108

99.200

ATV 61HC50N4

250

300

682

1188

3

VW3 A5 108

99.200

ATV 61HC63N4

250

300

682

1188

3

VW3 A5 108

99.200

3-phase supply voltage: 380…480 V 50/60 Hz ATV 61H075N4…HU40N4

ATV 61HU55N4…HD18N4

ATV 61HD22N4…HD30N4

ATV 61HD37N4

ATV 61HC40N4

Motor P 355 kW Motor P 400 kW

(1) Maximum length given for a switching frequency of 2.5 or 4 kHz depending on the rating of the fan, see Characteristics on page 79.

Presentation: pages 78 and 79

Characteristics: page 79

Dimensions: pages 108 to 110

Schemes: page 122

80 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Page 83

References (continued)

0

Variable speed drives for asynchronous motors

0

Altivar 61: Output filters Option: Motor chokes

IP 20 protection kits Description

For filters

Reference

Mechanical device consisting VW3 A5 104, 105 of an IP 20 cover and cable clips VW3 A5 106…108

Presentation: pages 78 and 79

Characteristics: page 79

Dimensions: page 110

VW3 A9 612

Weight kg –

VW3 A9 613

–

Schemes: page 122

81 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com