The text of a manual · part 15 of 30
Variable speed drives Altivar 61 Catalogue, pages 80 to 83
Pages 80 to 83 of 211: Output filters; Motor chokes
The original document is the PDF (4.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Telemecanique Altivar 61 ATV61, Schneider Altivar 61 ATV61 and Square D Altivar 61 ATV61
Page 80
Presentation
0
Variable speed drives for asynchronous motors
0
Altivar 61: Output filters
The Altivar 61 drive includes as standard a software function used to limit overvoltages at the motor terminals. Depending on the cable lengths or the type of application, it may be necessary to use output filters: b Motor chokes used to limit the dv/dt b Sinus filters that are particularly effective for long cable runs Cable length (2)
10…50 m
50…100 m
100…150 m
150…300 m
300…600 m
600…1000 m
Shielded cable ATV 61HpppM3 ATV 61H075N4…HD15N4 ATV 61HpppM3X ATV 61HD18N4…HC63N4
Software function Motor choke (1) Software function (1)
– Motor choke
–
Unshielded cable ATV 61H075M3, HU15M3 ATV 61H075N4...HU22N4 ATV 61HU22M3...HU30M3 ATV 61HU30N4…HU55N4 ATV 61HU40M3…HU75M3 ATV 61HU75N4…HD15N4 ATV 61HD11M3X…HU45M3X ATV 61HU18N4…HD75N4 ATV 61HD55M3X…HD90M3X ATV 61HD90N4…HC63N4
Software function (1)
–
Software function (1)
Motor choke or sinus filter Motor choke
Software function (1)
Motor choke
Sinus filter
Sinus filter
Software function (1)
Motor choke
Sinus filter
Software function (1)
Motor choke
2 motor chokes connected in series
–
–
(1) The software function limits the overvoltage at the motor terminals to twice the DC bus voltage. For any application with braking cycles, the DC bus voltage rises to more than the supply voltage multiplied by 2. You must check the electrical characteristics of the motor before using this function. (2) For an application with several motors connected in parallel, the cable length must include all tap-offs. Recommended cable types: b Shielded cables: “GORSE” cable, type GUOSTV-LS/LH; “PROTOFLEX” cable, type EMV2YSL CY, b Unshielded cables: “GORSE” cable, type H07 RN-F4GXX; “BELDEN” cable, type 2950X
Schemes: page 122
78 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 81
Presentation, characteristics
0
Variable speed drives for asynchronous motors
0
Altivar 61: Output filters Option: Motor chokes
Motor chokes Altivar 61 drives have been designed for operation with the following maximum motor cable lengths: For drives M1 3
Altivar 61
Motor choke
ATV 61HpppM3 ATV 61HD11M3X, HD15M3X ATV 61H075N4…HD18N4 ATV 61HD18M3X…HD90M3X ATV 61HD22N4…HC63N4
Maximum length of motor cable (1) Shielded cable Unshielded cable m m u 50 u 100 u 100 u 200
The motor choke enables operation beyond these motor cable length limits and/or can limit the dv/dt to 500 V/µs at the motor terminals. It also enables: b Overvoltages on the motor terminals to be limited as follows: v 1000 V to 400 V a (rms value) v 1150 V to 460 V a (rms value) b Interference caused by opening a contactor placed between the filter and the motor to be filtered b The motor earth leakage current to be reduced
General characteristics (2) Type of choke Maximum drive switching frequency
ATV 61HpppM3 ATV 61HD11M3X, HD15M3X ATV 61H075N4…HD30N4 ATV 61HD18M3X…HD90M3X ATV 61HD37N4…HC63N4 Maximum drive output frequency Degree of protection
Thermal protection Temperature controlled switch (3) Ambient air temperature around the device
Tripping temperature Maximum voltage Maximum current Operation Storage kHz
VW3 A5 101…103 4 kHz
2.5
Hz
100 IP 00
°C V A °C °C
By temperature controlled switch 125 250 a 0.5 - 10…+ 50 - 25…+ 70
VW3 A5 104…108
IP 00 IP 20 with kits VW3 A9 612 and VW3 A9 613 – – – –
Connection characteristics 10 mm2 (AWG 6) 1.5 Nm Connected on a bar, Ø 11 mm – VW3 A5 104 Connected on a tag connector, M10 – VW3 A5 105, 106 Connected on a tag connector, M12 – VW3 A5 107, 108 Connected on a tag connector, 2 x M12 – (1) These values are given for a maximum switching frequency of 2.5 or 4 kHz depending on the rating. (2) Choke performance is ensured by not exceeding the cable lengths between the motor and the drive given in the table above. For an application with several motors connected in parallel, the cable length must include all tap-offs. If a cable longer than that recommended is used, the motor chokes may overheat. (3) The contact should be connected in sequence (used for signalling or controlling the line contactor). Maximum connection capacity VW3 A5 101, 102 and tightening torque VW3 A5 103
References: page 80
Dimensions: pages 108 to 110
Schemes: page 122
79 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 82
References
0
Variable speed drives for asynchronous motors
0
Altivar 61: Output filters Option: Motor chokes
Motor chokes For drives
Maximum length Loss of motor cable (1) Shielded Unshielded m m W
Nominal Sold current in lots of
Unit reference
A
Weight kg
3-phase supply voltage: 200…240 V 50/60 Hz
VW3 A5 101
ATV 61H075M3…HU22M3
150
300
150
12
–
VW3 A5 101
5.500
ATV 61HU30M3…HU75M3
200
260
250
48
–
VW3 A5 102
8.000
300
300
350
90
–
VW3 A5 103
10.000
ATV 61HD11M3X…HD22M3X
150
300
350
90
–
VW3 A5 103
10.000
ATV 61HD30M3X…HD45M3X
150
300
430
215
3
VW3 A5 104
17.300
ATV 61HD55M3X, HD75M3X
150
300
475
314
3
VW3 A5 105
29.600
ATV 61HD90M3X
250
300
530
481
3
VW3 A5 106
44.400
75
90
150
12
–
VW3 A5 101
5.500
85
95
250
48
–
VW3 A5 102
8.000
160
200
350
90
–
VW3 A5 103
10.000
85
95
250
48
–
VW3 A5 102
8.000
160
200
350
90
–
VW3 A5 103
10.000
200
300
430
215
3
VW3 A5 104
17.300
140
170
350
90
–
VW3 A5 103
10.000
150
300
430
215
3
VW3 A5 104
17.300
97
166
350
90
–
VW3 A5 103
10.000
200
300
430
215
3
VW3 A5 104
17.300
ATV 61HD45N4…HD75N4
150
300
430
215
3
VW3 A5 104
17.300
ATV 61HD90N4
200
300
430
215
3
VW3 A5 104
17.300
ATV 61HC11N4, HC13N4
150
250
475
314
3
VW3 A5 105
29.600
ATV 61HC16N4
250
300
530
481
3
VW3 A5 106
44.400
ATV 61HC22N4
250
300
530
481
3
VW3 A5 106
44.400
ATV 61HC25N4
200
250
598
759
3
VW3 A5 107
64.500
ATV 61HC31N4
200
250
598
759
3
VW3 A5 107
64.500
200
250
598
759
3
VW3 A5 107
64.500
250
300
682
1188
3
VW3 A5 108
99.200
ATV 61HC50N4
250
300
682
1188
3
VW3 A5 108
99.200
ATV 61HC63N4
250
300
682
1188
3
VW3 A5 108
99.200
3-phase supply voltage: 380…480 V 50/60 Hz ATV 61H075N4…HU40N4
ATV 61HU55N4…HD18N4
ATV 61HD22N4…HD30N4
ATV 61HD37N4
ATV 61HC40N4
Motor P 355 kW Motor P 400 kW
(1) Maximum length given for a switching frequency of 2.5 or 4 kHz depending on the rating of the fan, see Characteristics on page 79.
Presentation: pages 78 and 79
Characteristics: page 79
Dimensions: pages 108 to 110
Schemes: page 122
80 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Page 83
References (continued)
0
Variable speed drives for asynchronous motors
0
Altivar 61: Output filters Option: Motor chokes
IP 20 protection kits Description
For filters
Reference
Mechanical device consisting VW3 A5 104, 105 of an IP 20 cover and cable clips VW3 A5 106…108
Presentation: pages 78 and 79
Characteristics: page 79
Dimensions: page 110
VW3 A9 612
Weight kg –
VW3 A9 613
–
Schemes: page 122
81 Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com